NTPC Local Management Instruction DADRI

TITLE: MANAGEMENT OF DC SUPPLY SYSTEM FAILURE Rev. : 0

DOOCUMENT CUM WORK INSTRUCTION OF DC FAILURE STAGE-1

Date12/12/2017

Document is jointly prepared by Balram Sharma(O), Pankaj Shukla(C&I) &

Jayathran PS.

INDEX

SECTION TITLE PAGE NO


1. 0 Introduction 1
2. 0 Scope 1
3. 0 Reference Document 1
4. 0 DC Supply In Stage#1 2
5. 0 Failure of 24 V DC SG/TG System Stage#1 3
6. 0 Failure of 24 V DC BOP System Stage#1 8
7. 0 Failure of 240 V AC UPS Supply Stage#1 12
8. 0 Failure of 220 V DC Supply Stage#1 15
9.0 Failure of 110 V AC control supply stage-1 21

1.0 Introduction :

DC supply system in a power station is used either for providing a reliable source of control
power for vital control systems or as a back up power for running critical devices, lighting etc,
in case of emergency arising due to failure of AC power. Reliable functioning of DC system is
therefore of paramount importance. In case of failure of these DC power supplies, different
emergency situations can arise which need proper understanding of their consequences and
prompt action. Absence of such understanding and action may lead to extremely serious
damage to plant and equipment and safety hazards.
2.0 Scope:
This document pertains to 4 X 210 MW units of NTPC-DADRI Stage- I. The purpose of this
document is to identify all possible situations which may lead to non-availability of DC supply,
the results or consequences of such non-availability, and the measures to be taken to ensure
the safety of plant, equipment and personnel in such situations.

3.0 REFERENCE DOCUMENT : EMD and C&I DRAWINGS

1|Page
NTPC Local Management Instruction DADRI

TITLE: MANAGEMENT OF DC SUPPLY SYSTEM FAILURE Rev. : 0

4.0 DC SUPPLY IN STAGE #1 :

The following are the DC power supplies used in NTPC-Dadri Stage – I.


Sl Rated Battery b
Description Input supply No. of units
No Output ackup

2 DCDBs with 02
24 V DC supply for 415V ac 50Hz chargers and 02
24VDC, 640 AH
1. SG/TG system USS Sec-B & battery bank each
310A per DCDB
(maxDNA DCS) UES(EMCC) (02 charger in service
at a time).
415V ac 50Hz 2 DCDBs with 02
USS Sec-B & chargers and 02
24 V DC supply for BOP 24VDC, 590 AH
2. UES(EMCC) battery bank each
system (maxDNA DCS) 286A per DCDB
(02 charger in service
at a time)..
415V ac 50Hz
240 V AC UPS Two rectifiers, Two
240VAC, 430 AH USS Sec-B,
3. System(withDC battery inverters with One
105 kVA UES(EMCC)
backup) battery bank
& A bypass supply
415V ac 50Hz
220VDC, 990AH per Two chargers with
4. 220 V DC System USS Sec-B &
400A DCDB Two battery banks
UES(EMCC)
415V ac 50Hz 2 DCDBs with 02
24 V DC supply for USS Sec-B & chargers and 02
24VDC, 294 AH
5. Common electric UES(EMCC) battery bank each
139A per DCDB
system (maxDNA DCS) (02 charger in service
at a time).
415V ac 50Hz 2 DCDBs with 02
CW MCC Sec-A& Sec- chargers and 02
24 V DC supply for CW 24VDC, 120 AH
6. B battery bank each
system (maxDNA DCS) 59A per DCDB
(02 charger in service
at a time).

2|Page
NTPC Local Management Instruction DADRI

TITLE: MANAGEMENT OF DC SUPPLY SYSTEM FAILURE Rev. : 0

5.0 FAILURE OF 24 V DC SUPPLY FOR SG/TG SYSTEM Stage #1:

The supply for the 02 chargers is taken from unit service switchgear and unit emergency service
switchgear.
Charger Supply Source

24V SG/TG DCDB-I UES(EMCC)

24V SG/TG DCDB-II USS Sec-B

Case 1: Any one SG/TG 24V stream (both battery & charger units) fails.
Since bus coupler that interconnects the two 24V SG/TG DCDBs remains in OFF condition
during normal operation, failure of one stream 24V battery and charger will result in tripping of
one stream of MCBs in all SG & TG panels. Alarm annunciation for SG/TG Charger fail will
appear in LVS at CCR. The DPU status screen has to be monitored immediately to confirm that
all panels are powered up through the healthy 24V stream. Any panel that is not
communicating (shown in hashes) has to be inspected in the CER. C&I and EMD Area engineer
has to be informed immediately to take corrective action on any panel that is completely OFF
due to failure of its standby 24V stream.
 Before manually charging the dead 24V DCDB section through the bus coupler,
special care has to be taken first to ensure that no fault (eg. Earth fault) is
persisting that may lead to total failure of 24V to SG/TG systems.
- Resp.: SCE (Operation), Shift Engineer(C&I), Area Engineer EMD.

