Release Notes

( 9701-VWSx ) FactoryTalk View® Site Edition is a supervisory HMI software package for enterprise solutions. [FTView,
FTViewSE
Version 11.00.00 (released 2/2019)

Catalog Number FactoryTalk View Site Edition 

These release notes describe version information for FactoryTalk View Site Edition, version 11.00.00 (released 2/2019).

Requirements
This release has the following requirements.

FactoryTalk View SE works within the system requirements of all Rockwell Automation software products. For the latest information regarding software
platform support, refer to Rockwell Automation Product Compatibility and Download Center.

Hardware requirements

For the optimal performance of FactoryTalk View SE applications, the personal computer is recommended to meet or exceed the following hardware
requirements.

Type Description CPU RAM


Operator Workstation FactoryTalk View SE Client Intel® Core™ i5 Standard 4 GB
or Power processor
FactoryTalk View SE Station
Engineering FactoryTalk View Studio Intel Core i5 Standard 8 GB
Workstation Enterprise Power processor
RSLinx Classic
FactoryTalk Linx
Studio 5000
Application Server FactoryTalk View SE Server Smaller systems:
FactoryTalk View Studio Intel Core i5 Standard 4 GB
Enterprise Power processor
FactoryTalk Alarms & Events Tag Medium to larger 8 GB
Based Server  systems:
FactoryTalk Linx Data Server with Quad core Intel Core Xeon
FactoryTalk Alarms and Events family processor
enabled

Software requirements

Operating systems

FactoryTalk View SE is tested on the following operating systems:

Windows 10 Enterprise*
Windows 10 Professional* 
See the Windows Lifecycle FAQ and Windows as a Service (WaaS) topics on the Microsoft® Web site for details regarding servicing requirements
and other important information.
Windows 10 Semi-Annual Channel v1709, v1803, and v1809 
Windows 10 Semi-Annual Channel is governed by the Microsoft Modern Lifecycle Policy. Refer to the Microsoft Web site for details.
Windows 10 IoT Enterprise 2016 Long-Term Servicing Channel 
Windows 10 Long-Term Servicing Channel is governed by the Microsoft Fixed Lifecycle Policy. Refer to the Microsoft Web site for details.
Windows 10 IoT Enterprise 2016 Long Term Servicing Branch (LTSB) Embedded**
Windows Embedded 8.1 Industry Pro
Windows 7 Ultimate with Service Pack 1
Windows 7 Enterprise with Service Pack 1
Windows 7 Professional with Service Pack 1
Windows Server 2016 Standard*
Windows Server 2016 Datacenter*
Windows Server 2012 Standard
Windows Server 2012 Datacenter
Windows Server 2012 R2 Standard
Windows Server 2012 R2 Datacenter
Windows Server 2008 R2 Standard with Service Pack 1
Windows Server 2008 R2 Enterprise with Service Pack 1

* For more information, see Answer ID 964391 for Windows 10 support and Answer ID 991031 for Windows Server 2016 support in the Rockwell Automation
Knowledgebase.

** This operating system is supported with the Allen-Bradley® 61xx family of industrial computers and CompactLogix™ 5480 family of controllers.
Domain controller requirements

The following operating systems are supported for use as domain controllers for FactoryTalk View SE client computers. Using a domain is recommended for
applications that include more than 10 computers. If your application includes 10 or fewer computers, they can be organized in a workgroup.

Windows Server 2016 Standard
Windows Server 2016 Datacenter
Windows Server 2012 Datacenter
Windows Server 2012 R2 Datacenter
Windows Server 2012 Standard
Windows Server 2012 R2 Standard
Windows Server 2008 R2 Standard with Service Pack 1
Windows Server 2008 R2 Enterprise with Service Pack 1

Features
This release includes the following system features.

New features

FactoryTalk AssetCentre integration
Automates backups and manages versions of FactoryTalk View SE network applications with integration to FactoryTalk AssetCentre disaster
recovery.
Pulls FactoryTalk AssetCentre log information including Audit, Information, Warning, and Error and shows on TrendPro.

TrendPro
Traces with historian data can be added from OSIsoft® PI Server™. FactoryTalk Historian is not required to be installed.
The plot area's background color can be configured to align with ISA-101 styles.
Supports the use of tag values for the y-axis scale.
Supports SaveTemplate, DeleteTemplate, and ApplyTemplate methods to manage templates through VBA.

