Design low-rise reinforced concrete building (Restaurant in Siklós)

Biaxial bending verification


a a
 MEdy   MEdz  N ed
     1 s  
MRdy MRdz N Rdy1
   

a  1 if s  0.1 

 s  0.7 
 1.5  0.5  if s  0.7 a a
 0.3   MEdy   MEdz 
     "Ok"
MRdy3 MRdz3
 s  0.1     
1  0.5  otherwise
 0.6 
Reinforcement verification:
 N ed 
2
Minimum areas of reinforcement Asmin  max 0.002 Ac 0.1   mm
fyd
 
Maximum areas of reinforcement
2
Asmax  0.04 Ac  mm


 2
As.prov  n  l   mm
4
2
Use 6 H18

As  "C-S is not verified" if Ac .01  As.prov 

"cross section is verified" otherwise

Asmax  As.prov  Asmin


h b
spacingh   mm spacingb   mm Ok
nh nb

Transversal reinforcement
Maximum spacing
  l
 
smax  min 0.6 h 12  l 240mm  mm  Stirrup  max 6mm
 4 
  mm
Minimum spacing
Links: 35 H6
smin  20mm
 l   @120 mm
nStirrup  round   0.5 0
 
smax  90mm
   The cross section is verified

81