Case 2: Both SG/TG 24V streams (both battery & charger units) fail
Identification
 Check DPU Status screen. If all SG/TG DPUs are being shown in hashes (not
communicating) it indicates loss of both SG/TG 24V streams failure.
 SG & TG 24V- charger panels are to be inspected from local to confirm this indication.

3|Page
NTPC Local Management Instruction DADRI

TITLE: MANAGEMENT OF DC SUPPLY SYSTEM FAILURE Rev. : 0

The following table describes the status of critical systems in the unit in the event of 24V
SG/TG both streams failure:

S. Protection Indication
Equipment/ Expected
No & Interlock & Remarks
System Condition
. Healthiness Operation
Electrical
If turbine is tripped,
Turbine trip will not
220kV breaker will
Generator be sensed, so class-B
1 open through Reverse Available in OWS
protections trip on LFPR not
power protection
enabled
(Class-A)
220 kv Main / All Protections in
2 Operative from CCR Available in OWS .
transfer breaker service

6.6kV , 415V
All Protections in
3 Switchgears and Operative from CCR Available in OWS .
service
DG

Turbine
Turbine will not All remote
Turbine
Turbine trip as both turbine trips
speed and Hydraulic protections and
1 protections (TG – turbine out of service
load not
protection panels (Solenoids manual trip lever are healthy
TP 1&2) available in
24V supply is need 24V to
OWS
dead trip)
Not
All interlocks
2 FCNRV Same Status Available in
out of service
OWS
OWS / LVS Hash in all
3 Mimics mimics of TG
side
Only
Not
Turbine governing EHC will go to hydraulic Mechanical over speed trip
4 available in
system maximum governor will healthy
OWS
control speed
5 LSR Inoperative

6 Trimming Device Inoperative

7 Gen seal-oil DC SOP hard All interlocks Not DC SOP operation possible
system wired start will out of service available in with CCR Hardwired PB /
be available from OWS Local panel.
UCB/Local panel

4|Page
NTPC Local Management Instruction DADRI

TITLE: MANAGEMENT OF DC SUPPLY SYSTEM FAILURE Rev. : 0

Push button

All AOPs
interlocks out TG lub oil pressure Very low
EOP auto-start trip not in service.
of service. Not
by direct
8 TG lub-oil system AOP-1/2 will available in DC EOP start possible with
pressure switch
be NTS from OWS CCR Hardwired PB / Local
is healthy
OWS & Draw panel.
out desk.

Not
TG jacking oil Inoperative from All interlocks Can be started from Local
9 available in
system OWS out of service Start PB
OWS

Barring gear not Not


TG barring gear All interlocks Manually can be opened from
10 operative from available in
system out of service actuator.
OWS. OWS

Vacuum breaker
inoperative(normally remains
Not
TG Evacuation Vacuum pumps All interlocks closed), Manually can be
11 available in
system SIV will close. out of service made open from local by
OWS
isolating the vacuum breaker
governing oil

All interlocks Control loop also will remains


12 BFP available available
available available.
Valves position All remote Not Can be opened from local
13 LP bypass system will stay put. interlocks out available in from LPBP governing rack in
Control not a/v of service OWS confidence of TMD.

Not Bypass valve of these also


Seal steam Seal/leak off
14 available in not be available. Can be
controller valve will close. operated from local valve by
HMI
C&I.
Not
15 TSI available in Shaft Vibration Protection
OWS also will be out of service.

Will not
Close on
Operative from Turbine trip
16 Extraction MOVs Available
CCR but will close
on Drip Level
V.Hi.

