BACHELOR OF MECHANICAL ENGG. EXAMINATION, 2009


(1st Year, 2nd Semester, Old Syllabus)

ELECTRICAL TECHNOLOGY – II

Time : Three hours Full Marks : 100


(50 marks for each part)

Use a separate Answer-script for each part.

PART – I
Answer question no. 1 and any two from the rest.

1. a) What are the conditions to be fulfilled before two


alternators are put on parallel run.

b) Why a Synchronous motor cannot be started? How it


can be made to start?

c) An alternator is coupled to a steam turbine and


electrically connected to the grid . Explain with the
phasor diagram the effects of steam variation and
excitation.

d) Explain how the voltage induced in an alternator is


affected by distribution factor and pitch factor.

e) Explain with a sketch why the air gap flux depends on


the power factor of the load in an alternator.

f) A Synchronous motor runs at 1500 rpm fed from 3.3 KV


bus bar with 50 c/s. What are the no of poles of the
machine.
3x6=18
[ TURN OVER ]
( 2 ) (5)

2. a) A three phase ∆ – connected alternator is rated at b) A 3 – phase delta connected a.c. motor when
1600 KVA. 13500 volt. The effective resistance and connected to a 3 – phase 440 V, 50 Hz system is
reactance of the armature as measured between the developing 30 Kw at an efficiency of 86% and a
lines with other line open are 2.25 ohm and 45 ohm. power factor of 0.83. Calculate the line current and
Calculate the regulation for a load of 1000 KV at a P.F the phase current. 6
of (i) unity (ii) 0.8 lead. 8
9. a) Show that the balanced 3 – phase power consumd by
b) Derive an expression for electromagnetic power in a
3 - phase load can be measure by two wattmeters
cyclindrical wound Synchronous machine and show that
only. —————×————— 10
it is approximately follows a circle diagram. 8
b) Also show that the nature of the load can be
3. a) Describe how to measure the saturated Synchronous determined from the readings of the two wattmeters. 6
reactance of a Synchronous machine in the laboratory.
6

b) What is skin effect in a conductor ; how its resistance is


changed? 2

c) Two three phase parallel running alternators have


1730 V between lines. The phase Synchronous
impedance are ZS1 = (0.2 + j 6.0) ohm and ZS2 = (0.3 +
j 6.8) ohm. Find their terminal voltage and no load
circulating current for a phase divergence of 30 °
Electrical. 8

4. a) Find the cross sectional area of the distributor shown, if


fed from both ends at the same voltage and the
maximum voltage drop not to exceede 4 V. The
distances are given in yards and current loading in
amperes. Take the resistivity as 0.7 µΩ – in.
(3)
(4)
motor rotates in the direction of air gap rotating magnetic
field. 6

c) An 8 – pole alternator runs at 750 rpm. It supplies power


to a 6 - pole 3 – phase induction motor, which has a full
load slip of 3%. Find the full load speed of the induction
motor and the frequency of its rotor emf. 6
b) In the direct current ring main shown a voltage of 500 V
6. a) Define voltage regulation of a transformer. Find the is maintained at A. At B a load of 150 Amp. is taken and
condition under which maximum voltage regulation at C a load of 200 Amp is taken. Find the voltages at B
occurs. 8 and C. The resistance of each conductor of the main is
0.03 Ω per 1000 yards.
b) A 6600 / 440 V, 1 – phase transformer has an equivalent
resistance of 0.02 p.u. and an equivalent reactance of
0.05 p.u. Find the full load voltage regulation of the
transformer at 0.8 p.f. lag, if the primary voltage is 6600
V. Find also the secondary terminal voltage at full load.
8

7. a) Describe the open circuit test and short circuit test of a


PART – II
1 – phase transformer, with the help of circuit diagrams
Answer any three questions.
and showing the connection of various meters used for
these tests. Draw the equivalent circuits. 12 All questions carry equal marks.
Two marks allotted for neatness.
b) What information we can get from the above two tests?
4
5. a) Prove that torque – slip characteristics of 3 – phase
8. a) Deduse the relationship between phase and line induction motor at small slips is very nearly a straight
quantities of star and delta connected balanced 3 – line. 4
phase system. 10
b) Explain clearly why the rotor of a 3 – phase induction

[ TURN OVER ]