MASTER TRIP RELAY

The Stelmec make Master Trip Relay SLR JH13 is an Electromechanical High Speed Tripping Relay used
in tripping and signaling circuits of protective relays, where a high degree of reliability & high contact
rating is required. It is an instantaneous switching element that is used for Contact multiplication of
Protection relays of Circuit Breakers, thereby providing number of simultaneous instantaneous
switching operations.

Salient Features

• Conforms to IS 3231:1981
• High Speed Operation
• Electro Mechanical Design
• Hand Reset Contacts
• Hand Reset Mechanical Flag
• Heavy Duty Contacts: 1250 VA
• 10,000 Mechanical operations
• Flush Panel Mounting
• 2 elements and 3 elements relay also available
Dimensions

• Front Bezel: 152×92 mm


• Cut Out: 130×72 mm
SLR JH13 stelmec
beyond boundaries

Description

A fast operating, multi-contact, attracted armature relay with a The Mechanical interlock operates & Relay remains in lock out
high degree of mechanical stability, Type SLR JH13 has position until it is hand reset.
hand-reset contacts and an operating coil cut-out contact. A mechanically operated hand reset type flag, is provided as an
The control coil of the relay element is wound with super operation indicator. White for reset position & Red for Lock out
enamelled copper wire with a short time thermal rating so that indication.
the relay has a very fast operation with operation time < 10ms. The contacts are designed to have superior contact rating with
A coil cut-off contact (NC contact of same element) with minimum wear and tear.
suitable break rating is internally wired in series with the coil. The elements are mounted in compact, non-drawout case,
This makes coil operation momentary & disconnects the coil on suitable for flush mounting on panels.
operation.

Technical Specifications

Coil Rating 24/30, 110, 220V DC/AC


Operating Range 50 to 120% of rated voltage
Operating Time <10 ms at nominal rated voltage
Rated Burden <45 Watts
Operational Indicator Mechanical flag (HR type)
Mounting Flush
Contacts Upto 7 pair combinations (NO/NC)
Standards IS 3231:1981

Make & Carry Make & Carry for 3 sec. Break


AC 1250 VA with max. of 5A & 660 Volts 7500 VA with max. of 30A & 660 Volts 1250 VA with max. of 5A & 660 Volts
DC 1250 W with max. of 5A & 660 Volts 7500 W with max. of 30A & 660 Volts 100 W Resistive, 50 W Inductive
for 5A / 660V

Wiring Diagram Terminal Arrangement

• There is a continuous effort at Stelmec to keep abreast of latest technology inline with customers’ requirement.
• All these activities are followed as per ISO 9001 : 2008.
Contact:
SBU: Stelmec Limited, Power IT Solution Division, Plot No. 14/15, Western Express Highway No. 8, Sativali, Vasai (E), District: Thane - 401 208.
Tel. No. +91-250 6452377/6454150
CORPORATE: Stelmec Limited 'Sea Queen', 43-A, H.K. Bhabha Road, Bandstand, Bandra (W), Mumbai - 400 050.
Tel: +91 22 2643 6127 / 28 / 29 | Fax: +91 22 2643 6139 | E-mail: corporate@stelmec.com
website: www.stelmec.com

Você também pode gostar