Electrical network protection

Sepam series 80
Configuration

Sepam label: ...................................................................... sepam F3 (R5)


Application type: ............................................................... M81
Configuration file: ............................................................. S2902918-01
Date of last modification: ................................................. 01/11/2010
Date printed: ...................................................................... 03/11/2010

Customer: .......................................................................... a
Project: .............................................................................. a
Switchboard: ..................................................................... a
Cubicle: ............................................................................. a
Contents

1. GENERAL SETTINGS ............................................................................................................................................ 3


1.1. Hardware setup .......................................................................................................................................... 3
1.1.1. ACE 850 (communication network interface) ............................................................................... 4
1.2. General characteristics .............................................................................................................................. 5
1.3. CT-VT sensors ........................................................................................................................................... 6
1.4. CT/VT circuit supervision ........................................................................................................................... 7
1.5. Particular characteristics ............................................................................................................................ 7
1.6. Predefined control logic ............................................................................................................................. 8
1.7. Logic input/output assignment ................................................................................................................... 8
1.8. GOOSE input assignment .......................................................................................................................... 9
2. SET PROTECTIONS ............................................................................................................................................... 10
2.1. Motor M81 ................................................................................................................................................. 10
2.2. Protection units on ..................................................................................................................................... 11
2.3. Customized tripping curve ......................................................................................................................... 11
2.4. 50/51: Phase overcurrent ........................................................................................................................... 11
2.5. 50N/51N: Earth fault .................................................................................................................................. 12
2.6. 50BF: Breaker failure ................................................................................................................................. 12
2.7. 46: Negative sequence current / unbalance .............................................................................................. 12
2.8. 49RMS: Thermal overload ......................................................................................................................... 13
2.9. 67N: Directional earth fault ........................................................................................................................ 13
2.10. 32P: Active overpower ............................................................................................................................. 13
2.11. 32Q: Reactive overpower ........................................................................................................................ 14
2.12. 37: Phase undercurrent ........................................................................................................................... 14
2.13. 48/51LR: Excessive starting time and locked rotor ................................................................................. 14
2.14. 66: Starts per hour ................................................................................................................................... 14
2.15. 40: Field loss ............................................................................................................................................ 14
2.16. 78PS: Pole slip ......................................................................................................................................... 14
2.17. 12: Overspeed .......................................................................................................................................... 15
2.18. 14: Underspeed ....................................................................................................................................... 15
2.19. 27D: Positive sequence undervoltage ..................................................................................................... 15
2.20. 27R: Remanent undervoltage .................................................................................................................. 15
2.21. 27: Undervoltage ...................................................................................................................................... 16
2.22. 59: Overvoltage ........................................................................................................................................ 16
2.23. 59N: Neutral voltage displacement .......................................................................................................... 16
2.24. 47: Negative sequence overvoltage ........................................................................................................ 16
2.25. 81H: Overfrequency ................................................................................................................................. 17
2.26. 81L: Underfrequency ............................................................................................................................... 17
2.27. 38/49T: Temperature monitoring ............................................................................................................. 17
3. LOGIPAM SETTINGS ............................................................................................................................................. 18
3.1. Logipam ..................................................................................................................................................... 18
4. DEFINITION OF EQUATIONS ................................................................................................................................ 19
4.1. Logic equations .......................................................................................................................................... 19
5. SET CONTROL MATRIX ........................................................................................................................................ 20
5.1. Protection matrix ........................................................................................................................................ 20
5.2. Control logic output matrix ......................................................................................................................... 25
5.3. Logic input matrix ....................................................................................................................................... 26
5.4. Logic equation output variable matrix ........................................................................................................ 26
5.5. GOOSE input matrix .................................................................................................................................. 27
6. SET FUNCTIONS .................................................................................................................................................... 30
6.1. Disturbance recording ................................................................................................................................ 30
1. GENERAL SETTINGS

1.1. Hardware setup

Sepam label: .................................................................................................................. sepam F3 (R5) Application type: M81 Model: In tegrated UMI
MES120 (14 input + 6 output module) n°1 ................................................................. Present
MES120 (14 input + 6 output module) n°2 ................................................................. Absent
MES120 (14 input + 6 output module) n°3 ................................................................. Absent
MSA141 (1 analog output module) .............................................................................. Present Type of output 4 - 20mA Variable: Current phase 2 (x 0.1 A)
Min. value: -100 Max. value: 100
MET148 (8 temperature sensors module) n°1 ........................................................... Present Type of t emp. sensor PT100 Assignment of temperature sensors Other Use
MET148 (8 temperature sensors module) n°2 ........................................................... Absent
COM1 module ................................................................................................................ Absent
COM2 module ................................................................................................................ Absent
ACE 850 (communication network interface) (Ethernet) .......................................... Present Communication protocol Eth ernet-FO IP address 172.20.12.15