Pinned popup 
Provides the ability to temporarily pin an on-top display. Once a display is pinned, it will remain on top even when navigating to other displays.

FactoryTalk Diagnostics Viewer object 
Provides the native control to view FactoryTalk Diagnostics on HMI displays.

VBA interface for HMI tag database 
Provides the HMI TagDB object model, similar to RSView®32, to access and manage HMI tags through VBA.

Electronic signature
Embeds the functionality on the command button, numeric input, and string input objects.
Supports single and counter signatories.

Enhanced features

License simplification for ThinManager® 
One FactoryTalk View SE client license can enable the delivery of multiple SE client sessions to a terminal in ThinManager.

RecipePro+
A tag is updated with the recipe name after the download operation is successfully completed.
Audit messages for the download operation is streamlined to eliminate unnecessary messages.

FactoryTalk View SE Application Manager 
Formerly known as Distributed Application Manager, manages all types of SE applications (network distributed, network station, and local station) with
one tool.

Supports the disabled appearance for the numeric input and string input objects. Typically use the option to restrict access to the objects at run time.

Provides the AE_ActiveEvents function to get the number of FactoryTalk Alarms and Events active server-based events.

Installation
Provides the FactoryTalk Updater utility to assist the management of installed Rockwell Automation software by announcing new versions and
patch roll-ups.
Supports Modify and Repair from the Install user interface to change the product installation and to run a repair operation on installed
products.

Corrected Anomalies
This release corrects the following anomalies.

When using the PlantPAx Library for Multiple Analog Input AOI, if all the configured Process Variables Inputs are bad, the output value will equal
1.#QNAN. The PlantPAx faceplates show the wireframe with this value in FactoryTalk View Studio. First reported in version 7.00.00. [70341] 
In this release, the PlantPAx faceplates show the wireframe for invalid values and a message is logged in the Diagnostics Viewer to indicate the error.

TrendPro objects do not save the previous trace configuration when adding a new trace. First reported in version 9.00.00. [72832] 
In this release, the previous trace can be saved successfully.

The scroll bar is shown on the printed trend area when printing a Trend object. First reported in version 9.00.00. [76433] 
In this release, Trend objects are printed without scroll bar.
The FactoryTalk Administration Console crashes if using FactoryTalk View SE version 10.00 with FactoryTalk Services Platform version 6.10.00. First
reported in version 10.00.00. [80081] 
In this release, FactoryTalk Administration Console runs correctly.

The first time the displays are opened, the last button clicked will open that display in front of all others. When any of the displays are open at a later
time, they are shown behind any other displays that are already open. First reported in version 7.00.00. [81723] 
In this release, the display order shows correctly.

EventDetector.exe crashes when frequent EventOn and EventOff commands are used. First reported in version 8.20.00. [100940] 
In this release, it runs correctly without crash.

Engineering Units and caption are removed from the tag list after replacing the tag with a parameter. First reported in version 10.00.00. [102993] 
In this release, the Engineering Units and caption can be added successfully.

The parameter /RP for the command Display can be only converted to a pair of coordinates (x, x) instead of (x, y), where x and y are the coordinate
values of the popup window. First reported in version 10.00.00. [103732] 
In this release, the parameter /RP can be converted correctly.

The on-screen keyboard cannot be closed after entering values from the electronic signature button. First reported in version 8.20.00. [104251] 
In this release, the on-screen keyboard is closed after entering the value.

In the FactoryTalk View SE Client Wizard, after a user logs out the SE client and the login dialog box is displayed for the amount of inactivity period
configured, the automatic logout does not work if another user logs into the SE client. First reported in version 8.10.00. [122181] 
In this release, the automatic logout works correctly.

The length of a line is changed in a display after its LinkSize property is set to False in the global object. First reported in version 10.00.00. [123231] 
In this release, the length of straight lines shows correctly.

When using the Set command with /v, the string HMI tag that is pointed as a device tag to the PLC does not receive the value. First reported in version
10.00.00. [129064] 
In this release, the string tag receives the value correctly.

