Você está na página 1de 51

Structural Engineers

Principals
Robinson Peter Robinson, S.E.
Meier Jayson E. Haines, S.E.
Juilly & Associates

G-Series Unit

Structural Calculations
For Seismic Anchorage

Prepared for:

Crenlo
April 06, 2015
RMJ Job No. 14273
Valid Thru April 06, 2016

241 Joaquin Avenue


San Leandro, CA 94577
(510) 991-0977
G Series Units

Table of Contents

Description Page
Project Description/Results ................................. 3
Scope, Assumptions, Limitations ........................ 4
Drawing Design Scenarios Summary .................. 5
Seismic Risk Map ................................................... 6
G-Series Unit Anchorage Flow Charts ......... 7-10
Low& Moderate Seismic Calcs.. .................. 11-20
High Seismic Calcs.. ...................................... 21-30
Drawings Details ............................................ 31-40
Appendix ......................................................... 41-51
Hilti Output File (Shear) ..................... 42-46
Hilti Output File (Tension) ................ 47-51
G-Series Unit Anchorage
Nationwide
RMJ Job# 14273

Project Description:

This project involves providing server anchorage support for units located throughout the United States. Calculations have
been assembled according to two distinct seismic regions low & moderate, and high. A map has been created based on
Figures 3.3-1 & 3.3-2 of ASCE 7-10 to define the two different seismic regions. Please note our seismic map shows three
distinct regions low, moderate, and high, but for simplicity of our calculations low and moderate were combined into one
region. The map also shows a solid line near the New Madrid Fault where the value of Ss exceeds 2.75. In this area of
extreme seismic potential, all anchorage is site specific. The other seismic regions have been determined according to the
table included below;

Seismic Design Data


Seismic design Short period spectral Short-period site Design spectral response
region response acceleration Ss coefficient Fa acceleration at short periods SDS
Low 0.4 1.5 0.4
Moderate 1.5 1.0 1.0
High 2.75 1.0 2.0

Anchorage

Calculations are based ½” diameter Hilti Kwik Bolt KB-TZ Carbon Steel expansion bolts, with the assumptions that anchors
are not located within any boundary edges, 4” thick concrete minimum thickness, 2” minimum embedment, and 3,000 psi
concrete strength. See table below for allow cabinet + content weight.

Allowable Values

LOW & MODERATE SEISMIC HIGH SEISMIC


MAX CABINET GROUND UPPER GROUND UPPER
WT. WITH
CONTENTS ON FLOOR RAISED ON FLOOR RAISED ON FLOOR RAISED ON FLOOR RAISED
SINGLE UNIT 1,300 1,300 1,300 1,200 800 SS1 700 SS1
GANGED UNIT 1,300 1,000 1,200 1,200 1,000 SS1 1,000 SS1
SS1‐ Site Specific Calculations Required 
Anchor Capacities

Please see the table below for a quick review of our results.
Bolt Alignment Max Tension (lbf.) Max Shear (lbf.) % Capacity
Ground Level 1,275 1,490 99
50% Bld. Ht. 1,275 1,490 99

I have included the Hilti output files along with my hand calculations in the appendix section of this calculation packet. Site
specific engineering is required where SS is greater than 2.75. Design is in accordance with the 2012 International Building
Code along with the 2013 California Building Code.
Structural Engineers

Robinson Principals
Peter Robinson, S.E.
Meier Jayson E. Haines, S.E.
Juilly & Associates

G-Series Units by Cenlo


Scope, Assumptions, and Limitations
RMJ Job #14273
April 4, 2015

Special Note:
Server rack anchorage calculations are valid under the 2012 International Building Code thru
date noted on cover sheet. After valid thru date, contact Crenlo for updates.

 Special Inspection shall be provided for expansion bolt installation.


 Existing concrete shall have a minimum compressive strength of 3,000 psi.
 Importance factor is assumed to be 1.0.
 Raised Units not to exceed 18”.
 Soil class is assumed to be D.
 Calculations and anchorage are done in accordance with the 2012 IBC and ASCE7-10.
 Maximum Ss value is 2.75. Where value of Ss exceeds 2.75, site specific calculations are required for
all anchorages. Ss values can exceed 2.75 near the New Madrid fault.
 The minimum slab on grade thickness is assumed to be 4”.
 The minimum concrete fill over metal deck thickness is 3½” (with 1 ½” metal deck).
 Enclosure is assumed to stay rigid during seismic loading (design by others).
 Computer access floor shall have strength to support compression and lateral loads.
 Floor slab and concrete filled metal deck shall have strength to resist uplift caused by overturning
moment of cabinets.
 Any installation located in a high seismic region above the upper half of building shall be site
specific. The second floor of a 2 story building is not considered the upper half of the building.
 Ganged Units based on a Minimum of 3 Units.
 Calculations are for Crenlo G-Series units.

241 Joaquin Avenue


San Leandro, CA 94577
(510) 991-0977
www.rmjse.com
Crenlo
241 Joaquin Ave. Low & Moderate Seismic
San Leandro, CA 94577 Job No. : 14273 Date: 03/29/10
510.991.0977 By: MAS Page: 7

S
Summary: G-Series
G S i - Low
L & Moderate
M d t Seismic
S i i

Single
G-Series
Unit

Ground Floor >0%, <50% of >50% of building


building height height

Concrete Slab Concrete Fill over Site Specific


(4" min) metal deck (3½"
(3½ min.
conc. Cover)

no computer 18" raised no computer 18" raised


floor computer floor floor computer floor

Max Wt
Wt.=1,300#
=1 300# Max Wt
Wt.=1,300#
=1 300# Max Wt
Wt.=1,300#
=1 300# Max Wt
Wt.=1,300#
=1 300#

SK3 SK3 SK3 SK3


Drawing
Ref.
SK6 SK9 SK7 SK8

Use Use Use Use


(4) 1/2" Dia. Hilti (4) 1/2" Dia. Hilti Kwik (4) 1/2" Dia. Hilti (4) 1/2" Dia. Hilti Kwik
Kwik Bolt KB-TZ Bolt KB-TZ per unit, Kwik Bolt KB-TZ Bolt KB-TZ per unit,
per unit, Embed Embed 2" Min. & ½" per unit, Embed 2" Embed 2" Min. & ½"
2" Min. Dia. Threaded Rod Min. Dia. Threaded Rod
Crenlo
241 Joaquin Ave. Low & Moderate Seismic
San Leandro, CA 94577 Job No. : 14273 Date: 03/29/10
510.991.0977 By: MAS Page: 8

Summary: G-Series - Low & Moderate Seismic

Ganged G-Series
Units
(3 OR MORE UNITS GANGED)

Ground Floor >0%, <50% of building >50% of building


height height

Concrete Slab Concrete Fill over Site Specific


(4" min) metal deck
(3½"min. conc. cover)

no computer 18" raised no computer 18" raised


floor computer floor floor computer floor

Load in
Max Wt
Wt.=1,300#
=1 300# Max Wt
Wt.=1,000#
=1 000# Max Wt
Wt.=1,300#
=1 300# Max Wt
Wt.=1,300#
=1 300#
pounds

SK4 SK4 SK4 SK5


Drawing
Ref.
SK6 SK9 SK7 SK8

Use Use Use Use


(2) 1/2" Dia.
Dia Hilti (2) 1/2" Dia.
Dia Hilti Kwik (2) 1/2" Dia.
Dia Hilti
(4) 1/2" Dia. Hilti 
Kwik Bolt KB-TZ Bolt KB-TZ per unit, Kwik Bolt KB-TZ
per unit, Embed Embed 2" Min. & ½" per unit, Embed 2" Kwik Bolt KB‐TZ per 
2" Min. Dia. Threaded Rod Min. unit, Embed 2" 
Crenlo
241 Joaquin Ave. High Seismic
San Leandro, CA 94577 Job No. : 14273 Date: 03/29/10
510.991.0977 By: MAS Page: 9

S
Summary: G-Series
G S i - High
Hi h Seismic
S i i

Single
G-Series
Unit

Ground Floor >0%, <50% of >50% of building


building height height

Concrete Slab Concrete Fill over Site Specific


(4" min) metal deck
(3½"min. conc. cover)

no computer 18" raised no computer 18" raised


floor computer floor floor computer floor

Load in
Max Wt.=800# Site Specific Max Wt.=800# Site Specific
pounds

SK3 SK4
Drawing
Ref.
SK6 SK7

Use Use
(4) 1/2" Dia. Hilti Kwik Bolt (4) 1/2" Dia. Hilti Kwik Bolt KB-
KB-TZ, Embed 2" Min. TZ per unit, Embed ½" Min.
Crenlo
241 Joaquin Ave. High Seismic
San Leandro, CA 94577 Job No. : 14273 Date: 03/29/10
510.991.0977 By: MAS Page: 10

Summary: G-Series - High Seismic


Ganged G-Series
Units
(3 OR MORE UNITS
GANGED)