Sepam label: sepam F3 (R5) 03/11/2010


Application type: M81 3 / 30
1.1.1. ACE 850 (communication network interface)

ACE850 advanced parameters SNMP SNTP


Description Setting Description Setting Description Setting
Port P1 100BaseFX (Full Duplex) Enable traps No Enable SNTP Yes
Port P2 100BaseFX (Full Duplex) Trap community name public Time zone UTC
Frame type Eth ernet II Manager 1 IP address 0.0.0.0 Enable DST No
IP address 172.20.12.15 Manager 2 IP address 0.0.0.0 DST offset 60 min
IP subnet mask 255.255.0.0 System name sepam F3 (R5) DST starts Last Sunday of March at 2:00
IP de fault gateway 0.0.0.0 System c ontact DST ends Last Sunday of October at 3:00
CID override IP settings No System loca tion Primary server IP address 10.10.10.10
FTP session idle time 30 s Read-Only community name public Secondary server IP address 0.0.0.0
TCP keep alive 30 s Read/Write community name priva te Poll interval 60 min

IP filtering RSTP User accounts


Description Setting Description Setting Description Setting
Enable filtering No Enable RSTP Yes User control enable Yes
IP address Mod bus IEC 61850 RSTP bridge priority 61440 Name Password Group
IP address 1 0.0.0.0 No No Hello time 2s User 1 Admin **** Administrator
IP address 2 0.0.0.0 No No Forward delay time 21 s User 2
IP address 3 0.0.0.0 No No Max age time 40 s User 3
RSTP max transmit
IP address 4 0.0.0.0 No No 32 User 4
count
IP address 5 0.0.0.0 No No RSTP cost style RSTP
IP address 6 0.0.0.0 No No
IP address 7 0.0.0.0 No No
IP address 8 0.0.0.0 No No
IP address 9 0.0.0.0 No No
IP address 10 0.0.0.0 No No

Sepam label: sepam F3 (R5) 03/11/2010


Application type: M81 4 / 30
1.2. General characteristics

Description Setting Description Setting


Network frequency 50 Hz Sepam working language English
Incomer/feeder Feeder Time synchronization mode None
Phase rotation direction 1_2_3 Auxiliary voltage monitoring (Vaux) Off
Active setting group for all protection functions. Setting group A Rated Vaux 48 Vdc
Remote protection sett ings enabled No Low threshold alarm 80 % Vaux
Remote control with s elect before operate (SBO) No High threshold alarm 120 % Vaux
Integration period 5 min Cumulative breaking current alarm threshold 65535 kA2
Meter increment - Active energy 0.1 kWh
Meter increment - Reactive energy 0.1 kVARh
Temperatures °C

Sepam label: sepam F3 (R5) 03/11/2010


Application type: M81 5 / 30
1.3. CT-VT sensors

Sepam label: sepam F3 (R5) 03/11/2010


Application type: M81 6 / 30
1.4. CT/VT circuit supervision

1.5. Particular characteristics

Motor/Generator speed
Rated speed (Rpm) 3000 rpm Zero speed threshold 5 %
Pulses per rotation 1

Sepam label: sepam F3 (R5) 03/11/2010


Application type: M81 7 / 30
1.6. Predefined control logic

Description Setting
Switchgear control No
Logic discrimination No
Load shedding No
Time delay 0 ms
Restart No
Time delay 0 ms
Max. dip duration 300 s

1.7. Logic input/output assignment

Used Charact. Pulse Used Charact. Pulse


O1 Yes NO O101 Yes NO
O2 Yes NC O102 Yes NO
O3 Yes NO O103 Yes NO
O4 Yes NO O104 Yes NO
O5 Yes NC O105 Yes NO
O106 Yes NO

Logic input Neg Latch


I101 Breaker closed
I102 Breaker open
I103 Other use
I104 Other use
I105 Other use
I106 Other use
I107 Other use
I108 Other use
I109 Other use
I110 Other use
I111 Other use
I112 Other use
I113 Other use
I114 Other use

