GAS-FILLED INSTRUMENT TRANSFORMERS

TG Combi 362/420 kV combined current


and voltage transformer
Compact solution for enhanced safety
and reliability
TG Combi 362/420 kV is suitable
for revenue metering and
protection, in applications such
as independent wind and solar
installations, and high energy
using industries.

Features Benefits
• Low partial discharge levels • Reduced footprint − two functions in one
• Explosion proof IPC Class II capable design • High accuracy in extended range
equipped with rupture disk • Increased substation safety
• Temperature compensated gauge with two level • Cost-efficient savings in transportation, erection
gas alarm and commissioning
• Rugged corrosion resistant housing and polymer • Safety margin for normal wind loads, stress from
insulator conductors and seismic forces
• Multiple-turn primaries for lower primary currents • Robust design for minimum maintenance and lower
leakage rates than IEEE/IEC standards

TG COMBI [unit] TG COMBI 362 TG COMBI 420


Rated frequency [Hz] 50 - 60
Highest voltage for equipment [kVr.m.s.] 362 420
Rated power-frequency withstand voltage [kVr.m.s.] 575 630
Rated lightning impulse withstand voltage [kVpeak] 1300 1425
VT - Rated overvoltage factor 120% continuous 190% - 30s
Metering Cores 0.2 (200 VA)
Protection Cores 3P (200 VA)
Thermal burden 1500 VA
CT - Rated primary current A up to 4000
Rated overcurrent factor 120% continuous
Rated short-time thermal current and duration kA - s 50 (2) 63 (1)
Rated dynamic current kA 164
Metering Cores N/A 0.2s (40 VA)
Protection Cores N/A 5P (40 VA)
Insulator: Material N/A composite - grey
[-30;+40] (SF6 only)
Min - Max operating temperature (shade conditions) [°C]
[-60;+40] (SF6 +N2)
TG COMBI [unit] TG COMBI 362 TG COMBI 420
A - Overall height mm 4450 5450
B - Primary terminal height mm 3150 4165
C - Lowest live part mm 2760 3780
D - Highest grounded part mm 480 480
E - Overall depth mm 1265 1265
F - Mounting holes interax mm 470 470
G - Mounting holes interax mm 470 470
H - Mounting holes diameter mm 24 24
Strike minimum mm 2200 3320
Creepage minimum mm 9050 13020
Weight (without gas) kg 1350 1400
SF6 weight at rated pressure (100%SF6) kg 25 30

2GJA708516 - Rev. -, en - Leaflet - 2017-06 - (TG Combi 362/420 kV combined current and voltage transformer) (gs)

— —
ABB S.p.A. We reserve the right to make technical We reserve all rights in this document and
Unità Operativa Adda changes or modify the contents of this in the subject matter and illustrations con-
Via dei Ceramisti, snc – Loc. S. Grato document without prior notice. With re- tained therein. Any reproduction, disclo-
I-26900 Lodi (LO), Italy gard to purchase orders, the agreed par- sure to third parties or utilization of its
Phone: +39 037 145.1 ticulars shall prevail. ABB AG does not ac- contents – in whole or in parts – is forbidden
E-mail: IT-motordrive.qa@abb.com cept any responsibility whatsoever for without prior written consent of ABB AG.
potential errors or possible lack of infor- Copyright© 2017 ABB
mation in this document. All rights reserved
www.abb.com/highvoltage

Você também pode gostar