When adding FactoryTalk Historian tags to TrendPro using the Invoke command with the AddTrace method, the following error may be displayed: 
Missing Tag: "Historian tag name" 
First reported in version 9.00.00. [ 129986 ] 
In this release, the Historian tags can be added successfully.

The Login dialog is always shown on the primary monitor when multi-monitor is enabled. First reported in version 10.00.00. [ 130460 ] 
In this release, the dialog box is shown on the monitor where the command is issued.

After upgrading to FactoryTalk View 10.00.00, texts on string display objects that use IF-TEHN-ELSE logic may be truncated. First reported in version
10.00.00. [ 137504 ] 
In this release, to resolve this issue, manually change the dimensions of the string display object or use a proportional font. For more instructions, see
Answer ID 1082182  in the Rockwell Automation Knowledgebase.

FactoryTalk View Studio does not respond after adding an OLE object to a display and right-clicking any place inside the OLE object. First reported in
version 9.00.00. [ 139898 ] 
In this release, the shortcut menu of the OLE object shows and FactoryTalk View Studio works correctly.

The PDF generated by the PrintDisplay method is partially blacked out sometimes. First reported in version 9.00.00. [ 153420 ] 
In this release, the PDF is generated correctly.

The on-screen keyboard cannot be launched from the RecipePro + editor on the FactoryTalk View SE Client. First reported in version 10.00.00. [
181507 ] 
In this release, the Windows on-screen keyboard is displayed.

After upgrading to FactoryTalk Services Platform version 6.10.00, the CurrentUserHasGroup() function always returns False if the user is in the
Engineers or Maintenance group. First reported in version 8.00.00. 
In this release, the function can return the correct value.

Known Anomalies
This release The ACD detection mechanism may not detect the new device, with duplicated IP address, inserted in the middle of linear topology. One of the
device with duplicated IP address may bump out from the network. The workaround for the user is in making sure the new device does not have duplicated
IP with any existing device in the networkhas the following known anomalies.

Display client

FactoryTalk View SE Client does not respond 
When Alarm and Event Log Viewer is opened from the FactoryTalk View SE Client but cannot get events from the SQL Server database, the
FactoryTalk View SE Client does not respond for a few minutes. First reported in version 7.00.00. [344892] 
To resolve this problem, on the toolbar of Alarm and Event Log Viewer, click Stop to stop reading events from the database.

When login from ThinManager directly to FactoryTalk View SE Client, some warnings about the password do not show on FactoryTalk View SE Client.
For example, the password expires or will expire, or the password needs to be changed. First reported in version 10.00.00. [367304] 
To resolve the issue, check messages in FactoryTalk Diagnostics and follow the instructions accordingly.

When multiple SE clients are launched simultaneously on the same computer, the startup of the SE clients may not respond at the Loading Command
Server stage. First reported in version 8.10.00. [368162] 
To resolve the issue, check messages in FactoryTalk Diagnostics and follow the instructions accordingly.To resolve this issue, create a Windows batch
file and add a Pause 5 command between the launch of each SE client file. This will allow the start of each SE client to be offset from each other.
FactoryTalk View SE Application Manager

Timeout may occur when you perform backup or restore operation through an unstable or slow network. First reported in version 8.10.00. [355276] 
To resolve this issue, open the Registry Editor of the computer that runs the tool, update the registry key CompressTimeout to a value larger than
1200 and try again. The key is in HKEY_CURRENT_USER\Software\Rockwell Software\RSView Enterprise\DistributeApplicationManager\Settings.

Cannot overwrite all components in the HMI server 
During the restore operation, when overwriting components of a running HMI server, some components of the server may still exist in the HMI folder
after you restart the computer. This happens when the names of these components do not exist in the archived HMI file. First reported in version
8.10.00. [354220]

Find and Replace

East Asian languages do not show correctly 
There is a possibility that some object properties that are configured in character sets for East Asian languages such as Chinese or Japanese, will
display a question mark in the result list when you use the Find and Replace, Cross Reference or Undo feature. First reported in version 7.00.00.
[338894] 
To resolve this problem, go to Control Panel > Regional and Language Options, and select the appropriate language to match the language
version desired.