Ground >0%, <50% of >50% of building


Floor building height height

Concrete Slab Concrete Fill over


(4" min) metal deck Site Specific
(3½"min. conc. cover)

no computer 18" raised no computer 18" raised


floor computer floor floor computer floor

Load in
Max Wt
Wt.=1,000#
=1 000# Site Specific Max Wt
Wt.=800#
=800# Site Specific
pounds

SK4 SK4
Drawing
Ref.
SK6 SK7

Use Use
(4) 1/2" Dia. Hilti (4) 1/2" Dia. Hilti
Kwik Bolt KB-TZ Kwik Bolt KB-TZ
per unit, Embed per unit, Embed
2" Min. 2" Min.
Structural Engineers

Principals
Robinson Peter Robinson, S.E.
Meier Jayson E. Haines, S.E.
Juilly & Associates

Low Seismic Calculations

241 Joaquin Avenue


San Leandro, CA 94577
(510) 991-0977
Crenlo
241 Joaquin Ave. Low & Moderate Seismic
San Leandro, CA 94577 Job No. : 14273 Date: 04/06/15
510.991.0977 By: MAS Page: 12

Find the Seismic Design Category (SDC) Unit : G-Series

Project Location: Low & Moderate Seismic


Latitude: Varies Longitude: Varies

Soil Classification: D Table 1613.5.2 & Section 1613.5.2


Occupancy Category: II Table 1604.5

Information from U.S. Geological Survey Website


http://earthquake.usgs.gov/research/hazmaps/

SS= 1.500
500 g
S1= 1.070 g
Fa= 1.000 Table 1613.5.3(1)
Fv= 1.500 Table 1613.5.3(2)
SMS= 1.50 g (Equation 16-37)
SM1= 1.61 g (Equation 16-38)
SDS= 1.000 g (Equation 16-39)
SD1= 1.070 g (Equation 16-40)

Seismic Design Category (SDC): Varies


Crenlo
241 Joaquin Ave. Low & Moderate Seismic
San Leandro, CA 94577 Job No. : 14273 Date: 04/06/15
510.991.0977 By: MAS Page: 13

Load Case: Single Unit (Ground floor)

Unit Dimensions
Width(w) (in) = 18.75 Seismic Force
Depth(D) (in) = 15
Low & Moderate
Frame Height (in) = 82.875 SDS = 1.0 Seismic
g (lb.)
Unit Weight ( )= 1,300 Center of Gravity
y Location Ip = 1.0 (Importance)

Unit Part Weight (lbs) X (in) Y (in) Z (in) ap = 1.0 (Cabinets)

G-Series Frame+Contents 1,300 7.5 9.375 41.4375 Rp = 2.5 (Cabinets)


z/h = 0.0 (Ground Floor)
Longitudinal Anchorage Spacing (in) = 18.75 Fp = 0.160 W
Transverse Anchorage Spacing (in) = 15 Fp,min = 0.30 W
Fp,max = 1.60 W
Use Fp = 0.30 W
Longitudinal Overturning Ω= 2.5 Overstrength

Overturning G-Series unit Plan


Moment = 0.30 (41.4375 in. x 1300lbs.) = 16,161 lb-in

Longitudinal Seismic
Force (Fp)
0.9xResisting
Moment = 0.9 [1300 lbs. x (7.5in)]= 8,775 lb-in 18.75 in.

Total # of Bolts = 4 Anchorage Force = 616 lbs/per bolt


Shear Force = 488 lbs/per bolt
Anchorage and Shear Force Increased by Overstrength Factor

15 in.
Design Bolts for 616 lbs tension, 488 lbs. shear, longitudinal direction

Transverse Overturning G-Series unit Plan


Overturning
Moment = 0.30 (41.4375 in. x 1300lbs.) = 16,161 lb-in

Transverse 18 75 in
18.75 in.
0.9xResisting Seismic Force (Fp)
Moment = 0.9 [1300 lbs. x (9.375in.)]= 10,969 lb-in

Total # of Bolts = 4 Anchorage Force = 346 lbs/per bolt


Shear Force = 488 lbs/per bolt
Anchorage and Shear Force Increased by Overstrength Factor 15 in.
Design Bolts for 0 lbs tension, 488 lbs. shear, transverse direction

Drawing Reference See: SK3 & SK6


Crenlo
241 Joaquin Ave. Low & Moderate Seismic
San Leandro, CA 94577 Job No. : 14273 Date: 04/06/15
510.991.0977 By: MAS Page: 14

Case Single Units on 18in raised computer floor (Ground floor)


Load Case:

Unit Dimensions Raised Floor = 18 in Seismic Force


Width(w) (in) = 18.75
Low & Moderate
Depth(D) (in) = 15 SDS = 1.0 Seismic
Frame Height (in) = 82.875 Ip = 1.0 (Importance)

Unit Weight (lb) = 1,300 Center of Gravity Location ap = 1.0 (Cabinets)

Unit Part Weight (lbs) X (in) Y (in) Z (in) Rp = 2.5 (Cabinets)

G-Series Frame+Contents 1,300 7.50 9.38 59.4375 z/h = 0.0 (Ground Floor)

Fp = 0.160 W
Longitudinal Anchorage Spacing (in) = 18.75 Fp,min = 0.30 W
Transverse Anchorage Spacing (in) = 15 Fp,max = 1.60 W
Use Fp = 0 30
0.30 W
Longitudinal Overturning Ω= 2.5 Overstrength

Overturning G-Series unit Plan


Moment = 0.30 (59.4375 in. x 1300lbs.) = 23,181 lb-in

Longitudinal Seismic
Force (Fp)
0.9xResisting
Moment = 0 9 [1300 lb
0.9 lbs. x (7
(7.5in.)]=
5i )] 8 775 lb-in
8,775 lb in 18 75 in
18.75 in.

Total # of Bolts = 4 Anchorage Force = 1,201 lbs/per bolt


Shear Force = 488 lbs/per bolt
Anchorage and Shear Force Increased by Overstrength Factor

15 in.
Design Bolts for 1,201 lbs tension, 488 lbs. shear, longitudinal direction

Transverse Overturning G-Series unit Plan


Overturning
Moment = 0.30 (59.4375 in. x 1300lbs.) = 23,181 lb-in

Transverse 18.75 in.


Seismic Force (Fp)
0.9xResisting
0 9 R i ti
Moment = 0.9 [1300 lbs. x (9.375in)]= 10,969 lb-in

Total # of Bolts = 4 Anchorage Force = 814 lbs/per bolt


Shear Force = 488 lbs/per bolt
Anchorage and Shear Force Increased by Overstrength Factor 15 in.
Design Bolts for 814 lbs tension, 488 lbs. shear, transverse direction

Drawing Reference See: SK3 & SK9


Crenlo
241 Joaquin Ave. Low & Moderate Seismic
San Leandro, CA 94577 Job No. : 14273 Date: 04/06/15
510.991.0977 By: MAS Page: 15

Case Ganged Unit (Ground floor)


Load Case:

# of Units ganged (min.)= 3

Single Unit Dimension Seismic Force


Width(w) (in) = 18.75
Low & Moderate
Depth(D) (in) = 15 SDS = 1.0 Seismic
Frame Height (in) = 82.875 Ip = 1.0 (Importance)

Frame Weight (lb.) = 1,300 Center of Gravity Location ap = 1.0 (Cabinets)

Unit Part Weight (lbs) X (in) Y (in) Z (in) Rp = 2.5 (Cabinets)

3 - G-Series Frame+Contents 3,900 28.5 9.375 41.44 z/h = 0.0 (Ground Floor)
Fp = 0.160 W
Longitudinal Anchorage Spacing (in) = 57.25 Fp,min
p min = 0.30 W
Transverse Anchorage Spacing (in) = 18.75 Fp,max = 1.60 W
Use Fp = 0.30 W
Longitudinal Overturning Ω= 2.5 Overstrength

Overturning
Moment = 0.30 (41.4375 in. x 3900lbs.) = 48,482 lb-in G-Series unit Plan
Longitudinal Seismic Force

0.9xResisting
Moment = 0.9 (3900 lbs. x28.5 in.)= 100,035 lb-in

Anchorage Force = 0 lbs 3 ganged units


Shear Force = 975 lbs/per bolt Total # of bolts/Unit = 2
Anchorage and Shear Force Increased by Overstrength Factor
Design Bolts for 0 lbs tension
tension, 975 lbs
lbs. shear
shear, transverse direction

Transverse Overturning
Overturning Ganged G-Series unit Plan
Moment = 0.30 (41.4375 in. x 3900lbs.) = 48,482 lb-in Transverse Seismic Force

0.9xResisting
M
Moment = 0.9 (3900 lbs x9.375 in.) = 32 906 lb-in
32,906 lb i

Anchorage Force = 692 lbs/per bolt 3 ganged units


Shear Force = 975 lbs/per bolt Total # of bolts/Unit = 2
Anchorage and Shear Force Increased by Overstrength Factor
Design Bolts for 1 lbs tension, 975 lbs. shear, transverse direction