5|Page
NTPC Local Management Instruction DADRI

TITLE: MANAGEMENT OF DC SUPPLY SYSTEM FAILURE Rev. : 0

Load /speed / lub Not Lub oil pressure will be


17 oil / seal oil /H2 Hash available in available on main mimic
pr OWS (Used only for display
purpose)

Boiler

Boiler protections MFT will act on Healthy (Fail- Not


loss of FSSS 24V
1 (SG – FSSS MFT DC (from SG safe available in -
1, 2, 3) hardwired) OWS
24V)

Coal firing All will trip


equipment Healthy (Fail- Not
through MFT or
2 safe available in -
(Mills, feeders, loss of FSSS 24V
hardwired) OWS
HAG) DC

Both will trip


Healthy (Fail-
through MFT or Panel supply from BOP
3 PA Fans safe All Available
loss of FSSS 24V system
hardwired)
DC

All remote Not


4 Seal air fans Will not trip protections available in -
out of service OWS

DC scanner air
fan will take start Healthy (Fail- Not
DC Scanner Air
5 and emergency safe available in -
fan
air damper will hardwired) OWS
open

Status not
AC Scanner air
6 Same status available in
fan
OWS

Control
Furnace press, Will be switched
7 functions Loops will not work in auto
drum level control to manual
healthy

Operation
HOTV/LOTV/HON Through Not Status not will not be
8 Will Close. hard wired
V available in available in OWS so closing
control. OWS to be ensured from local

Hash in all
OWS / LVS
9 mimics of SG
Mimics
side

6|Page
NTPC Local Management Instruction DADRI

TITLE: MANAGEMENT OF DC SUPPLY SYSTEM FAILURE Rev. : 0

Valves position Not


10 HP bypass will stay put. available in
Control not a/v OWS

Will not be
11 Hydrastep available

N Actions: Responsibility

Boiler Desk
1 Ensure Boiler trips on loss of 24V DC.
engr.

Inform HOD(C&I), HOD (EMD) and HOD (OPN) immediately after the
2 SCE
failure.

3 Maintain drum level using BFP control. TG Desk Engr.

Ensure Tripping of PA fans (Through Hard wired trip) else Give trip Boiler Desk
4
command from Breaker or EPB engr.

5 Ensure from location HOTV & LOTV have closed. UCE

Ensure Tripping of Mills (Through Hard wired trip) in SWGR / Else Give
6 UCE
trip command from Breaker or EPB

Ensure Tripping of Feeders (Through Hard wired trip) Else Trip them from
7 UCE
Feeder Panels in CCR

Trip Turbine using Local trip lever From Governing Rack as Turbine
8 TG Desk Engr.
Protections are not available

Ensure Generator trips on reverse power protection, 220 KV breaker/


9 TG Desk Engr.
Field breaker trips on protection.

Start DCEOP from CCR hardwired push buttons & confirm locally. (Will get
10 TG Desk Engr.
an auto start command from Hardwired Pr switch as well)

11 Close Boiler Stop valves manually from local. TG Desk Engr.

12 Kill Vacuum and Isolate Seal Steam as Vacuum pumps SIVs will close. TG Desk Engr.

Do Hand barring of TG periodically every 10-15 minutes till AOP comes


13 UCE
into service.

14 Try to start AOP / AC JOP of turbine from local Start button. SCE

7|Page
NTPC Local Management Instruction DADRI

TITLE: MANAGEMENT OF DC SUPPLY SYSTEM FAILURE Rev. : 0

15 Open Gate valve gearing from location after Starting AOP UCE

16 Close HPH/LPH/De-aerator Extraction valves from CCR TG Desk Engr.

17 Monitor Lube oil/seal oil parameters at Location UCE

Restore DC supply as quickly as possible after ensuring healthiness of at


18 SCE
least one charger & battery streams

Start Main turbine AOP and Open turning gear valves from OWS if not
19 UCE
done already .

6.0 FAILURE OF 24 V DC SUPPLY FOR BOP SYSTEM Stage# 1:

The supply for the chargers is taken from unit service switchgear and unit emergency service
switchgear.
Charger Supply Source

24V BOP DCDB-I UES(EMCC)

24V BOP DCDB-II USS Sec-B

1: Any one BOP 24V stream (both battery & charger unit) fails
Since bus coupler that interconnects the two 24V BOP DCDBs remains in OFF condition during
normal operation, failure of one stream 24V battery and charger will result in tripping of one
stream of MCBs in all BOP panels. Alarm annunciation for “BOP Charger fail” will appear in LVS.
The DPU status screen has to be monitored immediately to confirm that all panels are powered
up through the healthy 24V stream. Any panel that is not communicating (shown in hashes)
has to be inspected in the CER. C&I engineer has to be informed immediately to take
corrective action on any panel that is completely OFF due to failure of its standby 24V stream.
 Before manually charging the dead 24V DCDB section through the bus coupler,
special care has to be taken first to ensure that no fault (eg. Earth fault) is
persisting that may lead to total failure of 24V to BOP systems.
 Before switching ON any BOP panel that turned off, its redundant analog
output connectors have to be removed, to prevent disturbance to the process
(mA outputs get initialized to 25% or 8mA during power up). The connectors
have to be put back after normalization of panel and matching analog output
commands with actual feedback (to prevent bump in process).
 In case the CRE 41, 42, 43 or 44 are turned off, EMD engineer to be informed
before power up.

