Você está na página 1de 15

PANEL 3

ACU
1ST FLOOR
2ND FLOOR

24

27

27

24 ACU

24

CIRCUIT NO. LOAD DESCRIPTION VOLTS


1 20-2x39W Fluorescent Lamp 230
2 20-2x39 W Fluorescent Lamp 230
3 20-2x39 W Fluorescent Lamp 230
4 20-2x39 W Fluorescent Lamp 230
5 9-2x39 W Fluorescent Lamp 230
6 11-2x39 W Fluorescent Lamp 230
11 7 8-2x39 W Fluorescent Lamp 230
8 SPARE 230
9 SPARE 230
10 space
7 11 8-2x39 W Fluorescent Lamp 230

8-2x39 W Fluorescent Lamp

SPARE
CIRCUIT NO. LOAD DESCRIPTION VOLTS
1 1-2 HP ACU Split Type (Inverter) 230
2 1-2 HP ACU Split Type (Inverter) 230
3 1-2 HP ACU Split Type (Inverter) 230
4 1-2 HP ACU Split Type (Inverter) 230
5 1-2 HP ACU Split Type (Inverter) 230
6 1-2 HP ACU Split Type (Inverter) 230
7 1-2 HP ACU Split Type (Inverter) 230
8 1-2 HP ACU Split Type (Inverter) 230
9 1-2 HP ACU Split Type (Inverter) 230
10 1-2 HP ACU Split Type (Inverter) 230
11 1-2 HP ACU Split Type (Inverter) 230
12 1-2 HP ACU Split Type (Inverter) 230
13 1-2 HP ACU Split Type (Inverter) 230
14 1-2 HP ACU Split Type (Inverter) 230
15 1-2 HP ACU Split Type (Inverter) 230
16 1-2 HP ACU Split Type (Inverter) 230
17 1-2 HP ACU Split Type (Inverter) 230
18 1-2 HP ACU Split Type (Inverter) 230
19 1-2 HP ACU Split Type (Inverter) 230
20 1-2 HP ACU Split Type (Inverter) 230
21 1-2 HP ACU Split Type (Inverter) 230
22 1-2 HP ACU Split Type (Inverter) 230
23 1-2 HP ACU Split Type (Inverter) 230
24 1-2 HP ACU Split Type (Inverter) 230

TOTAL
PANEL 1 PANEL 2

LIGHT OUTLET

21 19 64

21 25 73

21 25
21 LIGHT 20 OUTLET
3 ACU 2 LIGHT
2 ACU

24 24

PANEL BOARD 1
AMPERE CIRUIT BREAKER
VA LOAD
AB CA BC POLE
1560 6.78
1560 6.78
1560 6.78
1560 6.78
702 3.05
858 3.73
1560 6.78
1560 6.78
1560 6.78
0
624 2.71

1560

0
12
0
20.34 19.32 17.29
AVERAGE 18.9842028986
AB -1.3584057971
CA -0.3357971014
BC 1.6942028986

% UNBALANCED 0.0892427724
8.9242772404

PANEL BOARD 3
AMPERE CIRUIT BREAKER
VA LOAD
AB CA BC POLE
2760 12
2760 12
2760 12
2760 12
2760 12
2760 12
2760 12
2760 12
2760 12
2760 12
2760 12
2760 12
2760 12
2760 12
2760 12
2760 12
2760 12
2760 12
2760 12
2760 12
2760 12
2760 12
2760 12
2760 12

66240 96 96 96

AVERAGE 96
AB 0
CA 0
BC 0

% UNBALANCE 0%

MAIN DISTRIBUTION PANEL


PHASE
PANEL NO. LOAD DESCRIPTION VA LOAD
AB CA
1 LIGHTING PANEL 18400 27.5 25.8
2 POWER PANEL 29880 44.1 43.4
3 MOTOR LOADS 66240 96 96
TOTAL 114520 167.6 165.2
PANEL BOARD 1
AB CA BC

38.1 36.4 37.5

AVERAGE 37.3333333333

A -0.7666666667 %UNBALANCED
B 0.9333333333
C -0.1666666667

PANEL BOARD 2

AB CA BC

CIRUIT BREAKER
SIZE OF WIRE AND CONDUIT
AT AF
IT BREAKER
SIZE OF WIRE AND CONDUIT
AT AF
BUTION PANEL
PHASE
SIZE OF WIRE AND CONDUIT
BC POLE
26.9
42.6
96
165.5
q
0.025
2.5 %

CIRCUIT NO. LOAD DESCRIPTION


1 1 6-180 W Convenience Outlet
2 6-180 W Convenience Outlet
3 6-180 W Convenience Outlet
4 6-180 W Convenience Outlet
5 5 6-180 W Convenience Outlet
6 6-180 W Convenience Outlet

4
9
10
11
12
13
14
15
16
17
18
19
20
21 21

22 22
TOTAL
PANEL BOARD 2
AMPERE
VOLTS VA LOAD
AB CA BC
230 1080 4.7
230 1080 4.7
230 1080 4.7
230 1080 4.7
230 1080 4.7
230 1080 4.7
6480 9.4 9.4 9.4

AVERAGE 9.4
AB 0
CA 0
BC 0

% UNBALANCE 0
0
N

1 1 5.5
2 6 4.7
3 7 6.3
4 8 3.1
5 5 6.3
6 2 5.5
7 3 4.7
8 4 6.3
9 9 4.7
10 10 4.7
11 11 4.7
12 12 4.7
13 13 4.7
14 14 4.7
15 15 4.7
16 16 4.7
17 17 4.7
18 18 4.7
19 19 4.7
20 20 12
21 21 12
22 22 12

44.1 43.4 42.6


CIRUIT BREAKER
SIZE OF WIRE AND CONDUIT
POLE AT AF
\

5.5