Sepam label: sepam F3 (R5) 03/11/2010


Application type: M81 8 / 30
1.8. GOOSE input assignment

GOOSE Input Neg GOOSE Input Neg


G401 ------- (Not used) ----------- G501 ------- (Not used) -----------
G402 ------- (Not used) ----------- G502 ------- (Not used) -----------
G403 ------- (Not used) ----------- G503 ------- (Not used) -----------
G404 ------- (Not used) ----------- G504 ------- (Not used) -----------
G405 ------- (Not used) ----------- G505 ------- (Not used) -----------
G406 ------- (Not used) ----------- G506 ------- (Not used) -----------
G407 ------- (Not used) ----------- G507 ------- (Not used) -----------
G408 ------- (Not used) ----------- G508 ------- (Not used) -----------
G409 ------- (Not used) ----------- G509 ------- (Not used) -----------
G410 ------- (Not used) ----------- G510 ------- (Not used) -----------
G411 ------- (Not used) ----------- G511 ------- (Not used) -----------
G412 ------- (Not used) ----------- G512 ------- (Not used) -----------
G413 ------- (Not used) ----------- G513 ------- (Not used) -----------
G414 ------- (Not used) ----------- G514 ------- (Not used) -----------
G415 ------- (Not used) ----------- G515 ------- (Not used) -----------
G416 ------- (Not used) ----------- G516 ACE850 presence

Sepam label: sepam F3 (R5) 03/11/2010


Application type: M81 9 / 30
2. SET PROTECTIONS

2.1. Motor M81

Sepam label: sepam F3 (R5) 03/11/2010


Application type: M81 10 / 30
2.2. Protection units on

On Latching Trip C.B. On Latching Trip C.B. On Latching Trip C.B.


50/51 - 1 X X 49RMS - 1 X X 38/49T - 4 X X
50/51 - 2 X X 27 - 1 X 38/49T - 5 X X
50N/51N - 1 X X 38/49T - 1 X X 38/49T - 6 X X
50N/51N - 2 X X 38/49T - 2 X X 38/49T - 7 X X
46 - 1 X X 38/49T - 3 X X 38/49T - 8 X X

2.3. Customized tripping curve

1 2
I/Is 1.00 10.00
T(s) 1.00 1.00

2.4. 50/51: Phase overcurrent

Measurement Settings
Unit Activity Latching Confirmation Group
origin Tripping curve Threshold Delay Timer hold curve Timer hold
Sta ndard
No A 1 kA 1s Definite time 0 ms
1 On X I1,I2,I3 inver se time
confirmation
B Definite time 1.26 kA 100 ms Definite time 0 ms
No A Definite time 2.80 kA 100 ms Definite time 0 ms
2 On X I1,I2,I3
confirmation B Definite time 1.26 kA 100 ms Definite time 0 ms
No A Definite time 1.26 kA 100 ms Definite time 0 ms
3 Off X I1,I2,I3
confirmation B Definite time 1.26 kA 100 ms Definite time 0 ms
No A Definite time 1.26 kA 100 ms Definite time 0 ms
4 Off X I1,I2,I3
confirmation B Definite time 1.26 kA 100 ms Definite time 0 ms
No A Definite time 1.26 kA 100 ms Definite time 0 ms
5 Off X I1,I2,I3
confirmation B Definite time 1.26 kA 100 ms Definite time 0 ms
No A Definite time 1.26 kA 100 ms Definite time 0 ms
6 Off X I1,I2,I3
confirmation B Definite time 1.26 kA 100 ms Definite time 0 ms
No A Definite time 1.26 kA 100 ms Definite time 0 ms
7 Off X I1,I2,I3
confirmation B Definite time 1.26 kA 100 ms Definite time 0 ms
No A Definite time 1.26 kA 100 ms Definite time 0 ms
8 Off X I1,I2,I3
confirmation B Definite time 1.26 kA 100 ms Definite time 0 ms