8|Page
NTPC Local Management Instruction DADRI

TITLE: MANAGEMENT OF DC SUPPLY SYSTEM FAILURE Rev. : 0

- Resp. : SCE (Operation), Engr (C&I)

Case 2: Both BOP 24V streams (both battery & charger unit) fail
Identification
 All control loops and most parameters go hash.
 Check DPU Status screen. If all BOP DPUs are being shown in hashes (not
communicating) it indicates loss of both BOP 24V streams failure.
 BOP panels are to be inspected from local to confirm this indication.

The following table describes the status of critical systems in the unit in the event of 24V BOP
both streams failure:

Protection
Sl Equipment / Expected Indication
Interlock Remarks
No System Condition operation
Healthiness

Electrical
Generator
Inoperative / Not available in
1 /Electrical
hash OWS
screen

Generator will
Generator trip upon LFPR Available in
2 All interlocks healthy -
protections after turbine trip OWS
(class-B) protn.

220kV breaker will


trip on protection.
Remote operation
3 220kV Hash Not available
of 220 KV bkr is
not possible from
ows.

No HT/LT breaker
6.6 KV UAT-ST
operations
4 tie breaker auto Not available Not available
possible from
changeover
remote

9|Page
NTPC Local Management Instruction DADRI

TITLE: MANAGEMENT OF DC SUPPLY SYSTEM FAILURE Rev. : 0

Not available
415V Same status as All remote interlocks
5 for Swgr and -
Switchgears. before out of service
DG sets

Turbine
Turbine
protections Turbine will trip Panel supply from
1 All interlocks healthy Available
when MFT acts SG/TG system
(TG – TP 1, 2)

Turbine
Panel supply from
2 governing Not affected All interlocks healthy Available
TG system
system

Indication not
3 BFP Not a/v
a/v in OWS

Hot well /de-


Indication not
4 aerator /drum Not available
a/v in OWS
level control

LPH/HPH Level Indication not


5 Not available
Control a/v in OWS

Same status.
All remote interlocks Indication not
6 CEP Recirculation
out of service a/v in OWS
valve will open

All remote interlocks Indication not


7 ECW Same status
out of service a/v in OWS

ALL
All remote interlocks Indication not
8 EXTRACTION Inoperative
out of service a/v in OWS
MOVs

Boiler
Total air flow<30%,
Flame failure, Loss
Boiler Boiler will not Drum level SG Mimics
of all fuel, Furnace
protections trip immediately, Protection, All BFPs available, Boiler
pressure
1 but MFT circuits Tripped, All SAH Off, Auxiliaries
(SG – FSSS MFT will be only protections
Reheat protection mimics in BOP
1, 2, 3) healthy. Software
partially healthy Trip – all out of not available
EPB in service
service

Oil firing
equipment
All will trip when Available in Panel supply from
2 (LOTV, LONV, All interlocks healthy
MFT acts OWS SG system
HOTV, HONV,
HORV)

10 | P a g e
NTPC Local Management Instruction DADRI

TITLE: MANAGEMENT OF DC SUPPLY SYSTEM FAILURE Rev. : 0

Coal firing
equipment All will trip when Available in Panel supply from
3 All interlocks healthy
(Mills, feeders, MFT acts OWS SG system
HAG)

Both will trip


when MFT acts
All other protections Not available in PA scoop will
4 PA Fans (through will be out of service OWS. remain stay put
hardwired
protection)

Seal air fans Will not trip


Not available in
5 when both PA All interlocks healthy To be tripped .
OWS
fans are Off

Scanner air fans Not available in


6 Not affected All interlocks healthy -
OWS

electric motor All interlocks out of Not available in Dampers will


7 Air preheaters
keeps running service OWS remain stay put.

Different
response for
different units
All protections and
Status not Furnace Pressure
interlocks out of
8 ID fans Same status as available in indication, control
service in units where
before, IGV will OWS not available
VFD not available
remain stay put
and VFD remains
at same
command

