Escolar Documentos
Profissional Documentos
Cultura Documentos
(-2) revision
08 2016
Presigo PDT...(-2)
Pressure transmitters for HVAC applications
DIP-switch
The transmitter features one or two DIP-switches for
setting up suitable pressure range, output function and
damping time factor. If the DIP-switch settings are
changed, all changes will take effect immediately.
Models
Model Pressure range (Pa) Number of sensors
PDT12 PS1 0…1250
PDT25 PS1 0…2500 One
PDT75 PS1 0…7500
PS1 0…1250
PDT12S25-2 Two
PS2 0…2500
PS1 0…1250
PDT12S75-2 Two
PS2 0…7500
*PS = Pressure sensor
Accessories
Model Description
ANS-1 2 m plastic tube and two pressure outlets
ANS-12 4 m plastic tube and four pressure outlets
Technical data
Supply voltage 24 V AC/DC ±15 %
Protection class IP54
Calculated power consumption
0...10 V mode 2 VA (rms) / min. trafo size 7.5 VA
4...20 mA mode 2.7 VA (rms) / min. trafo size 9 VA
Overall accuracy, pressure ≤ 1 % full scale
Annual deviation (typical)
P1250 models ±2 Pa
P2500 models ±4 Pa
P7500 models ±20 Pa
Damping (settable) 1, 2, 4 and 8 s
Operating temperature range -25…+50°C
Operating humidity Max. 95 % RH (non-condensing)
Overvoltage on any terminal Max. ±18 V (referenced to GND)
2
Presigo PDT...(-2)
Dimensions
+
1 2
40
120
112
(mm)
Wiring
�
�
ON
ON
ON
Pushbutton Pushbutton
DIP-switch DIP-switches 1 (left) and 2 (right)
�
�
�
Sensor 1 Sensor 1
1 2 3 4 1 2 3 4 5 6
1 2 3 4 5 1 2 3 4 5 6
Sensor 2
UO2
+
+ +
UO1 UO1
24V AC/DC
+ 24V AC/DC
+ 0...10 V
or
or DC ±15 % or DC ±15 %
- 0...10 V
- 4...20 mA
or
4...20 mA
Fig. 1: Wiring for models with one sensor Fig. 2: Wiring for models with two sensors
Product documentation
Document Type
Instruction Presigo PDT...(-2) Instruction for PDT...(-2)