Você está na página 1de 1

Air distribution design

Project data :
Name of the project : IDEA DONJA GORICA
Customer : IDEA
Reference : 11-2017
Designed by : VJ
Information :

L dl L Space :
length = 20.0 m
V width = 15.0 m
dtZ height = 4.5 m
floor = 300.0 m2
volume = 1350.0 m3

vL
dtL
Placement :
H1 X1 = 3.0 m
X2 = 3.0 m
X3 = 3.0 m
X4 = 3.0 m
h vL nl = 3
dtL nb = 2
dl = 7.0 m
db = 9.0 m

vH1
1.8 dtL

Placement of diffusers : Definitions :


V [ m3/h ] : Air flow at the diffuser
dl,db [ m ] : Distance between the diffusers
14 X1,X2,X3,X4 [ m ] : Distance between the diffuser and the wall
H1 [ m ] : Distance between the stand level and the ceiling
12 vH1 [ m/s ] : Air velocity between the diffusers at the distance H1
L [ m ] : Distance by the wall ( L=X+H1, L=dl/2+H1, L=db/2+H1 )
vL [ m/s ] : Air velocity by the wall at the distance L
10 dtz [ K ] : Temperature difference between supply air and room air
dtL [ K ] : Temperature difference between core and room air at distance L
8 LwA [ dB(A) ] : A-weighted sound power level of the diffuser
LpA [ dB(A) ] : A-weighted sound pressure level in space
dpt [ Pa ] : Pressure drop at the diffuser
6 ß [ ° ] : Opening angle of the regulation flap ( ß=0° - opened )

0
0 2 4 6 8 10 12 14 16 18 20

Design criteria : Results of the calculation for OD-7 400 :


Optimal operative temperature : 20.0 °C Air flow at the diffuser : V = 95.0 l/s ( 342.0 m3/h )
Supply air temperature : 15.0 °C Air velocity between the diffusers at the distance H1 : vH1 < 0.10 m/s
Temperature difference : -5.0 K Air velocity by the wall at the distance L ( L=5.7m ) : vL < 0.10 m/s
Permissible mean air velocity in Temperature quotient at the distance L=db/2+H1 : dtL/dtz = 0.032
occupied zone : 0.20 m/s Temperature quotient at the distance L=X+H1 : dtL/dtz = 0.035
Required supply air flow rate : 1.9 l/s m2 floor Pressure drop on the diffuser : dpt(ß=0°) = 7 Pa
Required supply air flow rate in space : 570 l/s
Air change coefficient : 1.5 1/h Sound power level : Sound pressure level at h-H1 :
Sound pressure level : 35 dB(A) Lw63(ß=0°) = 21 dB Lp63(ß=0°) = 13 dB
Sound increment : 0 dB Lw125(ß=0°) = 17 dB Lp125(ß=0°) = 7 dB
Room reverberation time : 1.0 s Lw250(ß=0°) = 19 dB Lp250(ß=0°) = 11 dB
Occupied zone : 1.8 m Lw500(ß=0°) = 13 dB Lp500(ß=0°) = 0 dB
Lw1000(ß=0°) = 4 dB Lp1000(ß=0°) = 0 dB
Lw2000(ß=0°) = 1 dB Lp2000(ß=0°) = 0 dB
Lw4000(ß=0°) = 0 dB Lp4000(ß=0°) = 0 dB
Lw8000(ß=0°) = 0 dB Lp8000(ß=0°) = 0 dB
LwA(ß=0°) = 14.8 dB(A) NR = 9 LpA(ß=0°) = 6.2 dB(A) NR = 8