Graphic displays

Applying color animations to an object group as well as to the individual objects in the group causes unexpected behaviors. First reported in version
8.00.00. [346758] 
To set up color animations for an object group, either apply the color animations to the group, or to the individual objects in the group.

Graphic objects

Cannot register or unregister Microsoft ActiveX® Control objects 
When registering or unregistering an ActiveX Control object in FactoryTalk View Studio with User Account Control (UAC) enabled on the operating
system, an error message shows. First reported in version 8.00.00. [346124] 
To avoid this problem, before registering or unregistering an ActiveX Control object, do one of the following:
Turn off UAC and restart the computer
Run FactoryTalk View Studio as administrator

Cannot save animation expression changes 
If the expression setting for the animation property of the base object is empty when you change the LinkAnimation property of a reference object to
Link without expressions and change the expression setting for the animation property, the expression setting change cannot be saved. First reported
in version 6.00.00. [272937] 
To avoid this issue, fill in a valid value in the expression setting for the animation property of the base object first.

If you copy and paste a PNG image into an application, the image might appear blurred. First reported in version 7.00.00. [337726] 
To avoid this issue, import the image into the Image folder first, and then insert the image into the application from the Image folder.

The caption of Signature button does not support language switching. [367600]

HMI server

VBA execution may pause temporarily while an HMI server is replicating. First reported in version 7.00.00. [361749]

During replication some project information may fail to replicate to secondary servers. First reported in version 8.00.00. [347733] 
To resolve this issue, restart these secondary servers and replicate again. If the replication still fails, cancel the redundancy configuration and delete
HMI project from secondary servers, restart secondary servers, and configure the redundancy again.

If you configure NIC speed remotely, to Auto, (rather than to 100 Mb Full), it doubles the amount of time to open the tag editor. First reported in
version 6.10.00. [270579] 
To avoid this issue, we recommend that you configure NIC speed to the highest value possible.

HMI project folder does not replicate to secondary HMI Server. This issue can be caused by a couple of situations. One cause could be the size of the
HMI project file being larger than the maximum allowable file transfer size. The other cause could be the replication taking longer than the default time
limit of 20 minutes. 
To resolve this issue, change the limit size to an acceptable value or set the limit time to a larger value. For more instructions, see Answer ID 38407 in
the Rockwell Automation Knowledgebase.

The following issues may happen because of the security enhancements in FactoryTalk View SE:
After replicating from primary to secondary or restarting the secondary HMI server, the secondary HMI server stops responding in the Starting
state for a while and returns to Active.
The error The primary directory <> is either unavailable or unwritable is shown when executing the DataLogOn command.

First reported in version 9.00.00. [153380] 
To resolve these issues, make sure the user LOCAL SERVICE has access to the particular folder you are writing your datalog models to. For more
instructions, see Answer ID 1082286  in the Rockwell Automation Knowledgebase.

Installation

Cannot continue with the installation because of IIS 
If you have mapped IP addresses to host names in the C:\WINDOWS\system32\drivers\etc\hosts file, the invalid mapping could stop IIS from being
installed. The following message is displayed: 
IIS is not installed correctly. Install cannot continue. 
First reported in version 7.00.00. [338385] 
To resolve this issue, update the entries in the hosts file to include the correct IP addresses and host names. Alternatively, place a # symbol in front of
the entries so that they are not used and are not validated as part of the IIS installation.
The Client Install Portal feature cannot be added or installed in the Program Maintenance mode from Control Panel. First reported in version 8.10.00.
[346940] 
To avoid this issue, make sure to select the Client Install Portal check box at the first time if you plan to use this feature.

When upgrading FactoryTalk View version 6.00 or 6.10 to 9.00, the following message may be shown: "The following installed products are dependent
on this installed package and may not function properly if this package is uninstalled:" First identified in FactoryTalk View version 9.00.00. [363810] 
To resolve this problem, click Yes in the dialog box and continue with the upgrade.

Operating systems

When running FactoryTalk View SE redundant applications on Windows 10 Professional or Enterprise v1607 operating systems, initiating a network
connectivity break by disabling NIC adaptors in Device Manager can cause application failures requiring a restart of the application. This issue was
introduced in the Windows 10 v1607 feature build. First reported in version 9.00.00. [363223] 
To avoid this problem, run the Microsoft Hotfix KB3201845 outlined in https://support.microsoft.com/en-us/kb/3201845. 
Alternatively, you can run Windows 10 v1703 or other supported operating systems where this issue is not present. 
For more information about Windows 10 operating system support, see Answer ID 964391  in the Rockwell Automation Knowledgebase. 
For more information about Windows Server 2016 operating system support, see Answer ID 991031  in the Rockwell Automation Knowledgebase.