Sepam label: sepam F3 (R5) 03/11/2010


Application type: M81 11 / 30
2.5. 50N/51N: Earth fault

Measurement Settings
Unit Activity Latching Group
origin Tripping curve Threshold Delay Timer hold curve Timer hold H2 rest.
Sta ndard
A 200 A 1s Definite time 0 ms
1 On X Io sum inver se time
B Definite time 630 A 100 ms Definite time 0 ms
A Definite time 800 A 100 ms Definite time 0 ms
2 On X Io sum
B Definite time 630 A 100 ms Definite time 0 ms
A Definite time 630 A 100 ms Definite time 0 ms
3 Off X Io sum
B Definite time 630 A 100 ms Definite time 0 ms
A Definite time 630 A 100 ms Definite time 0 ms
4 Off X Io sum
B Definite time 630 A 100 ms Definite time 0 ms
A Definite time 630 A 100 ms Definite time 0 ms
5 Off X Io sum
B Definite time 630 A 100 ms Definite time 0 ms
A Definite time 630 A 100 ms Definite time 0 ms
6 Off X Io sum
B Definite time 630 A 100 ms Definite time 0 ms
A Definite time 630 A 100 ms Definite time 0 ms
7 Off X Io sum
B Definite time 630 A 100 ms Definite time 0 ms
A Definite time 630 A 100 ms Definite time 0 ms
8 Off X Io sum
B Definite time 630 A 100 ms Definite time 0 ms

2.6. 50BF: Breaker failure

Settings
Unit Activity Latching Use closed
Is threshold Delay position of CB
1 Off X 200 A 200 ms

2.7. 46: Negative sequence current / unbalance

Settings
Unit Activity Latching
Tripping curve Threshold Delay
1 On X Definite time 10 %Ib 100 ms
2 Off X Definite time 10 %Ib 100 ms

Sepam label: sepam F3 (R5) 03/11/2010


Application type: M81 12 / 30
2.8. 49RMS: Thermal overload

Measurement
Unit Activity Latching
origin
1 On X I1,I2,I3

Thermal settings 1 Thermal settings 2 (No)


Heat rise alarm set point (Es1) 85 % Heat rise alarm set point (Es1) 85 %
Heat rise tripping set point (Es2) 120 % Heat rise tripping set point (Es2) 120 %
Heating time constant (T1) 20 min Heating time constant (T1) 20 min
Cooling time constant (T2) 60 min Cooling time constant (T2) 60 min
Init ial heat rise value (Es0) 0% Init ial heat rise value (Es0) 0%

hange to thermal settings 2 by curre nt thres


Current threshold 200 %Ib

Negative sequence fact or Avera ge (4.5)


Use learnt cooling time constant T2 No
Accounting for ambient t emperature No
Maximum temperature of machine 120 °C

2.9. 67N: Directional earth fault

Settings
Measurement
Unit Activity Latching Type Group Curve Delay
origin Tripping curve Is o threshold Delay Angle Voltage Threshold Direction hold hold
Definite
A Definite time 1.26 kA 100 ms 0° 2 %Unp Line 0 ms
time
1 Off X Io sum Type2
Definite
B Definite time 1.26 kA 100 ms 0° 2 %Unp Line 0 ms
time
Definite
A Definite time 1.26 kA 100 ms 0° 2 %Unp Line 0 ms
time
2 Off X Io sum Type2
Definite
B Definite time 1.26 kA 100 ms 0° 2 %Unp Line 0 ms
time

2.10. 32P: Active overpower

Settings
Unit Activity Latching
Type Power threshold Delay
Reverse
1 Off X 1 MW 100 ms
power
Reverse
2 Off X 1 MW 100 ms
power

Sepam label: sepam F3 (R5) 03/11/2010


Application type: M81 13 / 30
2.11. 32Q: Reactive overpower

Settings
Unit Activity Latching
Type Power threshold Delay
Reverse
1 Off X 6.55 MVAR 100 ms
power

2.12. 37: Phase undercurrent

Settings
Unit Activity Latching
Threshold Delay
1 Off 20 %Ib 100 ms

2.13. 48/51LR: Excessive starting time and locked rotor

Settings
Unit Activity Latching Delay f or exces. Delay f or locked Delay f or locked
Threshold starting time (ST) rotor (LT) rotor on start (LTS)
1 Off X 50 %Ib 100 s 100 s 100 s

2.14. 66: Starts per hour

Settings
Unit Activity Latching period Total number Number of consec. Number of consec. Delay
Time of starts hot starts cold starts bet. stop/start
1 Off 1 hr 1 1 1 0 min

