Escolar Documentos
Profissional Documentos
Cultura Documentos
1
3 Pole high impedance differential relay 7VH83
2
3 Pole high impedance differential relay 7VH83
Technical Data
CT Circuits 50 Hz or 60 Hz
Normal frequency
Thermal Withstand
2 sec 505 volt
Continuous 400 volt
Measuring Circuit
Setting range
Differential protection 10 to 280 volts in 10 volt steps
Buswire supervision 5 to 160 volts in 5 volt steps
Buswire supervision timer 0 to 15 seconds in 1 second steps
Tripping Time
1,1 x setting 56 ms
1,2 x setting 43 ms
1,5 x setting 30 ms
5 x setting 21 ms
Reset Time 20 ms
3
3 Pole high impedance differential relay 7VH83
Environmental Withstand
Insulation Tests
HV Test IEC 255-5 2kV (rms); 50/60 Hz; 1 min
Impulse Test IEC 255-5 5kV (peak); 1,2/50 µs; 0,5J; sec
3 positive and 3 negative
shots at intervals of 5s
EMI Test
Weight Dimensions
Case
Ordering Data
Order No.
3 Pole High-Impedance Differential Relay 7VH8300 - A
With CT Shorting Input Relay
Auxiliary Supply Voltage
24/48V dc 3
60/110/125V dc 4
220/250V dc 5
Mechanical Construction
Reset Voltage
3
24/48V dc 4
60/110/25V dc 5
220/250V dc
ORDERING DATA
Please specify the varistor type required ( see page 10) for your application or consult your
nearest Siemens office.
5
3 Pole high impedance differential relay 7VH83
6
3 Pole high impedance differential relay 7VH83
7
3 Pole high impedance differential relay 7VH83
Relay setting
List of abbreviations
RL = Lead resistance between furthest current transformer and relay connection point.
RR = Relay impedance.
VF = The theoretical voltage which would be produced across the relay circuit
under internal fault conditions.
I FM
VF = ( RCT + 2 R L + RR )
N
VP = Peak voltage across relay circuit under maximum internal fault conditions.
K = Varistor constant.
B = Varistor constant.
8
3 Pole high impedance differential relay 7VH83
Calculation of relay protection l accidental open or short shown. From this curve, it is
setting circuit of the secondary of easy to determine the mag-
one or more CT’s. netising current IE for a sec-
The minimum setting voltage to ondary voltage of V.
ensure stability is The operating current of the
relay is 5mA irrespective of the CT supervision circuit
I voltage selected excluding the
VS ≥ FM ( RCT + 2 R L ) current drawn by the external If the CT’s have broken or
N varistor. shorted connections, the
protective relay may detect this
The relay plug setting voltage Configuration are generally condition as a busbar fault and
VR must be set to the nearest provided therefore trip all the circuit
tap above VS. The minimum breakers in that zone. If several
knee point voltage must be l polyphase faults; requiring a CT’s are associated in the zone,
three relay type 7VH83 the disconnection of one of them
VK≥2VR phase. Current transformer (corresponding perhaps to a
supervision, protects against lightly loaded feeder) will result
The primary current for operation the accidental opening of a CT in a very low fault current
is given by connection. This occurrence measurement. If this unbalance
normally causes a fault current is lower than the 7VH83
IP=N(IR+nIE) that is too low to activate the protection setting, this condition
relay circuits, however the will not be detected. Therefore a
If the resultant value of lP is too condition should be signalled more sensitive monitoring circuit
low it may be increased by the before the appearance is required for CT supervision.
addition of a shunt resistor RSH of an actual fault . This monitoring circuit is integral
to give a current of The supervision would to the 7VH83 relay.
register the low unbalanced
ISH=VR/RSH current and control a time CT Requirements
delayed output alarm.
The new increased value of The correct operation of the high
primary current Knee-point voltage of current impedance circulating current
transformers protection is largely dependant
on the CT dimensioning.
lP = N(IR+nIE+ISH)
The CT’s will not be saturated by
the short-circuit current if the To enable the CT manufacturer
Setting advice
knee-point voltage is greater to design an appropriate CT, a
than twice the maximum voltage class X specification, as outlined
With particular reference to high
likely to be applied across the in the BS3938 or similar should
impedance busbar protection,
terminals of the relay during the be specified and would include:
the plant and equipment should
fault. 1 . CT Knee point voltage (VK)
have protection with the
2. CT secondary resistance
following features:
(RCT)
V RMAX = 2 2VK (VF − VK ) 3. CT magnetisation/excitation
l adequate sensitivity
current(IE)
l fast response time
4. Turns ratio (N)
l stability, when external
At the maximum secondary 5. Thermal rating of the
faults occur
secondary turns to primary
l selectivity to allow
through fault current the varistor
should limit the voltage to load current.
disconnection of only
< 1 OOOV rms if possible.
the faulted section
In the case of existing current
l permanent supervision of
Determination of magnetising transformers the above details
the current transformers
current IE can be obtained either from the
manufacturers design test
Relay operation shall not sheets, or by carrying out a
occur on: The manufacturer of the current
transformer supplies the magnetising characteristic test
comparing excitation current to
l saturation of the CT’s by
magnetic characteristics from
which the magnetising current the applied voltage, a resistance
the transient dc compo- measurement and a primary to
curve versus the secondary
nent when a serious fault secondary ratio check.
voltage is
occurs outside the zone
9
3 Pole high impedance differential relay 7VH83
Varistor Selection
Each 7VH83 relay is normally tance and applied voltage is If the current transformer
applied with an external varistor non-linear, i.e. an increase in the secondary voltage is to be limit-
which must be connected applied voltage will result in a ed to a safe level during max-
across the relay input terminals. decrease in the resistance and imum internal fault conditions
The varistor limits the voltage hence an increase in the cur- then a varistor may be required.