Slow network communication performance because of IPv6 
If IPv6 is not supported or is disabled in your network environment, when you use FactoryTalk View Studio on Windows 8.1, Windows 8, Windows
Server 2012 R2, or Windows Server 2012, the network communication performance may be slow. First reported in version 8.00.00. [347310] 
To resolve this issue, you may need to disable IPv6 on your computer or enable IPv6 in your network environment. Contact your IT department for
details.

System and HMI tags are wireframed 
If your system is experiencing HMI tag failures and wireframing, you may have a port conflict. Check the event log for the message: "Unable to
establish connection with Live Data using TCP/IP protocol. Port may be in use by another process. " The HMI tag failures
could occur on any operating system but due to dynamic port range changes, this issue could occur more often on Windows 7 or Windows Server
2008. First reported in version 5.10.00. [264248] 
To resolve this, you will need to manually change the port. See Answer ID 61064  in the Rockwell Automation Knowledgebase for additional
information on how to do this.

On Microsoft Surface® tablets, the press and hold gesture may not open a component’s menu if the component is a text box. First identified in
FactoryTalk View 9.00.00. [362400] 
To avoid this problem, use a mouse and right-click the component to open the menu.

ODBC databases

The datalog cannot log data 
If a FactoryTalk View SE datalog becomes disconnected from a remote ODBC database and then eventually becomes reconnected, it fails to continue
logging data to the ODBC database. First reported in version 8.20.00. [359289] 
To resolve this issue, follow the steps below:
1.  In the datalog configuration, specify a backup ODBC database. If a disconnection occurs to the primary ODBC database, the logging of data will
now continue to the backup ODBC database.
2.  The connection to the primary ODBC database has recovered and you do not have a backup ODBC database configured. To make the datalog
resume logging to the primary ODBC database, issue the command Datalogoff <name of datalog> and then the command Datalogon
<name of datalog> .

See Answer ID 747699 in the Rockwell Automation Knowledgebase for additional information.

Software components

Cannot restore KEPServer 
Updating to the new KEPServer Enterprise version, V5.7, may require updating the OPC Data Server configuration after a restoring an application file.
First reported in version 6.10.00. [276028] 
To resolve this issue, on the OPC Data Server configuration tab, update the computer name then restart the computer before browsing for the new
Prog ID for KEPServer Enterprise.

Trend objects

If FactoryTalk View uses FactoryTalk Linx as the communication server, the Trend object cannot display historical values of SINT tags. First reported in
version 7.00.00. [266629] 
To resolve this issue, do any of the following:
Create an HMI tag that points to the SINT tag, and then display the historical value of this HMI tag in the trend.
Change the data type of the SINT tag to INT, DINT, or REAL.

Timeout may occur when you try to load large amounts of data points from an ODBC data source such as SQL Server, and the Trend object does not
show the historical data. First reported in version 7.00.00. [343026] 
To resolve this issue, open the Registry Editor, update the key DatalogOdbcDbTimeout to a larger value in the following two locations, and try again:
HKEY_USERS\.DEFAULT\Software\Rockwell Software\RSView Enterprise\Data Log
HKEY_USERS\S-1-5-18\Software\Rockwell Software\RSView Enterprise\Data Log

TrendPro objects

One hour datalog data is not displayed on the trend chart 
When switching from Daylight Saving Time back to Standard Time, you will see two 1:00 hours on the trend chart of a TrendPro object. If you trend
data from data logs, one hour data is not displayed on the trend chart and seems to be lost. All data actually is in the database and no data is lost.
First reported in version 9.00.00. [363699] 
To view the data that is not displayed, add a real-time trace to the chart. For more information, see Rockwell Automation Knowledgebase Answer ID
39658.

Functional Changes
This release has the following functional changes from the previous release.

DeskLock utility

FactoryTalk View has enhanced the security of the utility. We strongly recommend that you reconfigure the utility to secure your system.