Same status as
All protections and Air flow indication,
before, blade Not available in
9 FD fans interlocks out of control not
pitch will remain OWS
service available
stay put

ERV
electromatic Transmitter interlocks Available only
10 Inoperative. -
safety relief out of service at OWS
valves

Auto control
Out of control, available,
Furnace Not available in
11 IGV and VFD at 2/3 protection
pressure control OWS
last position through switches in
service

11 | P a g e
NTPC Local Management Instruction DADRI

TITLE: MANAGEMENT OF DC SUPPLY SYSTEM FAILURE Rev. : 0

Total air flow,


Out of control, Total air flow <30% Possibility of low
Total air flow fuel flow and
12 FD blade pitch at protection not in oxygen condition
control excess oxygen
last position service if fuel is in excess
not available

Out of control, PA header pressure


PA header Not available in
13 PA scoop at last very low Protection of -
pressure control OWS
position Mills is healthy

Out of control, All Mill outlet


HAD and CAD Mill protections temp, PA flow,
14 Mill controls
expected to stay healthy feed rate not
put available

Out of control, Possibility of


MS and HRH All spray interlocks Not available in
15 spray valves will hammering if MS
temp controls out of service OWS
stay put flow is stopped.

Actions: Responsibility

Inform HOD(C&I), HOD (EMD) and HOD (OPN) immediately after


1 SCE
the failure.

2 Initiate MFT as BFP control and feedbacks will not be available Boiler Desk engr.

3 Ensure Turbine trips on MFT TG Desk Engr.

Ensure Generator Trips on LFPR - Ensure Field breaker and 220kV


4 UCE
tripping from Location.

Ensure Tripping of PA fans from SWGR / else Give Trip command in


5 UCE
breaker/EPB

6 Ensure Tripping of Mills and Feeders in SG Mimics. Boiler Desk engr.

7 Ensure closing of HOTV/LOTV in SG mimics Boiler Desk engr.

8 Trip Seal air fans from OWS Boiler Desk engr.

TG Desk engr. Thro


9 Stop Running CEPs thro EPB
Operator

10 Close HPH, LPH and De-aerator extraction valves using local switch TG Desk Engr.

Isolate HPBP Spray manual valves and SH & RH spray manual


11 TG Desk Engr.
valves.

Restore DC supply as quickly as possible after ensuring healthiness


12 SCE
of at least one charger & battery streams

12 | P a g e
NTPC Local Management Instruction DADRI

TITLE: MANAGEMENT OF DC SUPPLY SYSTEM FAILURE Rev. : 0

7.0 Failure of 240 V AC UPS SUPPLY:

UPS has 2 independent streams with output 240V AC voltage regulation and frequency
tracking. Each UPS has a common DC bus which receives DC power from a rectifier/charger
and common battery bank. The two rectifier/charger systems receive 415 V AC incoming
supply from unit service switchgear or station service switchgear. This DC power is converted
to give 240 V AC power output by inverter circuit of each UPS. Besides the two UPS streams,
there is a bypass emergency supply directly coming from unit emergency switchgear which will
automatically come in to service in the event of both UPS failure.
Case 1: Any one UPS stream (including battery) fails
In the event of any one stream failing, other source will continue to feed the ACDBs and “UPS
fail” alarm will come in LVS? at CCR. No system abnormality is expected. However the failed
supply has to be restored at the shortest possible time with the help of EMD/C&I.
-Resp. : SCE / HOD (EMD)/ HOD (C&I)
Case 2: Both UPS streams (including battery) fail and bypass supply in service
In the event of both streams failing, emergency bypass source will continue to feed the ACDBs
and “UPS fail” alarm will come in LVS at CCR. No system abnormality is expected. However the
failed supplies have to be restored at the shortest possible time with the help of EMD/C&I.
-Resp. : SCE / HOD (EMD)/ HOD (C&I)
Case 3: Both 240V AC UPS streams (both UPS & battery) and bypass supply fail
The following table describes the status of critical systems in the unit in the event of 240V AC both
streams and bypass supply failure:

Protection &
SL Equipment / Indication &
Expected Condition Interlock Remarks
No System operation
Healthiness

All LVS/OWS will be


1 OWS Available Not available
dead.

Boiler protectionsMFT will act on both


All interlocks
2 (SG – FSSS MFT 1, ID fans Off or Flame healthy Available -
2, 3) Failure