2.15. 40: Field loss

Settings
Unit Activity Latching
Xa (Common point of the 2 circles) Xb (Circle1 definition point) Xc (Circle2 definition point) Circle1 time delay Circle2 time delay
1 Off X 2.5 Ohm 20.8 Ohm 42.800 Ohm 70 ms 500 ms

2.16. 78PS: Pole slip

Settings
Unit Activity Latching
Protection principle(s) Delay
1 Off X Equal-area criterion 700 ms

Sepam label: sepam F3 (R5) 03/11/2010


Application type: M81 14 / 30
2.17. 12: Overspeed

Settings
Unit Activity Latch
Speed threshold Time delay T
1 Off 110 %rated speed 1s
2 Off 110 %rated speed 1s

2.18. 14: Underspeed

Settings
Unit Activity Latch
Speed threshold Time delay T
1 Off 20 %rated speed 1s
2 Off 20 %rated speed 1s

2.19. 27D: Positive sequence undervoltage

Measurement Settings
Unit Activity Latching
origin Voltage threshold Delay
V1,V2,V3 /
1 Off X 30 %Unp 100 ms
U21,U32
V1,V2,V3 /
2 Off X 30 %Unp 100 ms
U21,U32

2.20. 27R: Remanent undervoltage

Measurement Settings
Unit Activity Latching
origin Voltage threshold Delay
V1,V2,V3 /
1 Off 20 %Unp 100 ms
U21,U32
V1,V2,V3 /
2 Off 20 %Unp 100 ms
U21,U32

Sepam label: sepam F3 (R5) 03/11/2010


Application type: M81 15 / 30
2.21. 27: Undervoltage

Measurement Settings
Unit Activity Latching
origin Tripping curve mode Voltage threshold Delay
V1,V2,V3 /
1 On Definite time Phase-to -phase 10 %Unp 100 ms
U21,U32
V1,V2,V3 /
2 Off Definite time Phase-to -phase 10 %Unp 100 ms
U21,U32
V1,V2,V3 /
3 Off Definite time Phase-to -phase 10 %Unp 100 ms
U21,U32
V1,V2,V3 /
4 Off Definite time Phase-to -phase 10 %Unp 100 ms
U21,U32

2.22. 59: Overvoltage

Measurement Settings
Unit Activity Latching
origin Mode Voltage threshold Delay
V1,V2,V3 /
1 Off Phase-to -phase 110 %Unp 100 ms
U21,U32
V1,V2,V3 /
2 Off Phase-to -phase 110 %Unp 100 ms
U21,U32
V1,V2,V3 /
3 Off Phase-to -phase 110 %Unp 100 ms
U21,U32
V1,V2,V3 /
4 Off Phase-to -phase 110 %Unp 100 ms
U21,U32

2.23. 59N: Neutral voltage displacement

Measurement Settings
Unit Activity Latching
origin Tripping curve Voltage threshold Delay
1 Off Vo Definite time 10 %Unp 100 ms
2 Off Vo Definite time 10 %Unp 100 ms

2.24. 47: Negative sequence overvoltage

Measurement Settings
Unit Activity Latching
origin Voltage threshold Delay
V1,V2,V3 /
1 Off 10 %Unp 100 ms
U21,U32
V1,V2,V3 /
2 Off 10 %Unp 100 ms
U21,U32

Sepam label: sepam F3 (R5) 03/11/2010


Application type: M81 16 / 30
2.25. 81H: Overfrequency

Measurement Settings
Unit Activity Latch
origin Fs threshold Delay Vs threshold
1 Off V1,V2,V3/U21,U32 53 Hz 100 ms 20 %Un
2 Off V1,V2,V3/U21,U32 53 Hz 100 ms 20 %Un

2.26. 81L: Underfrequency

Settings
Measurement
Unit Activity Latch df/dt
origin Fs threshold Delay Vs threshold restraint
1 Off V1,V2,V3/U21,U32 45 Hz 100 ms 20 %Un No
2 Off V1,V2,V3/U21,U32 45 Hz 100 ms 20 %Un No
3 Off V1,V2,V3/U21,U32 45 Hz 100 ms 20 %Un No
4 Off V1,V2,V3/U21,U32 45 Hz 100 ms 20 %Un No