FactoryTalk View ME Application Manager

Application Manager is renamed to FactoryTalk View ME Application Manager and supports ME applications only.

FactoryTalk View SE Application Manager

Distributed Application Manager is renamed to FactoryTalk View SE Application Manager. The tool supports all types of SE applications.

Legacy HMI tag alarms

Starting from FactoryTalk View version 11.00, legacy HMI tag alarms are no longer supported.

Legacy Alarms commands are removed.
HMI Tag Alarming functions are removed.
The HMI tag alarm summary control is removed.
HMI Tag Alarms, Suppressed List, and Alarm setup are removed from the explore tree.
The tools HMI Tag Alarm Log Setup and HMI Tag Alarm Log Viewer are removed.

After upgrading to version 11.00, legacy HMI alarm definitions in your existing application are stored in the HMI tag database. Use the FactoryTalk View Alarm
Migration tool to migrate them to FactoryTalk Alarms and Events. For an example of instructions, see the YouTube page  of Rockwell Automation.

Redundancy

The Save edits to both active and standby HMI servers option is selected by default.

Application Notes
This release has the following application notes.

Considerations for application server host computers

In a network application, it is possible for a single server computer that meets the recommended requirements to host all of the following components:

One FactoryTalk View SE Server
One FactoryTalk Linx data server (which can also be set up as FactoryTalk Alarms and Events device-based alarm server)
One RSLinx Classic server (or some other OPC data server)
One FactoryTalk Alarms and Events Tag based alarm Server
The FactoryTalk Network Directory

If a network application requires multiple HMI servers, data servers, or alarm servers, to distribute the load, it is recommended that you install the necessary
software and run the servers on multiple host computers.

Running more than one HMI server on a single computer is not recommended. If you plan to deploy a network distributed application that uses more than
two servers (or two pairs of redundant servers) and more than 20 clients, or if you would like architectural assistance, contact your local Rockwell
Automation Sales office for architectural assistance.

For information about setting up redundant FactoryTalk View SE servers, see FactoryTalk View Site Edition User’s Guide .

FactoryTalk Diagnostics

FactoryTalk Diagnostics cannot log to a remote database using Microsoft Access. You can only log to a local database using Microsoft Access.

Find and Replace

If an HMI server at the root node of an SE Network distributed application has the same name as the application itself, the Find and Replace feature search
results might include the application name even though you performed the search at the HMI server level.

Floating-point operations

Floating-point numbers may not precisely represent all real numbers. As a result, expressions based on floating-point arithmetic operations may not
evaluate as expected. This is a side effect of how the CPU represents the floating-point data. For this reason, in certain cases you may experience loss of
precision and get unexpected results of floating-point operations.

KEPServer

If you are using KEPServer Enterprise as an OPC server with FactoryTalk View version 9.00.00 or later and using an HMI tag to connect to a third-party
device, you will not be able to access the tag value. The cause is that the security enhancements in FactoryTalk View version 9.00.00 or later affect the
communications with third-party devices. To access the tag value, additional Distributed Component Object Model (DCOM) configuration is required for
KEPServer Enterprise on the computers.

For more information about the configuration, see Appendix, "Troubleshoot KEPServer Enterprise" in the FactoryTalk View SE Installation Guide.

Pre-installation configuration

Before you install FactoryTalk View SE, there are a number of steps required to set up the installation environment. This will help ensure that the installation
proceeds smoothly and that your new or upgraded FactoryTalk system operates as expected. For detailed information about pre-requisites before
installation, see Chapter 3, Pre-installation configuration of FactoryTalk View Site Edition Installation Guide.

Security requirements

For information on the security considerations when using Rockwell Automation products, including

File extensions created by Rockwell Automation software, firewall rules, and service dependences, see Rockwell Automation Knowledgebase Answer
ID 609492 .
TCP/UDP ports used by Rockwell Automation products, see Rockwell Automation Knowledgebase Answer ID 29402 .

System sizing recommendations

When you design and set up a FactoryTalk system, we recommend using the following guidelines. If you find that your system needs to expand beyond
these guidelines, contact your Rockwell Automation sales or distributor representative to discuss your application design.

Component Recommended guidelines

FactoryTalk Alarms and Events  

FactoryTalk Alarms and Events servers per application 10 non-redundant servers or 10 redundant
server pairs

FactoryTalk tag-based alarms per server 20,0001

Logix device-based alarms per server 10,0002

Total alarms per application 100,0003

FactoryTalk Linx  

FactoryTalk Linx data servers per application 10 non-redundant servers or 10 redundant
server pairs

Total device tags per application 1,000,0004

Tags per FactoryTalk Linx data server 100,0004

FactoryTalk View SE  

HMI servers 10 non-redundant servers or 10 redundant
server pairs

HMI tags per HMI Server 40,0005

Total data logged tags per HMI server (1 second scan 5,000
rate)

FactoryTalk View SE client sessions simultaneously 1204
connected to the application

FactoryTalk ViewPoint SE servers per application 4

FactoryTalk ViewPoint SE concurrent clients per ViewPoint 50
server
1.  The number of alarm backing tags influences the maximum number of available alarms because
they increase the resource requirements of the alarm server. When using backing tags for status
and control, a good rule of thumb is to multiply the total number of backing tags by the total number
of alarms, and ensure the result is less than 20,000. PlantPAx® users should refer to the PlantPAx
Reference Manual PROCES-RM001 for alarm server sizing guidance for a PlantPAx application.
2.  This number is the sum of both instruction alarms and Logix tag-based alarms across all the
controller shortcuts in each FactoryTalk Linx server.
3.  The total number of alarms per application includes all FactoryTalk Alarms and Events tag-based
and device-based alarms in the application.
4.  Refer to Rockwell Automation Answer ID 1070902 for detailed information to determine system
scalability for the total device tags per application.
5.  The maximum number of HMI tags that can be created on a single HMI server is 175,000. Extensive
use of HMI tags has a significant performance impact on an HMI server, so Rockwell Automation
recommends minimizing their use, and instead using direct-reference tags as much as possible.

Tag Browser

If you rename an HMI server while you are deploying an application, you may need to restart the computer in order to have the HMI tags show up in the Tag
Browser.

Tools and utilities

In the DeskLock utility, all Windows hot keys are disabled except the Windows Logo + L combination, which still locks the Windows Desktop. This is
found in the Windows 7 Professional and Windows Server 2008 operating systems.
In the Tag Import and Export Wizard, you are recommended to close the running project while importing a tag CSV file containing large amounts of
tags and alarms. Otherwise, you will need to wait a few minutes and the Server Busy Dialog box may pop up.

Trend objects

The Trend objects cannot get the oldest data from FactoryTalk Historian server when you click the Oldest Data button.

TrendPro objects

Clicking on the X-axis or Y-axis takes it into the free layout mode. In this case, anything done to the canvas is how you want it and it does not resize. The free
mode does not persist scale and removes tags from the trend. Avoid using the free mode in the trend.

UAC support
Turning off User Account Control (UAC) is not recommended.

This action Prompts for authentication or confirmation before running
this program
RSViewWebManager.exe
Configuring Internet Information Services
(IIS) CustomWebSite.exe

Updating Samples application directory RefreshSampleApplication.exe
information

Terminate processes VSClean.exe

DeskLock DeskLock2000.exe

Legacy Tag Database Conversion LegacyTagDBConvertTool.exe

Unattended installation

The following table identifies the installation command-line parameters. Command-line parameters are case-insensitive. However, if a specified value
includes a space, be sure to enclose the value in quotation marks (for example, "value with spaces").

Parameter Description

/? Shows the usage options for installation parameters.
Silent Install. Install runs in a quiet mode without any user
/Q interface.

This parameter is recommended if you are deploying the software
installation using an IT tool or script, and don’t expect to see any
error or restart messages. When using this parameter, your IT tool
or script should check the error codes, and respond as needed.
For example, if the installation returns error code 1641, then the IT
tool or script should restart the computer and relaunch the
installation after restart.

This parameter is required if /QS or /Record is not specified.
Unattended Install. Install runs in a quiet simple mode and shows
/QS progress through the UI. It does not accept any input, but still
shows error or restart messages.

When using this parameter, you will not have to check the error
codes, and the installation will stop and show a prompt if there are
error or restart messages. For example, if an immediate restart is
required to complete the install, a restart message will be shown
for you to confirm the restart. Installation resumes automatically
from the point of interruption after restart.

