MEDIUM VOLTAGE POWER CABLES

35kV Copper Conductor, XLPE Insulated,


Copper Tape Shielded, PVC Jacketed, Single Conductor

Insulation
Jacket Shield
Conductor
Shield

Conductor
Copper Tape
Insulation

Detailed Description or Construction Insulation Levels


100 Percent Level = Cables in this category may
be applied where the system is provided with
Conductor relay protection such that ground faults will be
Compact round stranded copper conductor cleared as rapidly as possible, but in any case
Conductor Shield within 1 minute.
Thermosetting extruded semi-conducting compound 133 Percent Level = This insulation level
Insulation corresponds to that formerly designated for
Cross-linked polyethylene (XLPE) 90°C underground systems. Cables in this category
Insulation Shield
may be applied where the clearing time
Thermosetting extruded semi-conducting compound
Metallic Shield requirements of the 100 percent level category
Copper tape shield cannot be met, and yet there is adequate
Jacket assurance that the faulted section will be de-
Polyvinyl chloride (PVC) energized in a time not exceeding 1 hour.

Reference Standards Application


ICEA S - 93 - 639 Primary power and distribution circuits in
industrial, commercial and power circuit
generating plants. Single conductor cables, 1/0
AWG and larger, can be marked for CT use to be
Voltage Rating installed in ladder cable tray as per NEC 318.
35kV

Temperature Rating Installation


Cables may be installed indoor and outdoor,
Normal Condition
exposed to sunlight, in raceway, conduit, duct or
90°C
aerially supported by a messenger and directly
Emergency Condition
130°C buried as per NEC 250-51.
Short-circuit Condition
250°C

Customer Approval
Executive office: Manufacturing Plant:
2297 2/F BCS Prime Bldg. Pasong Luisita Industrial Park Name
Tamo Ext. Makati City, Philippines San Miguel, Tarlac City Philippines Date
T. (632) 813-2529 T. (6345) 985-1088 to 91
F. (632) 893-4990 Signature
MEDIUM VOLTAGE POWER CABLES
35kV Copper Conductor, XLPE Insulated,
Copper Tape Shielded, PVC Jacketed, Single Conductor

35kV 100%IL
Allowable
Conductor Overall Cable Minimum
Equivalent Minimum Insulation ampacities Standard
Size diameter diameter weight bending
copper size number thickness in free air packing
(approx.) (approx.) (approx.) radius
of wires @ 40°C
mm² AWG / MCM mm mm mm kg / km A mm m / reel
50 1/0 18 8.5 8.76 30.1 1,533 225 361 500
60 2/0 18 9.6 8.76 31.2 1,713 260 374 500
80 3/0 18 10.8 8.76 32.3 1,926 300 388 500
100 4/0 18 12.1 8.76 33.6 2,185 345 404 500
125 250 35 13.2 8.76 34.8 2,415 380 417 500
150 300 35 14.4 8.76 36.0 2,703 425 432 500
200 400 35 17.6 8.76 39.2 3,259 507 471 500
250 500 35 18.6 8.76 40.2 4,004 580 482 500
300 600 58 20.4 8.76 42.0 4,562 640 504 500
325 650 58 21.2 8.76 44.7 4,826 670 537 500
350 700 58 22.0 8.76 45.5 5,099 700 546 500
375 750 58 22.8 8.76 46.4 5,380 730 556 500
400 800 58 23.6 8.76 47.1 5,641 750 565 300
450 900 58 25.0 8.76 48.5 6,183 802 582 300
500 1000 58 26.3 8.76 49.8 6,689 850 598 300
35kV 133%IL
Allowable
Conductor Overall Cable Minimum
Equivalent Minimum Insulation ampacities Standard
Size diameter diameter weight bending
copper size number thickness in free air packing
(approx.) (approx.) (approx.) radius
of wires @ 40°C
mm² AWG / MCM mm mm mm kg / km A mm m / reel
50 1/0 18 8.5 10.67 38.2 1,764 225 459 500
60 2/0 18 9.6 10.67 39.3 1,950 260 472 500
80 3/0 18 10.8 10.67 40.5 2,170 300 486 500
100 4/0 18 12.1 10.67 41.8 2,436 345 501 500
125 250 35 13.2 10.67 44.8 2,863 380 538 500
150 300 35 14.4 10.67 46.1 3,165 425 553 500
200 400 35 17.6 10.67 49.3 3,742 507 591 500
250 500 35 18.6 10.67 50.2 4,308 580 603 500
300 600 58 20.4 10.67 52.0 4,876 640 625 500
325 650 58 21.2 10.67 52.9 5,144 670 634 500
350 700 58 22.0 10.67 53.7 5,422 700 644 500
375 750 58 22.8 10.67 54.5 5,707 730 654 500
400 800 58 23.6 10.67 55.2 5,972 750 662 300
450 900 58 25.0 10.67 56.7 6,523 802 680 300
500 1000 58 26.3 10.67 58.0 7,036 850 696 300

+Diagrams of cables are illustrative only and not necessarily to scale. PDP reserves the right to change or vary the construction of any of their products without notice.
While every care has been taken in the preparation of this data sheet, PDP accept no liability of any kind and are not responsible for the results of any actions taken on
the basis of this information or resulting from errors or omissions. This technical data sheet is intended as a guide only; any person using it must make reference to
the appropriate local standards or authorities.