AHU Modification Report - Tower-1 Pilot Floors

Overall Analysis / Recommended AHU Modifications as per AHU Manufacturer


Tower & AHU Reference Data AHU ESP Analysis Fan Curve Analysis Chilled Water Flow Analysis Cooling Capacity Analysis
(Klimak)

Difference w/r to Existing

Existing AHU ISP (Pa)


% Difference w/r to
Existing Airflow Airflow as per AEB

Existing AHU
Existing AHU AEB AEB Calc. Fan operating AEB Air Fan operating AEB Air Fan operating AEB Calculated
at AHU Heat Load CALC TSP At 100% TSP At TSP At 40% Fan Pulley/
AHU Quantity Design ESP Calculated Air flow rate Point within flow rate at Point within flow rate at Point within Existing Design AEB Calculated AHU Existing Cooling Difference w/r to

AHU
Diversified Peak Diversified PEAK AEB 60% AEB AEB Motor Pulley Cooling Coil analysis as per Fitout
S.No. Tower Ref# Level Type Level Ref# AHU Ref# Including Considering ESP at 100% Recommended 60% Recommended 40% Recommended Chilled Water Chilled Water Cooling Capacity (Fitout existing Cooling Any other modifications / Conclusion
Load with Base with Base Build Diversified Diversified Diversified to be changed Design
Typical Floors Induction VAV considering PI Diversified Region of Fan Diversified Region of Fan Diversified Region of Fan Flow Rate (l/s) Flow Rate (l/s) Capacity (Kw) Cooling Capacity
Build +2% Duct Leakage Load (Pa) Load (Pa) Load (Pa) (Y/N)
(Pa) VAV (Pa) Load Curve Load Curve Load Curve Capacity) (Kw)
(l/s) (L/s)

The required total cooling


Existing fan and motor can operate at
1 T-1 Prayer L2 AHU-T1-07 1 4602 4542 1 486 420 66 277 4542 697 ✔ 2725 251 ✔ 1817 112 X 1.832 1.84 67.5 68.4 -0.9 Yes load can be met with existing
100% & 60% airflow as per fitout design
coil

The required total cooling Existing fan and motor can operate at
2 T-1 Prayer L2 AHU-T1-07A 1 1992 2024 -2 464 341 123 292 2024 633 ✔ 1214 228 ✔ 810 101 X 1.03 0.86 38 31.9 6.1 Yes load can be met with existing @ 100% & 60% air flow as per fitout
coil design.

The required total cooling


Existing fan and motor can operate at
3 T-1 Prayer L2 AHU-T1-07B 1 1994 2073 -4 449 366 83 320 2073 686 ✔ 1244 247 ✔ 829 110 X 0.994 0.86 36.6 31.8 4.8 Yes load can be met with existing
100% & 60% airflow as per fitout design
coil

Existing fan model has to be


The required total cooling
changed to ADH-G2E4-280 to meet
4 T-1 Type B1 L3 AHU-T1-07 1 3866 3356 13 494 425 69 258 3356 683 X 2014 246 X 1342 109 X 1.637 1.44 60.3 53.5 6.8 No load can be met with existing
100% air flow at revised condition but
coil
existing motor can be retained

The required total cooling


Existing fan and motor can operate at
5 T-1 Type B1 L3 AHU-T1-08 1 4068 4067 0 494 446 48 256 4067 702 ✔ 2440 253 ✔ 1627 112 X 1.768 1.65 65.1 61.2 3.9 Yes load can be met with existing
100% & 60% airflow as per fitout design
coil
The required total cooling
Existing fan and motor can operate at
6 T-1 Type C L12 AHU-T1-07 7 3791 4101 -8 494 442 52 256 4101 698 ✔ 2461 251 ✔ 1640 112 X 1.616 1.58 59.5 58.9 0.6 Yes load can be met with existing
100% & 60% airflow as per fitout design
coil

The required total cooling


Existing fan and motor can operate at
7 T-1 Type C L12 AHU-T1-08 7 3940 4085 -4 494 430 64 253 4085 683 ✔ 2451 246 ✔ 1634 109 X 1.732 1.55 63.8 57.5 6.3 Yes load can be met with existing
100% & 60% airflow as per fitout design
coil

The required total cooling


Existing fan and motor can operate at
8 T-1 Type B L13 AHU-T1-07 4 3812 3880 -2 494 398 96 256 3880 654 ✔ 2328 235 ✔ 1552 105 X 1.622 1.55 59.7 57.8 1.9 Yes load can be met with existing
100% & 60% airflow as per fitout design
coil

The required total cooling


Existing fan and motor can operate at
9 T-1 Type B L13 AHU-T1-08 4 4403 4278 3 489 499 -10 264 4278 763 ✔ 2567 275 ✔ 1711 122 X 1.853 1.65 68.2 61.2 7 Yes load can be met with existing
100% & 60% airflow as per fitout design
coil

It is not possible to meet


the required total cooling Existing fan and motor can operate at
10 T-1 Type A L14 AHU-T1-09 1 3789 4004 -6 494 394 100 256 4004 650 ✔ 2402 234 ✔ 1602 104 X 1.624 1.71 59.8 63.6 -3.8 Yes
load with existing coil. 100% & 60% airflow as per fitout design
Cooling to to be replaced.

The required total cooling


load can be met with existing Existing fan and motor can operate at
11 T-1 Type A L14 AHU-T1-10 1 3526 3567 -1 434 382 52 249 3567 631 ✔ 2140 227 ✔ 1427 101 X 1.427 1.47 54.2 54.6 -0.4 Yes coil 100% & 60% airflow as per fitout design