This parameter is required if /Q or /Record is not specified.
Acknowledges acceptance of the license terms and agreement to
/IAcceptAllLicenseTerms continue the installation.

This parameter is required.
Automatically restarts the computer after the installation is
/AutoRestart complete. Used when a restart is required to complete the
installation.

This parameter is optional. If this parameter is not used, silent
install (/Q) will return error code 1641 or 3010 if a restart is
required, and unattended install (/QS) will result in a confirmation
prompt that must be agreed to before the installation is completed.
Specifies which language will be shown during install process.
/SetupLanguage="value"
This parameter is optional. If this parameter is not used, the
default language is the current user or operating system user
interface language.

The value must be one of the following:
ENU
CHS
DEU
ESP
FRA
ITA
JPN
KOR
PTB
Records the installation options chosen to a recording file.
/Record
This parameter is optional.
Plays back a recording file to specify the installation options.
/Playback
This parameter is optional.
Runs a repair operation on the installed products.
/Repair
This parameter is optional.
Specifies which product will be installed.
/Product="value"
This parameter is required.

The value must be the one of following:
Studio Enterprise
Site Edition Server
Site Edition Client
Site Edition Station
FactoryTalk ViewPoint SE
Stand-alone FactoryTalk Linx Server
Stand-alone FactoryTalk Directory Server
Uninstalls components that are already installed with the product
/Uninstall specified.

This parameter is optional.
Specifies the language version of the software being installed.
/ProductLanguage="value"
This parameter is optional. If this parameter is not used, the
default language is the same as the setup language.

If the software does not support multiple languages, this parameter
is not available.

The value must be one of the following:
ENU
CHS
DEU
FRA
JPN
Specifies the installation drive.
/InstallDrive="value"
This parameter is optional. If this parameter is not used, the
default install drive is C:.
Specifies the serial number of the software being installed. This is
/SerialNumber="value" used to activate the software during installation.

This parameter is optional. If it is not specified the software must
be activated manually after installation if activation is required.

Some software does not require activation. If activation is not
required, this parameter is not available.
Specifies the product key used to get activation keys during
/ProductKey="value" installation.
This parameter is optional. If it is not specified, the software must
be activated manually after installation if activation is required.

Some software does not require activation. If activation is not
required, this parameter is not available.
Specifies the version of the software to activate which corresponds
/Version="value" to the product version associated with the SerialNumber and
ProductKey.

This parameter is optional. If it is not specified, the installer will use
the most recent product version available.

Some software does not require activation. If activation is not
required, this parameter is not available.

Error codes

The following table identifies the error codes that can be returned by an installation.

Error Code Value Description

ERROR_SUCCESS 0 Installation completed successfully.

ERROR_INVALID_PARAMETER 87 One parameters is invalid.

ERROR_INSTALL_USEREXIT 1602 Installation cancelled by user.

ERROR_INSTALL_FAILURE 1603 Fatal error during installation.

ERROR_BAD_CONFIGURATION 1610 Configuration data for product corrupt. Contact


support personnel.

ERROR_REBOOT_CONTINUE 1641 Restart required to continue installation.

ERROR_SUCCESS_REBOOT_REQUIRED3010 Restart required to complete installation. After
restart, product is successfully installed.

ERROR_REBOOT_PENDING 3012 Restart pending. Restart computer for installation to


continue.

ERROR_SUCCESS_NOT_APPLICABLE 3013 The installation cannot proceed because the


products are already installed.

VeriSign Universal Root Certification Authority certificate

If the VeriSign Universal Root Certification Authority certificate does not exist on the local computer, the certificate is installed while installing Rockwell
Automation software. Use Microsoft Management Console (MMC) to view the certificate in Console Root > Certificates (Local Computer) > Trusted
Root Certification Authorities > Certificates .

Copyright © 2019 Rockwell Automation, Inc. All rights reserved.
Rockwell Automation, Allen-Bradley, and Rockwell Software are trademarks of Rockwell Automation, Inc.
To view a complete list of Rockwell Automation trademarks please click here.
Trademarks not belonging to Rockwell Automation are property of their respective companies.