developed across the CT and rent. The change in resistance Generally if
relay terminals under fault con- occurs instantaneously.
ditions. VRMAX > 2KV
The electrical characteristics can
B
A varistor is a non-linear or be expressed as V = KI where then a varistor is required
voltage dependent resistor. It is K and B are constant for any
a ceramic semi-conducting one varistor.
resistance material in which the
VRMAX = 2 2VK (VF − VK )
relationship between resis-
Table 2
Table 3
10
3 Pole high impedance differential relay 7VH83
Relays which are supplied tests, must subsequently be
unmounted and not intended for Commisioning preliminaries replaced.
immediate installation should be Inspection It is only necessary to check the
returned to their protective relay at the setting on which it is
cartons. Carefully examine the module to be used. The relay must not
and case to see that no damage be used at any setting other than
Care must be taken when has occurred during transit. that for which the setting has
unpacking and installing the Check that the relay serial been calculated.
relays so that none of the parts number on the module, case
are damaged or their settings and cover are identical, and that Commissioning Tests
altered and must at all times be the model number and rating Test Equipment
handled by skilled persons only. information are correct.
1 Secondary injection test
Relays which have been Check that the external wiring is equipment capable of
removed from their cases should correct to the relevant relay providing an AC voltage
not be left in situations where diagram or scheme diagram. supply of up to at least
they are exposed to dust or 120% of the relay setting.
damp. This particularly applies Particular attention should be 1 Test plug for use with test
to installations which are being paid to the correct wiring and block if fitted.
carried out at the same time as value of any external resistors 3 Calibrated multimeters 0-10
construction work. indicated on the wiring amp AC 0 - 400 volt AC.
diagram/relay rating information. 1 Set of primary injection
If relays are not installed testing equipment.
immediately upon receipt they Note that shorting switches
should be stored in a place free shown on the relay diagram are General
from dust and moisture in their fitted internally across the
original cartons and where relevant case terminals and If the relay is wired through a
dehumidifier bags have been close when the module is test block it is recommended
included in the packing they withdrawn. It is essential that that all secondary injection tests
should be retained. such switches are fitted across should be carried out using this
all CT circuits. block.
The action of the de-humidifier
crystals will be impaired if the If a test block is provided, the Ensure that the main system
bag has been exposed to damp connections should be checked current transformers are shorted
ambient conditions and may be to the scheme diagram, before isolating the relay from
restored by gently heating the particularly that the supply the current transformers in
bag for about an hour, prior to connections are to the ’live’ side preparation for secondary
replacing it in the carton. of the test block. injection tests.
11
3 Pole high impedance differential relay 7VH83
Record the current at which the is injected into each current be very low, only a few milliamps
relay operates (A2). It should be transformer in turn and if the connections are correct. A
approximately 5mA at setting. increased until the relay high reading (twice the injected
operates. The voltage at which current, referred through the
Note also the voltage at which the relay operates should be current transformer ratio)
the relay operates which should within ± 10% of the relay setting indicates that one of the current
correspond to the setting VR of voltage VR. The primary current transformers polarity is reversed.
the relay with a tolerance of for operation and relay current
± 10%. The total secondary should be noted. Injection should be carried out
current for operation will be through each phase to neutral.
given on ammeter A1.This test
should be repeated for each For large machines the machine In the case of machine protec-
pole of the relay. itself can be used to provide the tion similar stability tests must
fault current to check the primary be carried out by injecting into
Record the value at which the fault setting as shown in Figure 8. one and out of another current
relay picks up and then reduce The machine should be run up to transformer connected on the
the voltage until it drops off. speed with no excitation. The same phase.
From these two values calculate excitation should then be
the drop off/pick up value. It increased until the relays have all For large machines, the machine
should be approximately 0,95. operated. The primary current, itself can be used to provide the
relay current and relay voltage fault current, but the short circuit
Primary injection testing should be noted as each relay must now be fitted as shown in
operates. Figure 9. The machine should
It is essential that primary be run up to normal speed and
injection testing is carried out to Through fault stability the excitation increased until the
prove the circuit is dead, isolated primary current is approximately
from the remainder of the With any form of unbalanced full load, when the spill current
system and that only those earth protection it is necessary to should be checked.
connections associated with the check that the current trans-
primary test equipment are in formers are correctly connected. All other types of balanced
position. For this purpose the circuit protection should be tested in a
shown in Figure 7 may be used. similar manner.
Primary fault setting During this test the relay is
shorted out and the spill current At the conclusion of the tests
The primary fault setting of any through the relay circuit A2 is ensure that all connections are
balanced scheme can be measured. The current is correctly restored and any
checked using the circuit shown increased up to as near full load shorting connections removed.
in Figure 6. The primary current as possible and the spill current
noted. The spill current should
12
3 Pole high impedance differential relay 7VH83
TEST RESULTS
Relay CT Shorting Switch
Secondary Voltage to operate relay
Phase Total Current A1 Relay Current (A2) P.U. Volts D.O. Volts
A
B
C
Table 5
Table 6
Table 7
Table 8
Maintenance
13
3 Pole high impedance differential relay 7VH83
14
3 Pole high impedance differential relay 7VH83
15
3 Pole high impedance differential relay 7VH83
The information contained in this publication is subject to change without prior notice.
Siemens Limited
P O Box 207 lsando 1600
South Africa
Telephone (011) 921-7000
16