EQUIPMENT ID NUMBER(S) EQUIPMENT DESCRIPTION EQPT CODE SYSTEM ID. PLANT NO.
LAYOUT DRAWING NUMBER REV. NO. PURCHASE ORDER NUMBER EC / PMCC / MCC NO.
SCHEDULED INSPECTION DATE & TIME ACTUAL INSPECTION DATE & TIME QUANTITY INSP. MH's SPENT TRAVEL TIME
SAUDI ARAMCO USE ONLY
SAUDI ARAMCO TIP NUMBER SAUDI ARAMCO ACTIVITY NUMBER WORK PERMIT REQUIRED?
ITEM
ACCEPTANCE CRITERIA REFERENCE PASS FAIL N/A RE-INSP DATE
No.
SAES-K-002
A1 Air shall not be recycled from battery rooms
Para 6.36.4
The bottom of the ventilation air inlet into the battery room shall not SAES-K-002
A2
be higher than 150 mm above the floor. Para 6.46.5
Air outlet of the battery room shall be located in the ceiling or its SAES-K-002
A3
upper edge flush with the ceiling if it is located in a wall. Para 6.46.5
Air inlets and outlets shall be located to provide effective cross SAES-K-002
A4
ventilation over the batteries Para 6.46.5
SAES-K-002
A5 No false ceilings are allowed in battery rooms
Para 6.46.6
The Battery Room shall not have any ventilation opening that would SAES-K-003
A8
compromise the effectiveness of the passive cooling system Para 6.3.17.4.2
REMARKS:
REFERENCE DOCUMENTS:
1-SAES-K-002 -- Air Conditioning Systems for Essential Operating Facilities 31 May, 2004 15 August 2012
2-SAES-K-003 -- Air Conditioning Systems for Communication BuildingsFacilities and Data Centers 31 May, 2004 19 December
2010
3-NFPA-90A -- Standard for the Installation of Air-Conditioning and Ventilating Systems 2009 edition
Page 1 of 2
Performed Inspection Work / Rework May Proceed T&I Witnessed QC Record Reviewed Work Verified
Name, Initials and Date: Name, Initials and Date: