National Inspection and Technical Testing Co.

FAHSS/TÜV
Member of TÜV NORD Gr

INSULATION RESISTANCE RE
REPORT NO. AFI-IR-2019-001
CLIENT: ALAA FOR INDUSTRY (AFI) P.O. NO.
P. O. BOX 9998, DAMMAM-31423. JOB/CONTRACT NO.
KINGDOM OF SAUDI ARABIA. TEST DATE
LOCATION
COMPONENT TRIPLE SWING JOINT ASSEMBLY ID. NO
MATERIAL SPECIFICATION CARBON STEEL NOMINAL THICKNES
INSPECTION STANDARD As Per OEM Recommendation APPARATUS / MODE

Background:
A site visit was conducted at AFI as requested by email in order to inspect &
isolating flange of a triple elbow in AFI yard

Continuity check
Observations & Actions:
1- The assembly was isolated completely from the ground prior to test
2- All hoses across the flange were not connected.
3- Visually inspected the assembly and found ok.
4- The continuity check was done across the insulation flange joint an
5- Insulation resistance testing was done across the flange at test volt
General Arrangement of the Assembly
Remarks & Recommendations:
1- Measured IR is excellent & acceptable as per standard.
2- Isolating the assembly by dry thick wood or any other acceptable in
3- Testing to be done after drying the assembly internally.
Not allowed to use metallic washer touching directly the object body
4-
checked properly before using.
5- It's better to carry out the Megger testing during assembly connectio

MEASURED IR 4.28 MW
REMARKS :
INSPECTOR'S NAME Anantha Kumar.A APPROVED BY
Eng.Saed Barakat
SIGNATURE

OPTR QUAL: SENIOR NDT INSPECTOR CHECK DATE :21 Januar

ORIGINAL - CLIENT
COPY - FAHSS/TUV INV FILE
ng Co.
FAHSS/TÜV
of TÜV NORD Group

N RESISTANCE REPORT
SHEET 01 OF 01
200029951
JOB/CONTRACT NO. N/A
21-Jan-19
AFI YARD AT DAMMAM IND. AREA
ID. NO LA-111 (JOINT ASSEBLY)
NOMINAL THICKNESSN/A
APPARATUS / MODEL:INSULATION MULTIMETER / FLUKE 1555

ail in order to inspect & measure the insulation resistance for an

Insulation Resistance testing

he ground prior to testing.

sulation flange joint and found open circuited.


s the flange at test voltage 500 VDC. Measured value 4.28 MΩ
Isolating Flange

gement of the Assembly

ny other acceptable insulating materials.


internally.
directly the object body. Insulation of Bolts, Nuts & Washers to be

ng assembly connection.

ACCEPTABLE IR > 2.0 M W

INSPECTION
Eng.Saed Barakat AUTHORITY
FAHSS/TÜV NORD
CHECK DATE :21 January 2019 NEXT INSPECTION DATE: N/A