2.27. 38/49T: Temperature monitoring

Settings Settings
Unit Activity Latch Unit Activity Latch
Alarm Trip Alarm Trip
1 On X 180 °C 180 °C 9 Off X 180 °C 180 °C
2 On X 180 °C 180 °C 10 Off X 180 °C 180 °C
3 On X 180 °C 180 °C 11 Off X 180 °C 180 °C
4 On X 180 °C 180 °C 12 Off X 180 °C 180 °C
5 On X 180 °C 180 °C 13 Off X 180 °C 180 °C
6 On X 180 °C 180 °C 14 Off X 180 °C 180 °C
7 On X 180 °C 180 °C 15 Off X 180 °C 180 °C
8 On X 180 °C 180 °C 16 Off X 180 °C 180 °C

Sepam label: sepam F3 (R5) 03/11/2010


Application type: M81 17 / 30
3. LOGIPAM SETTINGS

3.1. Logipam

Activity ...................... Off

Program file: ............


Program name: ........
Type of a pplic ation:
Diagram version: .....
SFT2885 version: ....

Author: ......................
Customer: ................
Project: .....................
Switchboard: ...........
Cubicle: ....................

Sepam label: sepam F3 (R5) 03/11/2010


Application type: M81 18 / 30
4. DEFINITION OF EQUATIONS

4.1. Logic equations

Sepam label: sepam F3 (R5) 03/11/2010


Application type: M81 19 / 30
5. SET CONTROL MATRIX

5.1. Protection matrix

O1 O2 O3 O4 O5 O101 O102 O103 O104 O105 O106


50/51 - 1 X X
50/51 - 2 X X
50/51 - 3
50/51 - 4
50/51 - 5
50/51 - 6
50/51 - 7
50/51 - 8
50N/51N - 1 X X
50N/51N - 2 X X
50N/51N - 3
50N/51N - 4
50N/51N - 5
50N/51N - 6
50N/51N - 7
50N/51N - 8
50BF - 1
46 - 1 X X X
46 - 2
49RMS - 1 X X X
49RMS - inhibit
49RMS - alarm
67N - 1
67N - 2
32P - 1
32P - 2
32Q - 1
37 - 1
48/51LR - 1
48/51LR - exces. starting time
48/51LR - locked rotor
48/51LR - locked rotor on start
66 - 1
40 - 1
78PS - 1
12 - 1
12 - 2
14 - 1

Sepam label: sepam F3 (R5) 03/11/2010


Application type: M81 20 / 30
O1 O2 O3 O4 O5 O101 O102 O103 O104 O105 O106
14 - 2
27D - 1
27D - 2
27R - 1
27R - 2
27 - 1 X X
27 - 2
27 - 3
27 - 4
59 - 1
59 - 2
59 - 3
59 - 4
59N - 1
59N - 2
47 - 1
47 - 2
81H - 1
81H - 2
81L - 1
81L - 2
81L - 3
81L - 4
38/49T - 1 X X
38/49T - alarm
38/49T - 2 X X
38/49T - alarm
38/49T - 3 X X
38/49T - alarm
38/49T - 4 X X
38/49T - alarm
38/49T - 5 X X
38/49T - alarm
38/49T - 6 X X
38/49T - alarm
38/49T - 7 X X
38/49T - alarm
38/49T - 8 X X
38/49T - alarm
38/49T - 9
38/49T - alarm
38/49T - 10
38/49T - alarm

Sepam label: sepam F3 (R5) 03/11/2010


Application type: M81 21 / 30
O1 O2 O3 O4 O5 O101 O102 O103 O104 O105 O106
38/49T - 11
38/49T - alarm
38/49T - 12
38/49T - alarm
38/49T - 13
38/49T - alarm
38/49T - 14
38/49T - alarm
38/49T - 15
38/49T - alarm
38/49T - 16
38/49T - alarm

Led1 Led2 Led3 Led4 Led5 Led6 Led7 Led8 Led9 English message Local message Rec.
50/51 - 1 X X X
50/51 - 2 X X X
50/51 - 3 X
50/51 - 4 X
50/51 - 5 X
50/51 - 6 X
50/51 - 7 X
50/51 - 8 X
50N/51N - 1 X X X
50N/51N - 2 X X X
50N/51N - 3 X
50N/51N - 4 X
50N/51N - 5 X
50N/51N - 6 X
50N/51N - 7 X
50N/51N - 8 X
50BF - 1 X
46 - 1 X X
46 - 2 X
49RMS - 1 X
49RMS - inhibit
49RMS - alarm
67N - 1 X
67N - 2 X
32P - 1 X

Sepam label: sepam F3 (R5) 03/11/2010


Application type: M81 22 / 30
Led1 Led2 Led3 Led4 Led5 Led6 Led7 Led8 Led9 English message Local message Rec.
32P - 2 X
32Q - 1 X
37 - 1 X
48/51LR - 1
48/51LR - exces. starting time
48/51LR - locked rotor
48/51LR - locked rotor on start
66 - 1
40 - 1 X
78PS - 1 X
12 - 1 X
12 - 2 X
14 - 1
14 - 2
27D - 1 X
27D - 2 X
27R - 1
27R - 2
27 - 1 X X
27 - 2 X
27 - 3 X
27 - 4 X
59 - 1 X
59 - 2 X
59 - 3 X
59 - 4 X
59N - 1 X
59N - 2 X
47 - 1 X
47 - 2 X
81H - 1 X
81H - 2 X
81L - 1 X
81L - 2 X
81L - 3 X
81L - 4 X
38/49T - 1 X
38/49T - alarm

Sepam label: sepam F3 (R5) 03/11/2010


Application type: M81 23 / 30
Led1 Led2 Led3 Led4 Led5 Led6 Led7 Led8 Led9 English message Local message Rec.
38/49T - 2 X
38/49T - alarm
38/49T - 3 X
38/49T - alarm
38/49T - 4 X
38/49T - alarm
38/49T - 5 X
38/49T - alarm
38/49T - 6 X
38/49T - alarm
38/49T - 7 X
38/49T - alarm
38/49T - 8 X
38/49T - alarm
38/49T - 9
38/49T - alarm
38/49T - 10
38/49T - alarm
38/49T - 11
38/49T - alarm
38/49T - 12
38/49T - alarm
38/49T - 13
38/49T - alarm
38/49T - 14
38/49T - alarm
38/49T - 15
38/49T - alarm
38/49T - 16
38/49T - alarm

Sepam label: sepam F3 (R5) 03/11/2010


Application type: M81 24 / 30
5.2. Control logic output matrix

O1 O2 O3 O4 O5 O101 O102 O103 O104 O105 O106


Pic k-up
Drop-out
TCS fault
Breaker monitoring
Reverse phase rotation
Disturbance recording inhibited
MET148 No 1 RTD fault
Low battery fault
Cumulative breaking current monitoring
Watchdog X

Led1 Led2 Led3 Led4 Led5 Led6 Led7 Led8 Led9 English message Local message Rec.
Pic k-up X
Drop-out
TCS fault
Breaker monitoring
Reverse phase rotation
Disturbance recording inhibited
MET148 No 1 RTD fault
Low battery fault
Cumulative breaking current monitoring
Watchdog

Sepam label: sepam F3 (R5) 03/11/2010


Application type: M81 25 / 30
5.3. Logic input matrix

O1 O2 O3 O4 O5 O101 O102 O103 O104 O105 O106


I101 (Breaker closed)
I102 (Breaker open)
I103 (Other use) X
I104 (Other use) X
I105 (Other use) X
I106 (Other use) X
I107 (Other use)
I108 (Other use) X
I109 (Other use) X
I110 (Other use)
I111 (Other use)
I112 (Other use)
I113 (Other use)
I114 (Other use)

Led1 Led2 Led3 Led4 Led5 Led6 Led7 Led8 Led9 English message Local message Rec.
I101 (Breaker closed) X
I102 (Breaker open) X
I103 (Other use)
I104 (Other use)
I105 (Other use)
I106 (Other use)
I107 (Other use)
I108 (Other use)
I109 (Other use)
I110 (Other use)
I111 (Other use)
I112 (Other use)
I113 (Other use)
I114 (Other use)

5.4. Logic equation output variable matrix

O1 O2 O3 O4 O5 O101 O102 O103 O104 O105 O106


V1
V2
V3
V4

Sepam label: sepam F3 (R5) 03/11/2010


Application type: M81 26 / 30
O1 O2 O3 O4 O5 O101 O102 O103 O104 O105 O106
V5
V6
V7
V8
V9
V10
V11
V12
V13
V14
V15
V16
V17
V18
V19
V20

Led1 Led2 Led3 Led4 Led5 Led6 Led7 Led8 Led9 English message Local message Rec.
V1
V2
V3
V4
V5
V6
V7
V8
V9
V10
V11
V12
V13
V14
V15
V16
V17
V18
V19
V20

5.5. GOOSE input matrix

Sepam label: sepam F3 (R5) 03/11/2010


Application type: M81 27 / 30
O1 O2 O3 O4 O5 O101 O102 O103 O104 O105 O106
G401 (------- (Not used) -----------)
G402 (------- (Not used) -----------)
G403 (------- (Not used) -----------)
G404 (------- (Not used) -----------)
G405 (------- (Not used) -----------)
G406 (------- (Not used) -----------)
G407 (------- (Not used) -----------)
G408 (------- (Not used) -----------)
G409 (------- (Not used) -----------)
G410 (------- (Not used) -----------)
G411 (------- (Not used) -----------)
G412 (------- (Not used) -----------)
G413 (------- (Not used) -----------)
G414 (------- (Not used) -----------)
G415 (------- (Not used) -----------)
G416 (------- (Not used) -----------)
G501 (------- (Not used) -----------)
G502 (------- (Not used) -----------)
G503 (------- (Not used) -----------)
G504 (------- (Not used) -----------)
G505 (------- (Not used) -----------)
G506 (------- (Not used) -----------)
G507 (------- (Not used) -----------)
G508 (------- (Not used) -----------)
G509 (------- (Not used) -----------)
G510 (------- (Not used) -----------)
G511 (------- (Not used) -----------)
G512 (------- (Not used) -----------)
G513 (------- (Not used) -----------)
G514 (------- (Not used) -----------)
G515 (------- (Not used) -----------)
G516 (ACE850 presence)

Led1 Led2 Led3 Led4 Led5 Led6 Led7 Led8 Led9 English message Local message Rec.
G401 (------- (Not used) -----------)
G402 (------- (Not used) -----------)
G403 (------- (Not used) -----------)
G404 (------- (Not used) -----------)
G405 (------- (Not used) -----------)
G406 (------- (Not used) -----------)
G407 (------- (Not used) -----------)
G408 (------- (Not used) -----------)

Sepam label: sepam F3 (R5) 03/11/2010


Application type: M81 28 / 30
Led1 Led2 Led3 Led4 Led5 Led6 Led7 Led8 Led9 English message Local message Rec.
G409 (------- (Not used) -----------)
G410 (------- (Not used) -----------)
G411 (------- (Not used) -----------)
G412 (------- (Not used) -----------)
G413 (------- (Not used) -----------)
G414 (------- (Not used) -----------)
G415 (------- (Not used) -----------)
G416 (------- (Not used) -----------)
G501 (------- (Not used) -----------)
G502 (------- (Not used) -----------)
G503 (------- (Not used) -----------)
G504 (------- (Not used) -----------)
G505 (------- (Not used) -----------)
G506 (------- (Not used) -----------)
G507 (------- (Not used) -----------)
G508 (------- (Not used) -----------)
G509 (------- (Not used) -----------)
G510 (------- (Not used) -----------)
G511 (------- (Not used) -----------)
G512 (------- (Not used) -----------)
G513 (------- (Not used) -----------)
G514 (------- (Not used) -----------)
G515 (------- (Not used) -----------)
G516 (ACE850 presence)

Sepam label: sepam F3 (R5) 03/11/2010


Application type: M81 29 / 30
6. SET FUNCTIONS

6.1. Disturbance recording

Description Setting
Activity On
Total recording time: 21 s
Memory used: 93 %
Number of recordings: 6
Duration of a recording: 3
Number of samples stored per period: 12
Number of Pretrig. periods: 36

List of logic I/Os to record:


Logic
Pick-up Flag rec ----- ----- ----- ----- -----
----- ----- ----- ----- ----- ----- -----
----- -----
Base unit outputs
O5 O4 O3 O2 O1
MES 120_1
I114 I113 I112 I111 I110 I109 I108
I107 I106 I105 I104 I103 I102 I101
O106 O105 O104 O103 O102 O101
ME GSE_4
----- ----- ----- ----- ----- ----- -----
----- ----- ----- ----- ----- ----- -----
----- -----
ME GSE_5
----- ----- ----- ----- ----- ----- -----
----- ----- ----- ----- ----- ----- -----
----- -----

Sepam label: sepam F3 (R5) 03/11/2010


Application type: M81 30 / 30