SHIELDING HEAT-ACTUATED DEVICES

INTRODUCTION
Closed head sprinklers, heat detectors and other heat-actuated devices (HADs) are sometimes
located where they can overhead water discharge, thus increasing the potential to delay response. In-
rack sprinklers discharging at higher levels can discharge water on lower level in-rack sprinklers. As
in the same, sprinklers under gratings, water spray nozzles protecting specific hazards and heat
detectors can be discharged upon by overhead protection. Outdoors, HADs can be introduced to the
“wetting” effect similar to overhead discharge from hose streams, water cannons, rain, sleet and
snow.
To prevent the overhead water discharge or “wetting” effect of sprinklers installing small metal
canopies, called water shields or weather hoods is recommended. Listed intermediate level sprinklers
are not required to follow the recommendation for shield sizing.

POSITION
Install shields over all HADs subject to overhead water discharge:
Use shields of substantial metal construction with a minimum dimension of not less than four times
the vertical distance between the bottom of the fusible element and the shield. This normally
translates into a shield at least 6 in. (15 cm) square or 6 in. (15 cm) in diameter.
Sprinklers with integral shields listed by UL as “Intermediate Level” sprinklers or by FM Approvals as
“Racked Storage” sprinklers are acceptable indoors where shields would be required over ordinary
sprinklers. Listed intermediate level sprinklers are not required to follow the recommendation for
shield sizing.

DISCUSSION
Per NFPA 13, sprinklers under open gratings shall be of the intermediate level/rack storage type of
otherwise shielded from the discharge of overhead sprinklers. Shields over automatic sprinklers
should not be less, in least dimension, than four times the distance between the shield and fusible
element, except special sprinklers incorporating a build-in shield need not comply with his
recommendation if listed for the particular application.
Sprinklers in locations not addressed by NFPA 13 and other types of HADs could also require
protection from wetting.
The integral shields on listed sprinklers will not protect the fusible element from rain, sleet or snow.
Sprinklers with larger, separate shields should be used for outdoor installations.
Water shields are not heat collectors, and they do not improve detector response time. Although a
shield may initially delay the flow of hot gases past a detector, most of the rising gases establish a
path around the obstruction offered by the shield. Larger metal canopies, up to 18 in. by 18 in. by 3 in.
deep (46 cm by 46 cm by 8 cm deep), are marketed for use with outside rate-of-rise type HADs and

100 Constitution Plaza, Hartford, Connecticut 06103 Copyright 2015, Global Asset Protection Services LLC

Global Asset Protection Services LLC and its affiliated organizations provide loss prevention surveys and other risk management, business continuity and facility asset
management services. Unless otherwise stated in writing, our personnel, publications, services, and surveys do not address life safety or third party liability issues. The
provision of any service is not meant to imply that every possible hazard has been identified at a facility or that no other hazards exist. Global Asset Protection Services LLC
and its affiliated organizations do not assume, and shall have no liability for the control, correction, continuation or modification of any existing conditions or operations. We
specifically disclaim any warranty or representation that compliance with any advice or recommendation in any document or other communication will make a facility or
operation safe or healthful, or put it in compliance with any law, rule or regulation. If there are any questions concerning any recommendations, or if you have alternative
solutions, please contact us.
GAP.12.1.1.3

are more effective for trapping updrafts of heated air. However, these canopies are not generally
used for sprinklers or thermostats.
Cold soldering and skipping of sprinklers are not the same as wetting. These problems are addressed
in GAP.12.1.1.0.