Você está na página 1de 4

JAC Series Pneumatic Control Drive


Stable driving of final control elements
such as dampers and vanes

JAC series control drives are


pneumatic actuators designed to
control stably for long period air
flow control dampers, vanes, fluid
coupling scoop tubes and others
used for power generation and
industrial boilers.


01

— Features: Input / Output:


01 JAC
• Selectable from 5 models by required torque • 4-20mA/20-100kPa/19.6-98.1kPa
• High reliability with simple structure • Position transmitter with 4-20mA output
• Wide range of options such as positioners • HART communication
• Cylinder position holdable in case of loss of • Limit Switches
air supply • Position indicator at site
• Manual operation function provided as standard
• Explosion proof available
• Easy maintenance

Items Specifications

Operating angle range 90° (can be limited with an optional stopper)

Minimum Rating torque JAC05: 542 Nm, @Supply air pressure 0.35MPa
JAC10: 960 Nm, Max. supply air pressure 0.35MPa
JAC20: 2030 Nm, Max. supply air pressure 0.35MPa
JAC50: 5423 Nm, Max. supply air pressure 0.53MPa
JAC60: 6260 Nm, Max. supply air pressure 0.53MPa

Positioner Pilot positioner (P/P), TZIDC positioner (I/P, HART)

Input signal (to be selected) 4~20mA /20~100kPa /19.6~98.1kPa

I/O characterization Linear /Square / Square root / Others

Operating Temperature –5~60̊ C/-5~80̊ C (-20̊ C possible with optional heater)

Air failure function Auto reset (standard) / On site reset /Remote reset

Position transmitter (option) External RQ transmitter / Embedded transmitter in TZIDC positioner

Limit switch (Option) Contact rating : 5A-250VAC /0.4A-125VDC /0.2A-250VDC

Tube material Copper /Insulated copper/Stainless /Nylon


Dimensions

JAC 05/10 W490 x D535 x Height of shaft


H925 724mm

JAC 20: W490 x D928 x Height of shaft


H1276 1035mm

JAC 50 W622 x D1094 x Height of shaft


H1230 924mm

JAC 60 W622 x D1244 x Height of shaft


H1320 924mm

JAC 50

622

289
914
442
400

300

250

(180)

1230
520

924
87

521 106 181

590 759
Nomenclature Contents
JAC □ □ □ B □ - □ □ □ □ - □ - □ - □ Pneumatic control drive
Rated torque, Drive lever travel, Stroke time
Rated torque Nm Drive Stroke time sec. (at no load) Old ver.
Air supply pressure kPa lever PILOT AV TZIDC type AC
travel Positione Positione Positione
280 350 530
05 380 542 - 90 5±3 5±3 Less AC0608
than 11
10 670 960 - 90 10±3 8±3 Less -
than 18
20 1353 2030 - 90 20±3 15±3 Less AC0816
50 2030 3050 5423 90 13±3 17±3 than 20 AC1016
60 3240 4085 6260 90 19±3 21±3 -
Positioning mechanism
V AV Positioner
P PILOT Positioner
T TZIDC Positioner
C TZIDC200 Positioner
S Solenoid valve [on - off Action]
N None
Input signal Available positioner
AV PILOT TZIDC TZID- C200 Solenoid valve None
Positioner Positioner Positioner
0 None X X X X O O
1 20~100kPa O O X X X X
2 4~20mA O X O O X X
A 20.7~186.2kPa O O X X X X
B 20.7~103.4kPa O O X X X X
C 19.6~ 98.1kPa O O X X X X
B Design
Ambient temperature
1 Basic model: -5 to 60 degree C (-20 to 60 degree C with space heater)
2 High temperature model: -5 to 80 degree C (-20 to 80 degree C with space heater)
Space heater
0 None
1 With heater
Air failure lock
1 Auto reset
2 Local reset
3 Remote reset
Stopper (non-releasable)
0 None
1 Min stop NOTE: Min. & Max. Stop display in case of direct action. In case of reverse
2 Max. stop action Min.
& Max. Stop are opposite upper and lower.
3 Min. & Max. Stop
Position transmitter
N None
A Type RQ position transmitter (4 to 20mADC output)
B Type JEDRQ explosion proof position transmitter (4 to 20mADC output)
E Pneumatic position transmitter (output: the same as input signal of pneumatic positio
F Transmitter billed in TZIDC /TZIDC-200 positioner (4 to 20mADC output)
Nomenclature Contents
JAC □ □ □ B □ - □ □ □ □ - □ - □ - □ Pneumatic control drive
Alarm contacts
Q’ty For (PART No.) Contents
N 0 None None
S1 2 Basic type Electrical rating 5A /125VAC, 0.4A /125VDC
S2 4 (J99931164-□) (at resistant load) 5A/ 250VAC, 0.2A/ 250VDC
Relay type terminal blocks in front of drives, Switch Q’ty 1 or
2, Simultaneous operation type /Center neutral type
SE1 2 Explosion proof type Electrical rating 5A /125VAC, 0.4A /125VDC
SE2 4 (J9993273-□) (at resistant load) 5A/ 250VAC, 0.2A/ 250VDC
Relay type terminal blocks in front of drives, Switch Q’ty 1 or
2, Simultaneous operation type /Center neutral type
L1 2 Basic type Electrical rating 5A /125VAC, 0.4A /125VDC
L2 4 (J99931164-□) (at resistant load) 5A/ 250VAC, 0.2A/ 250VDC
Relay type terminal blocks in front of drives, Switch Q’ty 1 or
2, Simultaneous operation type /Center neutral type
Tubing
Internal tubing External tubing
00 Copper tube None
02 Stainless steel tube
03 Plastic covered copper tube
10 Nylon tube *1 None
12 Stainless steel tube
13 Plastic covered copper tube
20 Stainless steel tube None
22 Stainless steel tube
30 Plastic covered copper tube None
32 Stainless steel tube
33 Plastic covered copper tube

Special specifications
R Mounted pressure regulator
P Special paints
L Special operating lever
X Others

NOTE: SPECIAL SPECIFICATION “X”


If special specification other than listed herein is re-
quired, designation “X” shall be affixed to applicable
column.
For example, if JAC05P requires special input signal,
its designation shall be indicated as JAC05PXB...
*1 Note: Flexible Tube (Nylon Tube) can be used un-
der 60 degree C

3AUA0000080942 REV A 18.5.2010 #14995

— —
ABB Bailey Japan Limited We reserve the right to make technical We reserve all rights in this document and in
Marketing & Sales changes or modify the contents of this the subject matter and illustrations contained
511 Baraki Izunokuni-shi document without prior notice. With re gard therein. Any reproduction, disclosure to third
Shizuoka 410-2193, Japan to purchase orders, the agreed particulars parties or utilization of its contents in whole
TEL +81(0)55-949-8824 shall prevail. ABB does not accept any or in partsis forbidden without prior written
FAX +81(0)55-949-1114 responsibility whatsoever for potential errors consent of ABB Bailey Japan.
jpbai.communications@jp.abb.com or possible lack of information in this copyright © 2018 ABB Bailey Japan
document. All rights reserved
www.abb.co.jp

Você também pode gostar