D
Drawing
i R Reference
f See:
S SK4 & SK6
Crenlo
241 Joaquin Ave. Low & Moderate Seismic
San Leandro, CA 94577 Job No. : 14273 Date: 04/06/15
510.991.0977 By: MAS Page: 16

L dC
Load Case: Ganged
G d units
it on 18i
18in raised
i d computer
t flfloor (G
(Ground
d Fl
Floor))

# of Units ganged (min.)= 3

Single Unit Dimension Raised Floor = 18 in Seismic Force


Width(w) (in) = 18.75
Low & Moderate
Depth(D)
p ( ) (in)
( )= 15 SDS = 1.0 Seismic
Frame Height (in) = 82.875 Ip = 1.0 (Importance)

Frame Weight (lb.) = 1,000 Center of Gravity Location ap = 1.0 (Cabinets)

Unit Part Weight (lbs) X (in) Y (in) Z (in) Rp = 2.5 (Cabinets)

3 - G-Series Frame+Contents 3,000 28.5 9.375 59.4375 z/h = 0.0 (Ground Floor)
Fp = 0.160 W
Longitudinal Anchorage Spacing (in) = 57.25 Fpp,min = 0.30 W
Transverse Anchorage Spacing (in) = 18.75 Fp,max = 1.60 W
Use Fp = 0.30 W
Longitudinal Overturning Ω= 2.5 Overstrength

Overturning
Moment = 0.3 (59.4375 in. x 3000lbs.) = 53,494 lb-in Ganged G-Series unit Plan
Longitudinal Seismic Force
0.9xResisting
0 9xResisting
Moment = 0.9 (3000 lbs. x28.5 in.)= 76,950 lb-in

Anchorage Force = 0 lbs/per bolt 3 ganged units


Shear Force = 750 lbs/per bolt Total # of bolts/Unit = 2
Anchorage and Shear Force Increased by Overstrength Factor
Design Bolts for 0 lbs tension, 750 lbs. shear, longitudinal direction

Transverse Overturning
Overturning Ganged G-Series unit Plan
Moment = 0.3 (59.4375in. x 3000lbs.) = 53,494 lb-in Transverse Seismic Force

0.9xResisting
Moment = 0 9 (3000 lbs x9
0.9 x9.375
375 in
in.)) = 25 313 lb-in
25,313

Anchorage Force = 1,253 lbs/per bolt 3 ganged units


Shear Force = 750 lbs/per bolt Total # of bolts/Unit = 2
Anchorage and Shear Force Increased by Overstrength Factor
Design Bolts for 1,253 lbs tension, 750 lbs. shear, transverse direction

Drawing Reference See: SK4 & SK9


Crenlo
241 Joaquin Ave. Low & Moderate Seismic
San Leandro, CA 94577 Job No. : 14273 Date: 04/06/15
510.991.0977 By: MAS Page: 17

Load Case: Single Unit ( ≤ 50% of Bldg


Bldg. Ht
Ht.))
(i.e. 2nd floor of a 4 story building or 4th floor of an 8 story building)

Unit Dimensions Seismic Force


Width(w) (in) = 18.75
Low & Moderate
Depth(D) (in) = 15 SDS = 1.0 Seismic
Frame Height (in) = 82.875 Ip = 1.0 (Importance)

Unit Weight (lb) = 1,300 Center of Gravity Location ap = 1.0 (Cabinets)

Unit Part Weight (lbs) X (in) Y (in) Z (in) Rp = 2.5 (Cabinets)

G-Series Frame+Contents 1,300 7.5 9.375 41.4375 z/h = 0.5 (50% of bldg ht.)

Fp = 0.320 W
Longitudinal Anchorage Spacing (in) = 18.75 Fp,min = 0.30 W
Transverse Anchorage
g Spacing
p g (in)
( )= 15 p,max =
Fp, 1.60 W
Use Fp = 0.320 W
Longitudinal Overturning Ω= 2.5 Overstrength

Overturning G-Series unit Plan


Moment = 0.32 (41.4375 in. x 1300lbs.) = 17,238 lb-in
Longitudinal Seismic
0.9xResisting Force (Fp)
Moment = 0 9 [1300 lbs
0.9 lbs. x (7
(7.5in.)]=
5in )]= 8 775 lb-in
8,775
18.75 in.

Total # of Bolts = 4 Anchorage Force = 705 lbs/per bolt


Shear Force = 520 lbs/per bolt
Anchorage and Shear Force Increased by Overstrength Factor
15 in.
Design Bolts for 705 lbs tension, 520 lbs. shear, longitudinal direction

Transverse Overturning G-Series unit Plan


Overturning
Moment = 0.32 (41.4375 in. x 1300lbs.) = 17,238 lb-in

Transverse 18.75 in.


0.9xResisting Seismic Force (Fp)
Moment = 0.9 [1300 lbs. x (9.375in)]= 10,969 lb-in

Total # of Bolts = 4 Anchorage Force = 418 lbs/per bolt


Shear Force = 520 lbs/per bolt 15 in.
Anchorage and Shear Force Increased by Overstrength Factor
Design Bolts for 418 lbs tension, 520 lbs. shear, transverse direction

Drawing Reference See: SK3 & SK7


Crenlo
241 Joaquin Ave. Low & Moderate Seismic
San Leandro, CA 94577 Job No. : 14273 Date: 04/06/15
510.991.0977 By: MAS Page: 18

Load Case: Single Units on 18in Raised Comp.


Comp floor (≤50% of Bldg
Bldg. Ht
Ht.))
(i.e. 2nd floor of a 4 story building or 4th floor of an 8 story building)

Unit Dimensions Raised Floor = 18 in Seismic Force


Width(w) (in) = 18.75
Low & Moderate
Depth(D) (in) = 15 SDS = 1.0 Seismic
Frame Height (in) = 82.875 Ip = 1.0 (Importance)

Unit Weight (lb) = 1,200 Center of Gravity Location ap = 1.0 (Cabinets)

Unit Part Weight (lbs) X (in) Y (in) Z (in) Rp = 2.5 (Cabinets)

G-Series Frame+Contents 1,200 7.5 9.375 59.4375 z/h = 0.5 (50% of bldg ht.)

Fp = 0.320 W
Longitudinal Anchorage Spacing (in) = 18.75 Fp,min = 0.30 W
Transverse Anchorage Spacing (in) = 15 Fp,max = 1.60 W
Use Fp = 0.320 W
Longitudinal Overturning Ω= 2.5 Overstrength

Overturning G-Series unit Plan


Moment = 0.32 (59.4375 in. x 1200lbs.) = 22,824 lb-in

0.9xResisting Longitudinal Seismic


Moment = 0 9 [1200 lbs
0.9 lbs. x (7
(7.5in)]=
5in)]= 8 100 lb-in
8,100 Force (Fp)
18.75 in.

Total # of Bolts = 4 Anchorage Force = 1,227 lbs/per bolt


Shear Force = 480 lbs/per bolt
Anchorage and Shear Force Increased by Overstrength Factor

15 in.
Design Bolts for 1,227 lbs tension, 480 lbs. shear, longitudinal direction

Transverse Overturning G-Series unit Plan


Overturning
Moment = 0.32 (59.4375 in. x 1200lbs.) = 22,824 lb-in

0.9xResisting Transverse 18.75 in.


Moment = 0.9 [1200 lbs. x (9.375in.)]= 10,125 lb-in Seismic Force (Fp)

Total # of Bolts = 4 Anchorage Force = 847 lbs/per bolt


Shear Force = 480 lbs/per bolt
Anchorage and Shear Force Increased by Overstrength Factor 15 in.

D i B
Design Bolts
lt ffor 847 lb
lbs ttension,
i 480 lb
lbs. shear,
h ttransverse di
direction
ti

Drawing Reference See: SK3 & SK8


Crenlo
241 Joaquin Ave. Low & Moderate Seismic
San Leandro, CA 94577 Job No. : 14273 Date: 04/06/15
510.991.0977 By: MAS Page: 19

Load Case: Ganged Unit (≤ 50% of Bldg


Bldg. Ht.)
Ht )

# of Units ganged (max)= 3

Single Unit Dimension Seismic Force


Width(w) (in) = 18.75
Low & Moderate
Depth(D) (in) = 15 SDS = 1.0 Seismic
Frame Height (in) = 82.875 Ip = 1.0 (Importance)

Frame Weight (lb.) = 1,200 Center of Gravity Location ap = 1.0 (Cabinets)

Unit Part Weight (lbs) X (in) Y (in) Z (in) Rp = 2.5 (Cabinets)

3 - G-Series Frame+Contents 3,600 28.5 9.375 41.4375 z/h = 0.5 (50% of bldg ht.)
Fp = 0.320 W
Longitudinal Anchorage Spacing (in) = 57.25 Fp,min = 0.30 W
Transverse Anchorage Spacing (in) = 18.75 Fp,max = 1.60 W
Use Fp = 0.320 W
Longitudinal Overturning Ω= 2.5 Overstrength

Overturning
Moment = 0.32 (82.875/2 in. x 3600lbs.) = 47,736 lb-in Ganged G-Series unit Plan
Longitudinal Seismic Force
0.9xResisting
Moment = 0.9 (3600 lbs. x28.5 in.)= 92,340 lb-in

Anchorage Force = 0 lbs 3 ganged units


Shear Force = 960 lbs/per bolt Total # of bolts/Unit = 2
Anchorage and Shear Force Increased by Overstrength Factor
Design Bolts for 0 lbs tension
tension, 960 lbs
lbs. shear
shear, longitudinal direction

Transverse Overturning
Overturning Ganged G-Series unit Plan
Moment = 0.32 (82.875/2 in. x 3600lbs.) = 47,736 lb-in Transverse Seismic Force

0.9xResisting
M
Moment t= 0.9 (3600 lbs x9.375 in.) = 30 375 lb-in
30,375 lb i

Anchorage Force = 772 lbs/per bolt 3 ganged units


Shear Force = 960 lbs/per bolt Total # of bolts/Unit = 2
Anchorage and Shear Force Increased by Overstrength Factor
Design Bolts for 772 lbs tension, 960 lbs. shear, transverse direction

Drawing Reference See: SK4 & SK7


Crenlo
241 Joaquin Ave. Low & Moderate Seismic
San Leandro, CA 94577 Job No. : 14273 Date: 04/06/15
510.991.0977 By: MAS Page: 20

L dC
Load Case: Ganged
G d units
it on 18i
18in raised
i d computer
t flfloor (≤50% off Bld
Bldg. Ht
Ht.))

# of Units ganged (max)= 3

Single Unit Dimension Raised Floor = 18 in Seismic Force


Width(w) (in) = 18.75
Low & Moderate
Depth(D)
p ( ) (in)
( )= 15 SDS = 1.0 Seismic
Frame Height (in) = 82.875 Ip = 1.0 (Importance)

Frame Weight (lb.) = 1,200 Center of Gravity Location ap = 1.0 (Cabinets)

Unit Part Weight (lbs) X (in) Y (in) Z (in) Rp = 2.5 (Cabinets)

3 - G-Series Frame+Contents 3,600 21 9.375 59.4375 z/h = 0.5 (50% of bldg ht.)
Fp = 0.320 W
Longitudinal Anchorage Spacing (in) = 42 Fpp,min = 0.30 W
Transverse Anchorage Spacing (in) = 18.75 Fp,max = 1.60 W
Use Fp = 0.320 W
Longitudinal Overturning Ω= 2.5 Overstrength

Overturning
Moment = 0.32 (59.4375 in. x 3600lbs.) = 68,472 lb-in Ganged G-Series unit Plan
Longitudinal Seismic Force

0.9xResisting
Moment = 0.9 (3600 lbs. x21 in.)= 68,040 lb-in

3 ganged units
Anchorage Force = 6 lbs/per bolt
Shear Force = 240 lbs/per bolt Total # of bolts/Unit = 4
Anchorage and Shear Force Increased by Overstrength Factor
Design Bolts for 06 lbs tension, 240 lbs. shear, longitudinal direction

Transverse Overturning
Overturning Ganged G-Series unit Plan
Moment = 0.3 (59.4375in. x 3600lbs.) = 68,472 lb-in Transverse Seismic Force

0.9xResisting
0 9xResisting
Moment = 0.9 (3600 lbs x9.375 in.) = 30,375 lb-in

Anchorage Force = 1,270 lbs/per bolt 3 ganged units


Shear Force = 240 lbs/per bolt Total # of bolts/Unit = 4
Anchorage and Shear Force Increased by Overstrength Factor
Design Bolts for 1,270 lbs tension, 240 lbs. shear, transverse direction

Drawing Reference See: SK5 & SK8


Structural Engineers

Principals
Robinson Peter Robinson, S.E.
Meier Jayson E. Haines, S.E.
Juilly & Associates

High Seismic Calculations

241 Joaquin Avenue


San Leandro, CA 94577
(510) 991-0977
Crenlo
241 Joaquin Ave. High Seismic
San Leandro, CA 94577 Job No. : 14273 Date: 04/06/15
510.991.0977 By: MAS Page: 22

Find the Seismic Design Category (SDC) Unit : G-Series


G Series

Project Location: High Seismic


Latitude: Varies Longitude: Varies

Soil Classification: D Table 1613.5.2 & Section 1613.5.2


Occupancy Category: II Table 1604.5

Information from U.S. Geological Survey Website


http://earthquake.usgs.gov/research/hazmaps/

SS= 2.750 g
S1= 1 070
1.070 g
Fa= 1.000 Table 1613.5.3(1)
Fv= 1.500 Table 1613.5.3(2)
SMS= 2.75 g (Equation 16-37)
SM1= 1.61 g (Equation 16-38)
SDS= 1 833
1.833 g (Equation 16
16-39)
39)
SD1= 1.070 g (Equation 16-40)

Seismic Design Category (SDC): Varies


Crenlo
241 Joaquin Ave. High Seismic
San Leandro, CA 94577 Job No. : 14273 Date: 04/06/15
510.991.0977 By: MAS Page: 23

Load Case: Single unit (Ground floor)

Unit Dimensions Seismic Force


Width(w) (in) = 18.75 SDS = 1.83 High Seismic

Depth(D) (in) = 15 Ip = 1.0 (Importance)

Frame Height (in) = 82.875 ap = 1.0 (Cabinets)

Max Weight (lb.) = 800 Center of Gravity Location Rp = 2.5 (Cabinets)

Unit Part Weight (lbs) X (in) Y (in) Z (in) z/h = 0.0 (Ground Floor)

G-Series Frame+Contents 800 7.5 9.375 41.4375 Fp = 0.293 W


Fp,min = 0.55 W
Longitudinal Anchorage Spacing (in) = 18.75 Fp,max = 2.93 W
Transverse Anchorage Spacing (in) = 15 Use Fp = 0.550 W
Ω= 2.5 Overstrength

Longitudinal Overturning
Overturning G-Series unit Plan
Moment = 0.55 (41.4375 in. x 800lbs.) = 18,233 lb-in

0.9xResisting Longitudinal Seismic


Moment = 0.9 [(800 lbs. - Vert. Comp.) x 7.5in.]= 3,420 lb-in Force (Fp)
Vertical Component (0.2*SDS*Wp) = 293 lbs 18.75 in.

Total # of Bolts = 4 Anchorage Force = 1,234 lbs/per bolt


Shear Force = 550 lbs/per bolt
Anchorage and Shear Force Increased by Overstrength Factor

15 in.
Design Bolts for 1,234 lbs tension, 550 lbs. shear, longitudinal direction

Transverse Overturning G-Series unit Plan


Overturning
Moment = 0.55 (41.4375 in. x 800lbs.) = 18,233 lb-in

0.9xResisting Transverse 18.75 in.


Moment = 0.9 [(800 lbs. - Vert. Comp.) x (9.375in.)]= 4,275 lb-in Seismic Force (Fp)
Vertical Component (0.2*SDS*Wp) = 293 lbs

Total # of Bolts = 4 Anchorage Force = 931 lbs/per bolt


Shear Force = 550 lbs/per bolt
Anchorage and Shear Force Increased by Overstrength Factor 15 in.
Design Bolts for 931 lbs tension, 550 lbs. shear, longitudinal direction

Drawing Reference See: SK3 & SK6


Crenlo
241 Joaquin Ave. High Seismic
San Leandro, CA 94577 Job No. : 14273 Date: 04/06/15
510.991.0977 By: MAS Page: 24

Load Case: Single units on 18in raised computer floor (Ground floor)

Unit Dimensions Raised Floor = 18 in Seismic Force


Width(w) (in) = 18.75 SDS = 1.83 High Seismic

Depth(D) (in) = 15 Ip = 1.0 (Importance)

Frame Height (in) = 82.875 ap = 1.0 (Cabinets)

Max Weight (lb.) = 800 Center of Gravity Location Rp = 2.5 (Cabinets)

Unit Part Weight (lbs) X (in) Y (in) Z (in) z/h = 0.0 (Ground Floor)

G-Series Frame+Contents 800 7.5 9.375 59.4375 Fp = 0.293 W


Fp,min = 0.55 W
Longitudinal Anchorage Spacing (in) = 18.75 Fp,max = 2.93 W
Transverse Anchorage Spacing (in) = 15 Use Fp = 0.550 W
Ω= 2.5 Overstrength

Longitudinal Overturning
Overturning G-Series unit Plan
Moment = 0.55 (59.4375 in. x 800lbs.) = 26,153 lb-in

Longitudinal Seismic
0.9xResisting Force (Fp)
Moment = 0.9 [(
[(800 lbs. - Vert. Comp.)
p ) x (7.5in.)]=
( )] 3,420
, lb-in 18.75 in.
Vertical Component (0.2*SDS*Wp) = 293 lbs

Total # of Bolts = 4 Anchorage Force = 1,894 lbs/per bolt


Shear Force = 550 lbs./per bolt
Anchorage and Shear Force Increased by Overstrength Factor
15 in.

Design Bolts for 1,894 lbs tension, 550 lbs. shear, longitudinal direction

Transverse Overturning G-Series unit Plan


Overturning
Moment = 0.55 (59.4375 in. x 800lbs.) = 26,153 lb-in

0.9xResisting Transverse 18.75 in.


Moment = 0.9 [(800 lbs. - Vert. Comp.) x (9.375in)]= 4,275 lb-in Seismic Force (Fp)
Vertical Component (0.2*SDS*Wp) = 293 lbs

Total # of Bolts = 4 Anchorage Force = 1,459 lbs/per bolt


Shear Force = 550 lbs/per bolt
Anchorage and Shear Force Increased by Overstrength Factor 15 in.

Design Bolts for 1,459 lbs tension, 550 lbs. shear, longitudinal direction

*Site Specific Engineering Required*


Crenlo
241 Joaquin Ave. High Seismic
San Leandro, CA 94577 Job No. : 14273 Date: 04/06/15
510.991.0977 By: MAS Page: 25

Load Case: Ganged Unit (Ground floor)

# of Units ganged (min)= 3

Single Unit Dimension Seismic Force


Width(w) (in) = 18.75 SDS = 1.83 High Seismic

Depth(D) (in) = 15 Ip = 1.0 (Importance)

Frame Height (in) = 82.875 ap = 1.0 (Cabinets)

Max Weight (lb.) = 1,000 Center of Gravity Location Rp = 2.5 (Cabinets)

Unit Part Weight (lbs) X (in) Y (in) Z (in) z/h = 0.0 (Ground Floor)

3 - G-Series Frame+Contents 3,000 29 9.375 41.4375 Fp = 0.293 W


Fp,min = 0.55 W
Fp,max = 2.93 W
Longitudinal Anchorage Spacing (in) = 42 Use Fp = 0.550 W
Transverse Anchorage Spacing (in) = 18.75 Ω= 2.5 Overstrength

Longitudinal Overturning
Overturning
Moment = 0.55 (41.4375 in. x 3000lbs.) = 68,372 lb-in Ganged G-Series unit Plan
Longitudinal Seismic
0.9xResisting
Moment = 0.9 [(3000 lbs. - Vert. Comp.) x28.5 in.]= 48,735 lb-in
Vertical Component (0.2*SDS*Wp) = 1,100 lbs

Anchorage Force = 292 lbs/per bolt 3 ganged units


Shear Force = 688 lbs/per bolt Total # of bolts/Unit = 4
Anchorage and Shear Force Increased by Overstrength Factor
Design Bolts for 292 lbs tension, 688 lbs. shear, longitudinal direction

Transverse Overturning
Overturning Ganged G-Series unit Plan
Moment = 0.55 (41.4375 in. x 3000lbs.) = 68,372 lb-in Transverse Seismic Force

0.9xResisting
Moment = 0.9 [(3000 lbs - Vert. Comp.) x9.375 in.] = 16,031 lb-in
Vertical Component (0.2*SDS*Wp) = 1,100 lbs
3 ganged units
Anchorage Force = 1,163 lbs/per bolt Total # of bolts/Unit = 4
Shear Force = 688 lbs/per bolt
Anchorage and Shear Force Increased by Overstrength Factor
Design Bolts for 1,163 lbs tension, 688 lbs. shear, transverse direction

Drawing Reference See: SK5 & SK6


Crenlo
241 Joaquin Ave. High Seismic
San Leandro, CA 94577 Job No. : 14273 Date: 04/06/15
510.991.0977 By: MAS Page: 26

Load Case: Ganged units on 18in raised computer floor (Ground floor)

# of Units ganged (min)= 3

Single Unit Dimension Raised Floor = 18 in Seismic Force


Width(w) (in) = 18.75 SDS = 1.83 High Seismic

Depth(D) (in) = 15 Ip = 1.0 (Importance)

Frame Height (in) = 82.875 ap = 1.0 (Cabinets)

Max Weight (lb.) = 1,000 Center of Gravity Location Rp = 2.5 (Cabinets)

Unit Part Weight (lbs) X (in) Y (in) Z (in) z/h = 0.0 (Ground Floor)

3 - G-Series Frame+Contents 3,000 29 9.375 59.4375 Fp = 0.293 W


Fp,min = 0.55 W
Longitudinal Anchorage Spacing (in) = 42 Fp,max = 2.93 W
Transverse Anchorage Spacing (in) = 18.75 Use Fp = 0.550 W
Ω= 2.5 Overstrength

Longitudinal Overturning
Overturning
Moment = 0.55 (59.4375 in. x 3000lbs.) = 98,072 lb-in Ganged G-Series unit Plan
Longitudinal Seismic Force

0.9xResisting
Moment = 0.9 [(3000 lbs. - Vert. Comp.) x28.5 in.]= 48,735 lb-in
Vertical Component (0.2*SDS*Wp) = 1,100 lbs
3 ganged units
Anchorage Force = 734 lbs/per bolt
Shear Force = 688 lbs/per bolt Total # of bolts/Unit = 4
Anchorage and Shear Force Increased by Overstrength Factor
Design Bolts for 734 lbs tension, 688 lbs. shear, longitudinal direction

Transverse Overturning
Overturning Ganged G-Series unit Plan
Moment = 0.55 (59.4375in. x 3000lbs.) = 98,072 lb-in Transverse Seismic Force

0.9xResisting
Moment = 0.9 [(3000 lbs - Vert. Comp.) x9.375 in.] = 16,031 lb-in
Vertical Component (0.2*SDS*Wp) = 1,100 lbs
3 ganged units
Anchorage Force = 1,823 lbs/per bolt
Shear Force = 688 lbs/per bolt Total # of bolts/Unit = 4
Anchorage and Shear Force Increased by Overstrength Factor
Design Bolts for 1,823 lbs tension, 688 lbs. shear, longitudinal direction

*Site Specific Engineering Required*


Crenlo
241 Joaquin Ave. High Seismic
San Leandro, CA 94577 Job No. : 14273 Date: 04/06/15
510.991.0977 By: MAS Page: 27

Load Case: Single Unit ( ≤ 50% of Bldg. Ht.)


(i.e. 2nd floor of a 4 story building or 4th floor of an 8 story building)

Unit Dimensions Seismic Force


Width(w) (in) = 18.75 SDS = 1.83 High Seismic

Depth(D) (in) = 15 Ip = 1.0 (Importance)

Frame Height (in) = 82.875 ap = 1.0 (Cabinets)

Max Weight (lb.) = 700 Center of Gravity Location Rp = 2.5 (Cabinets)

Unit Part Weight (lbs) X (in) Y (in) Z (in) z/h = 0.5 (50% of bldg ht.)

G-Series Frame+Contents 700 7.5 9.375 41.4375 Fp = 0.587 W


Fp,min = 0.55 W
Longitudinal Anchorage Spacing (in) = 18.75 Fp,max = 2.93 W
Transverse Anchorage Spacing (in) = 15 Use Fp = 0.587 W
Ω= 2.5 Overstrength

Longitudinal Overturning
Overturning G-Series unit Plan
Moment = 0.59 (41.4375 in. x 700lbs.) = 17,017 lb-in

0.9xResisting Longitudinal Seismic


Moment = 0.9 [(700 lbs. - Vert. Comp.) x (7.5in.)]= 2,993 lb-in Force (Fp)
Vertical Component (0.2*SDS*Wp) = 257 lbs 18.75 in.

Total # of Bolts = 4 Anchorage Force = 1,169 lbs/per bolt


Shear Force = 513 lbs/per bolt
Anchorage and Shear Force Increased by Overstrength Factor
15 in.
Design Bolts for 1,169 lbs tension, 513 lbs. shear, longitudinal direction

Transverse Overturning G-Series unit Plan


Overturning
Moment = 0.59 (41.4375 in. x 700lbs.) = 17,017 lb-in

0.9xResisting Transverse 18.75 in.


Moment = 0.9 [(700 lbs. - Vert. Comp.) x (9.375in)]= 3,741 lb-in Seismic Force (Fp)
Vertical Component (0.2*SDS*Wp) = 257 lb-in

Total # of Bolts = 4 Anchorage Force = 885 lbs/per bolt


Shear Force = 513 lbs/per bolt 15 in.
Anchorage and Shear Force Increased by Overstrength Factor
Design Bolts for 885 lbs tension, 513 lbs. shear, longitudinal direction

Drawing Reference See: SK3 & SK7


Crenlo
241 Joaquin Ave. High Seismic
San Leandro, CA 94577 Job No. : 14273 Date: 04/06/15
510.991.0977 By: MAS Page: 28

Load Case: Single unit on 18in raised computer floor (≤ 50% of Bldg. Ht.)
(i.e. 2nd floor of a 4 story building or 4th floor of an 8 story building)

Unit Dimensions Seismic Force


Width(w) (in) = 18.75 Raised Floor = 18 in SDS = 1.83 High Seismic

Depth(D) (in) = 15 Ip = 1.0 (Importance)

Frame Height (in) = 82.875 ap = 1.0 (Cabinets)

Max Weight (lb.) = 800 Center of Gravity Location Rp = 2.5 (Cabinets)

Unit Part Weight (lbs) X (in) Y (in) Z (in) z/h = 0.5 (50% of bldg ht.)

G-Series Frame+Contents 800 7.5 9.375 59.4375 Fp = 0.587 W


Fp,min = 0.55 W
Longitudinal Anchorage Spacing (in) = 18.75 Fp,max = 2.93 W
Transverse Anchorage Spacing (in) = 15 Use Fp = 0.587 W
Ω= 2.5 Overstrength

Longitudinal Overturning G-Series unit Plan


Overturning
Moment = 0.59 (59.4375 in. x 800lbs.) = 27,896 lb-in

0.9xResisting Longitudinal Seismic


Moment = 0 9 [(800 lbs.
0.9 lbs - Vert
Vert. Comp
Comp.)) x (7
(7.5in)]=
5in)]= 3,420
3 420 lb-in Force (Fp)
Vertical Component (0.2*SDS*Wp) = 293 lbs 18.75 in.

Total # of Bolts = 4 Anchorage Force = 2,040 lbs/per bolt


Shear Force = 587 lbs/per bolt
Anchorage and Shear Force Increased by Overstrength Factor 15 in.

Design Bolts for 2,040 lbs tension, 587 lbs. shear, longitudinal direction

Transverse Overturning G-Series unit Plan


Overturning
Moment = 0.59 (59.4375 in. x 800lbs.) = 27,896 lb-in

0.9xResisting Transverse 18.75 in.


Moment = 0.9 [(800 lbs. - Vert. Comp.) x (9.375in.)]= 4,275 lb-in Seismic Force (Fp)
Vertical Component (0.2*SDS*Wp*9.375in) = 293 lb-in

Total # of Bolts = 4 Anchorage Force = 1,575 lbs/per bolt


Shear Force = 587 lbs/per bolt 15 in.
Anchorage and Shear Force Increased by Overstrength Factor
Design Bolts for 1,575 lbs tension, 587 lbs. shear, longitudinal direction

*Site Specific Engineering Required*


Crenlo
241 Joaquin Ave. High Seismic
San Leandro, CA 94577 Job No. : 14273 Date: 04/06/15
510.991.0977 By: MAS Page: 29

Load Case: Ganged Unit (≤ 50% of Bldg. Ht.)

# of Units ganged (min)= 3


Seismic Force
Single Unit Dimension SDS = 1.83 High Seismic

Width(w) (in) = 18.75 add 0 in Edge length Ip = 1.0 (Importance)

Depth(D) (in) = 15 ap = 1.0 (Cabinets)

Frame Height (in) = 82.875 Rp = 2.5 (Cabinets)

Max Weight (lb.) = 1,000 Center of Gravity Location z/h = 0.5 (50% of bldg ht.)

Unit Part Weight (lbs) X (in) Y (in) Z (in) Fp = 0.587 W


3 - G-Series Frame+Contents 3,000 29 9.375 41.4375 Fp,min = 0.55 W
Fp,max = 2.93 W
Longitudinal Anchorage Spacing (in) = 42 Use Fp = 0.587 W
Transverse Anchorage Spacing (in) = 18.75 Ω= 2.5 Overstrength

Longitudinal Overturning
Overturning
Moment = 0.59 (41.4375 in. x 3000lbs.) = 72,930 lb-in Ganged G-Series unit Plan
Longitudinal Seismic Force
0.9xResisting
0 9xResisting
Moment = 0.9 [(3000 lbs. - Vert. Comp.) x28.5 in.]= 48,735 lb-in
Vertical Component (0.2*SDS*Wp) = 1,100 lbs

3 ganged units
Anchorage Force = 360 lbs
Shear Force = 733 lbs/per bolt Total # of bolts/Unit = 4
Anchorage and Shear Force Increased by Overstrength Factor
Design Bolts for 360 lbs tension, 733 lbs. shear, longitudinal direction

Transverse Overturning
Overturning Ganged G-Series unit Plan
Moment = 0.59 (41.4375 in. x 3000lbs.) = 72,930 lb-in Transverse Seismic Force

0.9xResisting
Moment = 0.9 [(3000 lbs - Vert. Comp.) x9.375 in.] = 16,031 lb-in
Vertical Component (0.2*SDS*Wp) = 1,100 lbs

3 ganged units
Anchorage Force = 1,264 lbs/per bolt Total # of bolts/Unit = 4
Shear Force = 733 lbs/per bolt
Anchorage and Shear Force Increased by Overstrength Factor
Design Bolts for 1,264 lbs tension, 733 lbs. shear, longitudinal direction

Drawing Reference See: SK5 & SK7


Crenlo
241 Joaquin Ave. High Seismic
San Leandro, CA 94577 Job No. : 14273 Date: 04/06/15
510.991.0977 By: MAS Page: 30

Load Case: Ganged unit on 18in raised computer floor (≤ 50% of Bldg. Ht.)

# of Units ganged (min)= 3

Single Unit Dimension Raised Floor = 18 in Seismic Force


Width(w) (in) = 18.75 SDS = 1.83 High Seismic

Depth(D) (in) = 15 Ip = 1.0 (Importance)

Frame Height (in) = 82.875 ap = 1.0 (Cabinets)

Max Weight (lb.) = 1,000 Center of Gravity Location Rp = 2.5 (Cabinets)

Unit Part Weight (lbs) X (in) Y (in) Z (in) z/h = 0.5 (50% of bldg ht.)

3 - G-Series Frame+Contents 3,000 29 9.375 59.4375 Fp = 0.587 W


Fp,min = 0.55 W
Longitudinal Anchorage Spacing (in) = 42 Fp,max = 2.93 W
Transverse Anchorage Spacing (in) = 18.75 Use Fp = 0.587 W
Ω= 2.5 Overstrength

Longitudinal Overturning
Overturning
Moment = 0.59 (59.4375 in. x 3000lbs.) = 104,610 lb-in Ganged G-Series unit Plan
Longitudinal Seismic Force
0.9xResisting
Moment = 0.9 (3000 lbs. x28.5 in.)= 48,735 lb-in
Vert. Comp. (0.2*SDS*Wp)= 1,100 lbs

3 ganged units
Anchorage Force = 832 lbs/per bolt
Shear Force = 733 lbs/per bolt Total # of bolts/Unit = 4
Anchorage and Shear Force Increased by Overstrength Factor
Design Bolts for 832 lbs tension, 733 lbs. shear, longitudinal direction

Transverse Overturning
Overturning Ganged G-Series unit Plan
Moment = 0.59 (59.4375in. x 3000lbs.) = 104,610 lb-in Transverse Seismic Force

0.9xResisting
Moment = 0.9 [(3000 lbs - Vert. Comp.) x9.375 in.] = 16,031 lb-in
Vertical Component (0.2*SDS*Wp) = 1,100 lb-in

3 ganged units
Anchorage Force = 1,968 lbs/per bolt
Shear Force = 733 lbs/per bolt Total # of bolts/Unit = 4
Anchorage and Shear Force Increased by Overstrength Factor
Design Bolts for 1,968 lbs tension, 733 lbs. shear, longitudinal direction

*Site Specific Engineering Required*


Structural Engineers

Principals
Robinson Peter Robinson, S.E.
Meier Jayson E. Haines, S.E.
Juilly & Associates

Drawing Details

241 Joaquin Ave.


San Leandro, CA 94577
(510) 991-0977
Structural Engineers

Principals
Robinson Peter Robinson, S.E.
Meier Jayson E. Haines, S.E.
Juilly & Associates

Appendix

241 Joaquin Avenue


San Leandro, CA 94577
(510) 991-0977
www.hilti.us Profis Anchor 2.5.1
Company: RMJ Page: 1
Specifier: Mario Project: Creno-G-Series
Address: 241 Joaquin Ave. Sub-Project I Pos. No.: 14273
Phone I Fax: 510.991.0977 | Date: 4/6/2015
E-Mail: msigala@rmjse.com

Specifier's comments: G-Series: SINGLE ANCHOR, Maximum Tension 1,625# 100% Capacity

1 Input data
Anchor type and diameter: Kwik Bolt TZ - CS 1/2 (2)
Effective embedment depth: hef,act = 2.000 in., hnom = 2.375 in.
Material: Carbon Steel
Evaluation Service Report: ESR-1917
Issued I Valid: 5/1/2013 | 5/1/2015
Proof: Design method ACI 318-11 / Mech.
Stand-off installation: eb = 0.000 in. (no stand-off); t = 0.250 in.
Anchor plate: lx x ly x t = 3.000 in. x 3.000 in. x 0.250 in.; (Recommended plate thickness: not calculated)
Profile: no profile
Base material: cracked concrete, 3000, fc' = 3000 psi; h = 4.000 in.
Installation: hammer drilled hole, Installation condition: Dry
Reinforcement: tension: condition B, shear: condition B; no supplemental splitting reinforcement present
edge reinforcement: none or < No. 4 bar
Seismic loads (cat. C, D, E, or F) Tension load: yes (D.3.3.4.3 (d))
Shear load: yes (D.3.3.5.3 (c))