Turbine protections Turbine will trip upon All interlocks


3 Available -
(TG – TP 1, 2) MFT healthy

Generator Generator will trip All interlocks


4 Available -
protections upon turbine trip healthy

LLD
All interlocks
5 Gen seal-oil system Not affected Available protection
healthy
will not work

13 | P a g e
NTPC Local Management Instruction DADRI

TITLE: MANAGEMENT OF DC SUPPLY SYSTEM FAILURE Rev. : 0

Protection &
SL Equipment / Indication &
Expected Condition Interlock Remarks
No System operation
Healthiness

Oil firing equipment


(LOTV, LONV, All will trip when MFT All interlocks
6 Available -
HOTV, HONV, acts healthy
HORV)

Coal firing
equipment All will trip when MFT All interlocks
7 Available -
(Mills, feeders, acts healthy
HAG)

Both will trip when All interlocks


8 PA Fans MFT acts healthy except Available -
vibration trip

Will trip when both All interlocks


9 Seal air fans Available -
PA fans are Off healthy

Air motor will take


All interlocks
10 Air preheaters start, electric motor Available -
healthy
keeps running

Same status as All interlocks


11 BFP and all CEPs Available
before. healthy

FD fan of unit 1will


trip on loss of both
ID. All interlocks
12 FD fans healthy except Available -
FD fan of unit 2,3,4 vibration trip
will remain
unaffected.

Boiler auto
All interlocks
13 controls: Furnace Will remain in auto. Available -
healthy
press, drum level

14 Hydrastep Will Remain Available

Actions: Responsibility

2 Ensure Boiler Trips of “Both ID fans OFF” or “ Flame Failure” Boiler Desk Engr

3 Ensure Turbine Trips on MFT and Generator Trip. TG Desk Engr.

14 | P a g e
NTPC Local Management Instruction DADRI

TITLE: MANAGEMENT OF DC SUPPLY SYSTEM FAILURE Rev. : 0

Inform HOD(C&I), HOD (EMD) and HOD (OPN) immediately after the
1 SCE
failure.

4 Ensure Tripping of PA Fans, Mills and Feeders Boiler Desk Engr

5 Ensure Closing of HOTV and LOTV Boiler Desk Engr

Start Main turbine DCEOP, DCSOP as a precautionary measure using


2 TG Desk Engr.
Hardwired pushbuttons in CCR.

Restore UPS supply as quickly as possible after ensuring healthiness of


6 SCE
at least one charger & battery streams

15 | P a g e
NTPC Local Management Instruction DADRI

TITLE: MANAGEMENT OF DC SUPPLY SYSTEM FAILURE Rev. : 0

8.0 Failure of 220 V DC supply :

The 220 V DC supply system supplies to main plant and offsite areas including CHP. It is being
used for the following purposes.
 Control supply for breaker operation, DC drives of Turbine-generator/ boiler and other
auxiliaries for whom power supply extended with breaker.
 Protection of switchgear, generators and other critical equipments.
 DC lighting (for emergencies like grid failure).
220 V DC system comprise DCDB Sec. – A & B. Each section is fed by a charger (one charger
is supplied from unit emergency switchgear – A and the other one from Unit service
switchgear-B) and a 220 V DC battery set. In case of problem in any of the battery set
/charger, the other set can cater to 100 % load.
Non-availability of DC supply could be due to
 Fuse failure in any individual control panel.
 Fuse failure /fault in individual DC feeder at DCDB / DC fuse board.
 Battery failure leading to charger failure / vice versa.
 Fault in any one of the sections of DCDB.
 Total DC failure due to inadvertent closing of bus coupler on to a fault leading to loss of
both sections.
Case 1: Failure of one 220 V DC source
Since bus coupler that interconnects the two 220V DCDBs remains in OFF condition during
normal operation, failure of one stream 220V battery and charger will result in supply failure
from one side of the DCDB. Alarm annunciation for “220 V DC Charger fail” will appear in LVS.
EMD engineer has to be informed to take corrective action on any panel that is completely OFF
due to non-function of standby 220V stream.
Depending on the DCDB which has failed, the 220V DC supply disturbance will vary.
The following table describes the status of critical systems in the unit in the event of 220V DC
any one stream failure:

Protection &
Sl Equipment Expected Interlock Indication & operation Remarks
No / System Condition Healthin
ess

Electrical

1 Generator / One source for All protection & Available


GT/UT 220V DC control interlocks in

16 | P a g e
NTPC Local Management Instruction DADRI

TITLE: MANAGEMENT OF DC SUPPLY SYSTEM FAILURE Rev. : 0

protections supply for GRP


service
not available

All protection &


Excitation
2 No change. interlocks in Available
System
service

No change.
All protection &
HT Second source
3 interlocks in Available
Switchgear will take over
service
automatically

Automatic
changeover
provided only in Protections and
UES. In other interlocks will be Indication available in OWS,
LT
4 switchgears, one available only in Remote operation not possible in
Switchgear
section will lose one section of one section.
DC supply. MCC.
Status will
remain same.

Boiler

Boiler All interlocks MFT will


1 Available Available
protections healthy act
ERV Status no Available only for
2 Available only for some ERVs. -
Operation change. some ERVs.

Status no All interlocks


3 ID fans Available -
change. healthy

Drum level BFP recirculation Scoop control will


4 Available
control will open. be available.

Turbine

Turbine
protections Turbine will trip if MFT All interlocks
1 Available -
(TG – TP 1, occurs healthy
2)

DC JOP is in Sec-A. Availability Availability


2 DC JOP Availability depends on depends on the depends on -
the affected section. affected section. the affected
section.
3 DC EOP DC EOP is in Sec-B. Availability Availability -
Availability depends on depends on the depends on
the affected section. affected section. the affected

17 | P a g e
NTPC Local Management Instruction DADRI

TITLE: MANAGEMENT OF DC SUPPLY SYSTEM FAILURE Rev. : 0

section.
DC SOP is in Sec-B. Availability Availability
4 DC SOP Availability depends on depends on the depends on
-
the affected section. affected section. the affected
section.

BFP and all Same status as before, All interlocks


5 Available
CEPs operative. healthy

Actions: Responsibility
1 Drum level to be maintained. Load to be reduced. SCE
2 Identify the DCDB which failed. SCE
Inform HOD(C&I), HOD (EMD) and HOD (OPN) immediately after the
3 SCE
failure.
If unit trips, ensure AC JOP has taken start since DC JOP may not be
4 SCE
available.

Before manually charging the dead 220V DCDB section through the bus coupler,
special care has to be taken first to ensure that no fault (eg. Earth fault) is persisting
that may lead to total failure of 220V DC systems.
- Resp.: HOD (Operation)/ HOD (EMD)/ HOD (C&I)
Case 2: Both 220V DC streams (both battery & charger unit) fail
The following table describes the status of critical systems in the unit in the event of 220V DC
both streams failure:

R
e
Protection &
Sl Equipmen m
Expected Interloc
N t/ Indication & operation a
Condition k
o System r
Healthiness k
s

Electrical
1 Generator / 220V DC All protection & Only indication available If Turbine trips
GT/UT control interlocks out Motoring will
protections supply for of service occur(main breaker
GRP not can be opened from

18 | P a g e
NTPC Local Management Instruction DADRI

TITLE: MANAGEMENT OF DC SUPPLY SYSTEM FAILURE Rev. : 0

OWS manual
available
command)

Field
All protection &
Excitation breaker
2 interlocks out Only indication available -
System will not
of service
open

220kV
Breaker
will be
operative All protection &
3 220kV Breaker since the interlocks out - -
control dc of service
is from
switchyar
d

All protection &


6.6kV UAT-ST tie Will not 220V DC control
4 interlocks out Available
auto changeover function supply fail at swgr
of service

Gen stator water


Not All interlocks
5 system and H2 Available -
affected healthy
cooling

Same
status as
Gen seal-oil before, All interlocks
6 Available
system but DC healthy
SOP not
available

Turbine
Turbine
Turbine
will trip if All interlocks
1 protections (TG Available -
MFT healthy
– TP 1, 2)
occur.

DC EOP All other


TG lub-oil
2 not interlocks Available -
system
available healthy

TG jacking oil DC JOP All other


3 system not interlocks Available -
available healthy

4 TG barring gear Not All interlocks Available -

19 | P a g e
NTPC Local Management Instruction DADRI

TITLE: MANAGEMENT OF DC SUPPLY SYSTEM FAILURE Rev. : 0

system
affected healthy

Vacuum
breaker
TG Evacuation will
All interlocks
5 system remain Available -
healthy
close and
will not be
operative

Same
BFP and all CEPs status as All remote trips MDBFP recirculation
6 before, Only indications.
out of service. valves will open
not
operative.

LP bypass
Not All interlocks
7 system Available -
affected healthy

All remote
Instrument air 220V DC control
Will keep protections out
8 and plant air Only indications supply fail at SWGR
running of service if
compressors if Unit #1 DC fails
Unit #1 DC fails

CW pumps All remote


Will keep 220V DC control
9 protections out Only indications
running supply fail at SWGR
of service

ECW pumps All remote


Will keep 220V DC control
10 protections out Only indications
running supply fail at SWGR
of service

Deaerator,
Not All interlocks
11 hotwell level Available -
affected healthy
control

Boiler
Scoop
Drum level BFP recirculation
1 control will Available
control normal operation
be available.

Furnace press All interlocks


2 Not affected Available -
Control healthy

3 ERV Not operative All interlocks Only indications Solenoid is 220V DC


electromotive out of operated
safety relief

20 | P a g e
NTPC Local Management Instruction DADRI

TITLE: MANAGEMENT OF DC SUPPLY SYSTEM FAILURE Rev. : 0

valves service

Oil firing
equipment
All will trip if MFT All interlocks
4 (LOTV, LONV, Available -
acts healthy
HOTV, HONV,
HORV)

Coal firing
Mills & Feeders All remote
equipment trips & EPB Only indication
5 will keep running -
(Mills, feeders, of mills out available
HAG) of service

All remote
trips Blade pitch of both
Both PA fans will including Only indication PA fans will be
6 PA Fans
keep running MFT & EPB available driven to minimum
out of on MFT
service

Will not trip


All interlocks
7 Seal air fans unless both PA Available -
healthy
fans trip

Same status as
All other
before, DC
8 Scanner air fans interlocks Available -
scanner air fan
healthy
not available

Air preheaters All interlocks


9 Not affected Available -
(SAPH & PAPH) healthy

HP bypass All interlocks


10 Not affected Available -
system healthy

All remote
protections 220V DC control
11 ID fans Will keep running Only indications
out of supply fail at SWGR
service

All remote
protections 220V DC control
12 FD fans Will keep running Only indications
out of supply fail at SWGR
service

Actions: Responsibility
1Inform HOD(C&I), HOD (EMD) and HOD (OPN) immediately after the failure. SCE

21 | P a g e
NTPC Local Management Instruction DADRI

TITLE: MANAGEMENT OF DC SUPPLY SYSTEM FAILURE Rev. : 0

2Maintain Drum level with BFPs. Standby BFP cannot be started.) TG Desk Engr.
Keep watch in important parameters of unit BLR/TG desk E
Close HP/LP bypass valves TG Desk Engr.
DG start in auto. Close DG breaker from local switchgear & than in UES UCE
All pumps from UES to be started TG Desk Engr.
open Generator main breaker from OWS UCE
Throttle condenser inlet valves and close MS1 /2 BLR/TG desk E
APH-A /B electrical motors to be started BLR desk E

220 V DC supply extended to different Offsite locations as following:

Unit #1: 1. Water treatment plant.

2. Raw water pump house.


3. FOPH
4. CHP
5. Compressor House
Unit #2: 1. FOPH.
2. Ash water pump house.
3. Water treatment plant.
4. CHP
Unit #3: 1. FOPH.
2. Ash water pump house.
3. CHP 4. Water treatment plant.

9.0 Failure of 110 V AC CONTROL SUPPLY:

110 V AC control supply is provided regulation and frequency tracking. Each UPS has a common
DC bus which receives DC power from a rectifier/charger and common battery bank. The two
rectifier/charger systems receive 415 V AC incoming supply from Unit service switchgear or Unit
emergency switchgear . This DC power is converted to give 240 V AC power output by inverter
circuit of each UPS. Besides the two UPS streams, there is a bypass emergency supply directly
coming from Unit service switchgear which will automatically come to service in the event of both
UPS failure.

Protection &
Equipment / Expected Indication &
Interlock Remarks
Sl System Condition operation
No Healthiness

Actions: Resposibility

22 | P a g e
NTPC Local Management Instruction DADRI

TITLE: MANAGEMENT OF DC SUPPLY SYSTEM FAILURE Rev. : 0

Inform HOD(C&I), HOD (EMD) and HOD (OPN) immediately after the
1 SCE
failure.

Start Main turbine DCEOP, DCSOP and TDBFP DCEOPS as a


2 TG Desk Engr.
precautionary measure using Hardwired pushbuttons in CCR.

3 Monitor Unit Running with MAX DNA station provided in CER UCE

Checked and certified by

Balram Sharma(O)

Pankaj Shukla(C&I)

Jayathran PS.(EMD)

23 | P a g e