Geometry [in.] & Loading [lb, in.lb]

Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
www.hilti.us Profis Anchor 2.5.1
Company: RMJ Page: 2
Specifier: Mario Project: Creno-G-Series
Address: 241 Joaquin Ave. Sub-Project I Pos. No.: 14273
Phone I Fax: 510.991.0977 | Date: 4/6/2015
E-Mail: msigala@rmjse.com

2 Load case/Resulting anchor forces


Load case: Design loads
y
Anchor reactions [lb]
Tension force: (+Tension, -Compression)
Anchor Tension force Shear force Shear force x Shear force y
1 0 1625 0 1625
max. concrete compressive strain: - [‰] 1 x
max. concrete compressive stress: - [psi]
resulting tension force in (x/y)=(0.000/0.000): 0 [lb]
resulting compression force in (x/y)=(0.000/0.000): 0 [lb]

3 Tension load
Load Nua [lb] Capacity fNn [lb] Utilization bN = Nua/fNn Status
Steel Strength* N/A N/A N/A N/A
Pullout Strength* N/A N/A N/A N/A
Concrete Breakout Strength** N/A N/A N/A N/A
* anchor having the highest loading **anchor group (anchors in tension)

Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
www.hilti.us Profis Anchor 2.5.1
Company: RMJ Page: 3
Specifier: Mario Project: Creno-G-Series
Address: 241 Joaquin Ave. Sub-Project I Pos. No.: 14273
Phone I Fax: 510.991.0977 | Date: 4/6/2015
E-Mail: msigala@rmjse.com

4 Shear load
Load Vua [lb] Capacity fVn [lb] Utilization bV = Vua/fVn Status
Steel Strength* 1625 3572 46 OK
Steel failure (with lever arm)* N/A N/A N/A N/A
Pryout Strength** 1625 1844 89 OK
Concrete edge failure in direction y+** 1625 1636 100 OK
* anchor having the highest loading **anchor group (relevant anchors)

4.1 Steel Strength


Vsa,eq = ESR value refer to ICC-ES ESR-1917
f Vsteel ≥ Vua ACI 318-11 Table D.4.1.1

Variables
n Ase,V [in.2] futa [psi]
1 0.10 106000
Calculations
Vsa,eq [lb]
5495
Results
Vsa,eq [lb] fsteel f Vsa [lb] Vua [lb]
5495 0.650 3572 1625

4.2 Pryout Strength

Vcp = kcp [(AA ) y


Nc
Nc0
ed,N yc,N ycp,N Nb ] ACI 318-11 Eq. (D-40)
f Vcp ≥ Vua ACI 318-11 Table D.4.1.1
ANc see ACI 318-11, Part D.5.2.1, Fig. RD.5.2.1(b)
ANc0 = 9 h2ef ACI 318-11 Eq. (D-5)

( )
1
yec,N = 2 e'N ≤ 1.0 ACI 318-11 Eq. (D-8)
1+
3 hef

yed,N = 0.7 + 0.3 (


ca,min
1.5hef
≤ 1.0) ACI 318-11 Eq. (D-10)

(
ca,min 1.5hef
ycp,N = MAX c , c
ac ac
≤ 1.0) ACI 318-11 Eq. (D-12)
1.5
Nb = kc la √fc hef
'
ACI 318-11 Eq. (D-6)

Variables
kcp hef [in.] ec1,N [in.] ec2,N [in.] ca,min [in.]
1 2.000 0.000 0.000 6.000

yc,N cac [in.] kc la f'c [psi]


1.000 5.500 17 1.000 3000

Calculations
ANc [in.2] ANc0 [in.2] yec1,N yec2,N yed,N ycp,N Nb [lb]
36.00 36.00 1.000 1.000 1.000 1.000 2634
Results
Vcp [lb] fconcrete fseismic fnonductile f Vcp [lb] Vua [lb]
2634 0.700 1.000 1.000 1844 1625

Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
www.hilti.us Profis Anchor 2.5.1
Company: RMJ Page: 4
Specifier: Mario Project: Creno-G-Series
Address: 241 Joaquin Ave. Sub-Project I Pos. No.: 14273
Phone I Fax: 510.991.0977 | Date: 4/6/2015
E-Mail: msigala@rmjse.com

4.3 Concrete edge failure in direction y+

Vcb = (AA ) y
Vc
Vc0
ed,V yc,V yh,V yparallel,V Vb ACI 318-11 Eq. (D-30)
f Vcb ≥ Vua ACI 318-11 Table D.4.1.1
AVc see ACI 318-11, Part D.6.2.1, Fig. RD.6.2.1(b)
AVc0 = 4.5 c2a1 ACI 318-11 Eq. (D-32)

( )
1
yec,V = 2e'v ≤ 1.0 ACI 318-11 Eq. (D-36)
1+
3ca1

yed,V = 0.7 + 0.3 1.5c(


ca2
a1
)
≤ 1.0 ACI 318-11 Eq. (D-38)

yh,V = √
1.5ca1
ha
≥ 1.0 ACI 318-11 Eq. (D-39)

(( ) )
0.2
l 1.5
Vb = 7 e √da la √f'c ca1 ACI 318-11 Eq. (D-33)
da

Variables
ca1 [in.] ca2 [in.] ecV [in.] yc,V ha [in.]
4.000 6.000 0.000 1.000 4.000

le [in.] la da [in.] f'c [psi] yparallel,V


2.000 1.000 0.500 3000 1.000

Calculations
AVc [in.2] AVc0 [in.2] yec,V yed,V yh,V Vb [lb]
48.00 72.00 1.000 1.000 1.225 2862
Results
Vcb [lb] fconcrete fseismic fnonductile f Vcb [lb] Vua [lb]
2337 0.700 1.000 1.000 1636 1625

5 Warnings
• Load re-distributions on the anchors due to elastic deformations of the anchor plate are not considered. The anchor plate is assumed to be
sufficiently stiff, in order not to be deformed when subjected to the loading!

Input data and results must be checked for agreement with the
existing conditions and for plausibility!
• Condition A applies when supplementary reinforcement is used. The Φ factor is increased for non-steel Design Strengths except Pullout
Strength and Pryout strength. Condition B applies when supplementary reinforcement is not used and for Pullout Strength and Pryout
Strength. Refer to your local standard.
• Refer to the manufacturer's product literature for cleaning and installation instructions.
• Checking the transfer of loads into the base material and the shear resistance are required in accordance with ACI 318 or the relevant
standard!
• An anchor design approach for structures assigned to Seismic Design Category C, D, E or F is given in ACI 318-11 Appendix D, Part
D.3.3.4.3 (a) that requires the governing design strength of an anchor or group of anchors be limited by ductile steel failure. If this is NOT the
case, the connection design (tension) shall satisfy the provisions of Part D.3.3.4.3 (b), Part D.3.3.4.3 (c), or Part D.3.3.4.3 (d). The
connection design (shear) shall satisfy the provisions of Part D.3.3.5.3 (a), Part D.3.3.5.3 (b), or Part D.3.3.5.3 (c).
• Part D.3.3.4.3 (b) / part D.3.3.5.3 (a) requires that the attachment the anchors are connecting to the structure be designed to undergo ductile
yielding at a load level corresponding to anchor forces no greater than the controlling design strength. Part D.3.3.4.3 (c) / part D.3.3.5.3 (b)
waives the ductility requirements and requires that the anchors shall be designed for the maximum tension / shear that can be transmitted to
the anchors by a non-yielding attachment. Part D.3.3.4.3 (d) / part D.3.3.5.3 (c) waives the ductility requirements and requires the design
strength of the anchors to equal or exceed the maximum tension / shear obtained from design load combinations that include E, with E
increased by W0.
• Hilti post-installed anchors shall be installed in accordance with the Hilti Manufacturer's Printed Installation Instructions (MPII). Reference
ACI 318-11, Part D.9.1

Fastening meets the design criteria!

Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
www.hilti.us Profis Anchor 2.5.1
Company: RMJ Page: 5
Specifier: Mario Project: Creno-G-Series
Address: 241 Joaquin Ave. Sub-Project I Pos. No.: 14273
Phone I Fax: 510.991.0977 | Date: 4/6/2015
E-Mail: msigala@rmjse.com

6 Installation data
Anchor plate, steel: - Anchor type and diameter: Kwik Bolt TZ - CS 1/2 (2)
Profile: no profile; 0.000 x 0.000 x 0.000 in. Installation torque: 480.001 in.lb
Hole diameter in the fixture: df = 0.563 in. Hole diameter in the base material: 0.500 in.
Plate thickness (input): 0.250 in. Hole depth in the base material: 2.625 in.
Recommended plate thickness: not calculated Minimum thickness of the base material: 4.000 in.
Cleaning: Manual cleaning of the drilled hole according to instructions for use is required.

1.500 1.500

1.500

1.500
1 x

1.500

1.500

1.500 1.500

Coordinates Anchor in.


Anchor x y c-x c+x c-y c+y
1 0.000 0.000 6.000 6.000 6.000 6.000

Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
www.hilti.us Profis Anchor 2.5.1
Company: RMJ Page: 1
Specifier: Mario Project: Creno-G-Series
Address: 241 Joaquin Ave. Sub-Project I Pos. No.: 14273
Phone I Fax: 510.991.0977 | Date: 4/6/2015
E-Mail: msigala@rmjse.com

Specifier's comments: G-Series: SINGLE ANCHOR, Maximum Tension 1,275# 100% Capacity

1 Input data
Anchor type and diameter: Kwik Bolt TZ - CS 1/2 (2)
Effective embedment depth: hef,act = 2.000 in., hnom = 2.375 in.
Material: Carbon Steel
Evaluation Service Report: ESR-1917
Issued I Valid: 5/1/2013 | 5/1/2015
Proof: Design method ACI 318-11 / Mech.
Stand-off installation: eb = 0.000 in. (no stand-off); t = 0.250 in.
Anchor plate: lx x ly x t = 3.000 in. x 3.000 in. x 0.250 in.; (Recommended plate thickness: not calculated)
Profile: no profile
Base material: cracked concrete, 3000, fc' = 3000 psi; h = 4.000 in.
Installation: hammer drilled hole, Installation condition: Dry
Reinforcement: tension: condition B, shear: condition B; no supplemental splitting reinforcement present
edge reinforcement: none or < No. 4 bar
Seismic loads (cat. C, D, E, or F) Tension load: yes (D.3.3.4.3 (d))
Shear load: yes (D.3.3.5.3 (c))

Geometry [in.] & Loading [lb, in.lb]

Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
www.hilti.us Profis Anchor 2.5.1
Company: RMJ Page: 2
Specifier: Mario Project: Creno-G-Series
Address: 241 Joaquin Ave. Sub-Project I Pos. No.: 14273
Phone I Fax: 510.991.0977 | Date: 4/6/2015
E-Mail: msigala@rmjse.com

2 Load case/Resulting anchor forces


Load case: Design loads
y
Anchor reactions [lb]
Tension force: (+Tension, -Compression)
Anchor Tension force Shear force Shear force x Shear force y
1 1275 0 0 0
max. concrete compressive strain: - [‰] 1 x
max. concrete compressive stress: - [psi] Tension
resulting tension force in (x/y)=(0.000/0.000): 1275 [lb]
resulting compression force in (x/y)=(0.000/0.000): 0 [lb]

3 Tension load
Load Nua [lb] Capacity fNn [lb] Utilization bN = Nua/fNn Status
Steel Strength* 1275 8029 16 OK
Pullout Strength* N/A N/A N/A N/A
Concrete Breakout Strength** 1275 1284 100 OK
* anchor having the highest loading **anchor group (anchors in tension)

3.1 Steel Strength


Nsa = ESR value refer to ICC-ES ESR-1917
f Nsteel ≥ Nua ACI 318-11 Table D.4.1.1

Variables
n Ase,N [in.2] futa [psi]
1 0.10 106000
Calculations
Nsa [lb]
10705
Results
Nsa [lb] fsteel f Nsa [lb] Nua [lb]
10705 0.750 8029 1275

Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
www.hilti.us Profis Anchor 2.5.1
Company: RMJ Page: 3
Specifier: Mario Project: Creno-G-Series
Address: 241 Joaquin Ave. Sub-Project I Pos. No.: 14273
Phone I Fax: 510.991.0977 | Date: 4/6/2015
E-Mail: msigala@rmjse.com

3.2 Concrete Breakout Strength

Ncb = (AA ) y
Nc
Nc0
ed,N yc,N ycp,N Nb ACI 318-11 Eq. (D-3)
f Ncb ≥ Nua ACI 318-11 Table D.4.1.1
ANc see ACI 318-11, Part D.5.2.1, Fig. RD.5.2.1(b)
ANc0 = 9 h2ef ACI 318-11 Eq. (D-5)

( )
1
yec,N = 2 e'N ≤ 1.0 ACI 318-11 Eq. (D-8)
1+
3 hef

(
yed,N = 0.7 + 0.3 1.5h
ca,min
ef
)
≤ 1.0 ACI 318-11 Eq. (D-10)

(
ca,min 1.5hef
ycp,N = MAX c , c
ac ac
)
≤ 1.0 ACI 318-11 Eq. (D-12)
1.5
Nb = kc la √fc hef
'
ACI 318-11 Eq. (D-6)

Variables
hef [in.] ec1,N [in.] ec2,N [in.] ca,min [in.] yc,N
2.000 0.000 0.000 6.000 1.000

cac [in.] kc la f'c [psi]


5.500 17 1.000 3000

Calculations
ANc [in.2] ANc0 [in.2] yec1,N yec2,N yed,N ycp,N Nb [lb]
36.00 36.00 1.000 1.000 1.000 1.000 2634
Results
Ncb [lb] fconcrete fseismic fnonductile f Ncb [lb] Nua [lb]
2634 0.650 0.750 1.000 1284 1275

Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
www.hilti.us Profis Anchor 2.5.1
Company: RMJ Page: 4
Specifier: Mario Project: Creno-G-Series
Address: 241 Joaquin Ave. Sub-Project I Pos. No.: 14273
Phone I Fax: 510.991.0977 | Date: 4/6/2015
E-Mail: msigala@rmjse.com

4 Shear load
Load Vua [lb] Capacity fVn [lb] Utilization bV = Vua/fVn Status
Steel Strength* N/A N/A N/A N/A
Steel failure (with lever arm)* N/A N/A N/A N/A
Pryout Strength* N/A N/A N/A N/A
Concrete edge failure in direction ** N/A N/A N/A N/A
* anchor having the highest loading **anchor group (relevant anchors)

5 Warnings
• Load re-distributions on the anchors due to elastic deformations of the anchor plate are not considered. The anchor plate is assumed to be
sufficiently stiff, in order not to be deformed when subjected to the loading!

Input data and results must be checked for agreement with the
existing conditions and for plausibility!
• Condition A applies when supplementary reinforcement is used. The Φ factor is increased for non-steel Design Strengths except Pullout
Strength and Pryout strength. Condition B applies when supplementary reinforcement is not used and for Pullout Strength and Pryout
Strength. Refer to your local standard.
• Refer to the manufacturer's product literature for cleaning and installation instructions.
• Checking the transfer of loads into the base material and the shear resistance are required in accordance with ACI 318 or the relevant
standard!
• An anchor design approach for structures assigned to Seismic Design Category C, D, E or F is given in ACI 318-11 Appendix D, Part
D.3.3.4.3 (a) that requires the governing design strength of an anchor or group of anchors be limited by ductile steel failure. If this is NOT the
case, the connection design (tension) shall satisfy the provisions of Part D.3.3.4.3 (b), Part D.3.3.4.3 (c), or Part D.3.3.4.3 (d). The
connection design (shear) shall satisfy the provisions of Part D.3.3.5.3 (a), Part D.3.3.5.3 (b), or Part D.3.3.5.3 (c).
• Part D.3.3.4.3 (b) / part D.3.3.5.3 (a) requires that the attachment the anchors are connecting to the structure be designed to undergo ductile
yielding at a load level corresponding to anchor forces no greater than the controlling design strength. Part D.3.3.4.3 (c) / part D.3.3.5.3 (b)
waives the ductility requirements and requires that the anchors shall be designed for the maximum tension / shear that can be transmitted to
the anchors by a non-yielding attachment. Part D.3.3.4.3 (d) / part D.3.3.5.3 (c) waives the ductility requirements and requires the design
strength of the anchors to equal or exceed the maximum tension / shear obtained from design load combinations that include E, with E
increased by W0.
• Hilti post-installed anchors shall be installed in accordance with the Hilti Manufacturer's Printed Installation Instructions (MPII). Reference
ACI 318-11, Part D.9.1

Fastening meets the design criteria!

Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
www.hilti.us Profis Anchor 2.5.1
Company: RMJ Page: 5
Specifier: Mario Project: Creno-G-Series
Address: 241 Joaquin Ave. Sub-Project I Pos. No.: 14273
Phone I Fax: 510.991.0977 | Date: 4/6/2015
E-Mail: msigala@rmjse.com

6 Installation data
Anchor plate, steel: - Anchor type and diameter: Kwik Bolt TZ - CS 1/2 (2)
Profile: no profile; 0.000 x 0.000 x 0.000 in. Installation torque: 480.001 in.lb
Hole diameter in the fixture: df = 0.563 in. Hole diameter in the base material: 0.500 in.
Plate thickness (input): 0.250 in. Hole depth in the base material: 2.625 in.
Recommended plate thickness: not calculated Minimum thickness of the base material: 4.000 in.
Cleaning: Manual cleaning of the drilled hole according to instructions for use is required.

1.500 1.500

1.500

1.500
1 x

1.500

1.500

1.500 1.500

Coordinates Anchor in.


Anchor x y c-x c+x c-y c+y
1 0.000 0.000 6.000 6.000 6.000 6.000

Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan