Você está na página 1de 6

Effective: March 2008

AlarmLine™ Addressable
Linear Heat Detector
P/N 73-100001-003 TM

K-73-02
FEATURES
• UL Listed
• FM Approved
• CSFM
• MEA (pending)
• Low-cost interface between AlarmLine™ sensor
cable and control panel accepting SmartOne™
addressable devices
• Up to 255 Addressable AlarmLine Modules (AAM)
per addressable loop
• Real-time monitoring
• Software adjustable alarm set point
• Optional pre-alarm and overheat output
configuration selections
• Three cable styles (standard, nylon, bronze braided)
• Sensor cable restorable up to 257°F
• Full supervision for short and open circuits
• Two-color status-LED display for alarm and trouble DESCRIPTION
conditions
The AlarmLine Addressable Linear Heat Detector
• Intrinsically safe option
provides early detection of fire or overheat condition in
• Flexibility in zoning
protected areas or equipment. It is especially suited for
• Enhanced response time confined areas or environments where adverse ambient
conditions cause other detection devices to be unreliable
or difficult to use. The detector consists of two major
components: A sensor cable and an Addressable
AlarmLine Module (AAM).
The AAM is used with any intelligent control panel that
accepts SmartOne devices.

APPLICATIONS
• Open-area protection
• Cable trays
• Rack storage
• Freezer warehouses
• Belt conveyers
• Floating roof fuel tanks
• Cooling towers
• Dust collectors
• Waste fuel drum storage
• Power distribution apparatus
• Escalators
• Tunnels
• Mines
• Hangars
BENEFITS
NEGATIVE TEMPERATURE
Application Flexibility: Allows installation at point of COEFFICIENT MATERIAL

risk. Programmable pre-alarm, alarm, and overheat SENSOR CONDUCTOR


levels for differing ambient conditions. WIRE

Durability: Extrusion and braiding options to satisfy


environmental conditions and project risks. CABLE SENSOR

Reliability: Fault signaling of open and short circuit PROTECTIVE INSULATION


conditions, pre-alarm, alarm, and overheat reporting. HIGH TEMPERATURE PVC

Figure 1. Standard Sensor Cable


Recoverability: Cable does not need to be replaced
after an alarm event as high as 257º F (125º C).
PART NUMBERS
Sensitivity: Proven superiority over point-type
measurement. Sensor cable is available with the following part numbers:
Standard Sensor Cable
ANALOG HEAT SENSING
73-117068-013 (656 ft./200 m)
AlarmLine’s analog heat sensing characteristics offer 73-117068-113 (3280 ft./1000 m)
several distinct advantages:
Recommended for environments ranging from clean and
Field Adjustability of pre-alarm, alarm, and overheat dry to moderate dust and moisture.
setpoints: Pre-alarm, alarm, and overheat thresholds
Nylon Coated Sensor Cable
may be programmed to meet specific system
requirements. 73-117068-016 (656 ft./200 m)
73-117068-116 (3280 ft./1000 m)
Integrating: It is not necessary to reduce sensor spacing Recommended for use in wet, oily, or corrosive
with increased ceiling height per NFPA 72-2007 Section environments or outdoors. Use in freezer warehouses.
5.6.5.5.1, Exception (1). System sensitivity remains
constant as ceiling height increases without reducing Phosphor Bronze Braided Sensor
spacing. 73-117068-019 (656 ft./200 m)
73-117068-119 (3280 ft./1000 m)
Short Circuit Discrimination: The system will produce
a trouble condition instead of a false alarm in the event of Recommended for applications requiring superior
a conductor to conductor short due to damage or abrasion protection and/or increased tensile strength.
electrical faults. ADDRESSABLE ALARMLINE MODULE (AAM)
SENSOR CABLE The AAM permits an AlarmLine sensor cable to be
The AlarmLine sensor cable consists of four 26 AWG directly interfaced to any control panel that accepts
copper conductors, each color-coded in an insulated SmartOne addressable loop devices. This interface will
sheath containing a negative temperature coefficient allow for pre-alarm, alarm, and trouble conditions to be
polymer (where an increase in temperature decreases transmitted to the control panel via the Signaling Line
the resistance of the sensor). Circuit (SLC). The AAM monitors the resistance of the
sensor cable and generates a pre-alarm (if enabled),
Two of the conductors are enameled and provide loop alarm, or overheat output (if enabled) when the
continuity supervision, but not temperature sensing. The resistance drops below the programmed threshold. The
conductors are twisted at thirty turns per foot (90 turns module also supervises the AlarmLine cable for opens
per meter) and protected by a flame-retardant outer and shorts, which will generate a fault condition.
extrusion or metallic braid (See Figure 1). The color
coding of the four inner conductors is repetitively marked All of the pre-alarm, alarm, overheat, and trouble
on the outer coating every three feet as an aid conditions will be displayed on the control panel. Up to
installation. Cable is sold in standard coils of 656 feet 255 AAM modules can be connected to a single SLC
(200 meters) and 3280 ft. (1000 m). loop. Use of multiple AAMs allows flexibility in zoning
larger installations for location of alarm and zone output
Note: The maximum length of sensor cable per zone control; the control panel acts as a central display and
depends on the maximum ambient temperature control interface.
defined on the nomogram(s) (See Figures 2 and
3). Regardless of ambient temperature, however, The AAM receives power directly from the SLC loop
the maximum length of cable is 3280 feet (1000 which eliminates the need for additional wiring and
meters) per zone for Type “T” cable. external power supplies.

-2-
For further information on installation and configuration of
Bronze
the AAM, please refer to the AlarmLine Addressable Description
Standard Nylon Coated
Braided
Linear Heat Detector Installation, Operation, and Sensor Sensor
Sensor
Maintenance Manual, P/N 06-235820-003.
Service Life Up to 212ºF Up to 212ºF Up to 212ºF
The Addressable AlarmLine Module is available using (100ºC) = 30 (100ºC) = 30 (100ºC) = 30
the following part numbers: years @ 257ºF years @ 257ºF years @ 257ºF
(125ºC) = 24 (125ºC) = 24 (125ºC) = 24
hours. hours. hours.
73-100001-003 Self Restores Self Restores Self Restores
Module with operating temperature range of -40º Fº to below 257ºF below 257ºF below 257ºF
(125ºC) (125ºC) (125ºC)
140º F (-40º C to 60º C). Mounted on a 4-inch square Above 374ºF Above 374ºF Above 374ºF
faceplate. AAM mounts in a 4-inch square backbox, (190ºC) is the (190ºC) is the (190ºC) is the
destructive destructive destructive
2-1/8-inches deep. temperature. temperature. temperature.

73-100003-001 Approved 30 ft. 30 ft. 30 ft.


Spacing (9 m) (9 m) (9 m)
NEMA-4 sealed, protective polycarbonate enclosure (between
used to mount AAM in wet or dusty environments. parallel runs)

CABLE SPECIFICATIONS
SENSOR MOUNTING HARDWARE
Three types of standard mounting hardware (master
Bronze
Description
Standard Nylon Coated
Braided
clamp, flange clamp, nylon cable tie) for AlarmLine
Sensor Sensor permit safe, secure sensor cable installation in most
Sensor
applications. Other mounting means may be used as
Part Number : 73-117068-013 73-117068-016 73-117068-019 required by the specific application. The sensor should
Length: 656 ft. (200 m) 656 ft. (200 m) 656 ft. (200 m)
Weight: 7 lbs. (3.2 kg) 7 lbs. (3.2 kg) 7 lbs. (3.2 kg) be supported at a minimum of ten foot intervals on
straight runs when under tension, and more as conditions
Part Number : 73-117068-113 73-117068-116 73-117068-119
Length: 3280 ft. (1000 m) 3280 ft. (1000 m) 3280 ft. (1000 m) dictate at corners and transition points to provide suitable
Weight: 35 lbs. (14.5 kg) 35 lbs. (14.5 kg) 35 lbs. (14.5 kg) strain relief. Local codes or conditions may also require
Jacket Blue PVC Black nylon Phosphor
the sensor to be supported at closer intervals. Refer to
Construction extrusion over bronze braid the AlarmLine Addressable Linear Heat Detector
blue PVC over blue PVC
Installation, Operation, and Maintenance Manual, P/N
External 0.117 in. 0.153 in. 0.153 in. 06-235820-003 for specific mounting information.
Diameter (3 mm) (3.9 mm) (3.9 mm)

Tensile 100 N 100 N 1000N


Strength

Conductor 1 = Orange 1 = Orange 1 = Orange


Insulation 2 = White 2 = White 2 = White
Costs 3 = Red 3 = Red 3 = Red
4 = Blue 4 = Blue 4 = Blue

Conductor 26 AWG Solid 26 AWG Solid 26 AWG Solid


Material Copper Copper Copper

Conductor 0.018 in. 0.018 in. 0.018 in.


Diameter (0.460 mm) (0.460 mm) (0.460 mm)

Twist of Inner 30 per ft. 30 per ft. 30 per ft.


Conductors (90 per m) (90 per m) (90 per m)

Dielectric Specially Doped Specially Doped Specially Doped


Material Polymer Polymer Polymer

Standard Outer High High High


Jacket Material Temperature Temperature Temperature
PVC PVC PVC

Voltage Proof 10 KV 10 KV‘ 10 KV


Between PVC
Jacket and a
Conductor

-3-
AAM SPECIFICATIONS UL Listed and FM Class I, Division I, Groups A, B, C, D
Approvals Class II, Division I, Groups E, F, G: Class
III, Division I
Specification Value
Operating Tempera- -4ºF (-20ºC) to 140ºF (60ºC)
Part Number 73-100001-003 ture Range
Humidity 5 -95% R.H.
Supply Voltage P.C. Line, 16.5 to 27.5 Vdc
Terminals Will accept up to #12 AWG
Current Consumption, 425 µAmps Working Voltage 6V
Standby Maximum Voltage 7.5V
Current Consumption, Alarm 440 µAmps Fuse Rating 100 mA
Leakage Current 1 mA maximum at 6V
Current Consumption,Fault 425 µAmps
End-To-End Resis- 145 ohm maximum
Noise Performance Withstands 5% RMS 60 Hz tance 90 ohm minimum
supply noise or 1 Vrms 60 Enclosures 73-117068-732 holds 2 barriers
Hz sensor noise with 73-117068-733 holds 5 barriers
negligible performance 73-117068-734 holds 12 barriers
range. RFI immunity at 10 73-117068-735 holds 24 barriers
V/meter field strength over
SETTING THE ALARM TEMPERATURE
the band of 20 to 900 MHz
When determining the alarm temperature setting, the
Normal: Slow flash GREEN designer must take into account environmental factors
every nine (9) seconds that may affect the overall response of the system. By
Pre-Alarm: Slow flash RED accounting for these factors, the designer minimizes
every nine (9) seconds unwanted alarms. Below is a step by step procedure
LED Pulse Modes
which instructs the designer in selection of the proper
Alarm: Fast flash RED every alarm trip points.
two (2) seconds
The required alarm temperature and the correct alarm
Trouble: Off configuration setting for the AAM are determined using
the AlarmLine nomogram(s).
Operating Temperature -40°F to 140°F
Range (-40°C to 60°C) Measurements are in feet/fahrenheit or meters/
centigrade.

INTRINSIC SAFETY BARRIERS The use of the nomogram requires two known factors:
In classified hazardous areas where potentially explosive • Maximum ambient temperature of the alarm zone.
vapors, dust, or fibers exist, AlarmLine cable must (Scale A).
installed using an intrinsic safety barrier. The barrier (P/N • The total length of the sensor cable to be used.
73-117068-031) is a shunt diode safety barrier which (Scale L).
limits the current and voltage in the sensor cable to safe The resistance change required to create an alarm can
levels. Each barrier handles two conductors, so two be a result of either a predetermined minimal increase in
barriers are needed for each sensor cable. The barriers temperature over the entire length of the sensor, or a
are designed to mount in separate weathertight significant increase on a shorter section of cable. The
enclosures. The intrinsic safety barrier’s specifications alarm temperature in either case is determined only after
are as follows: the alarm trip switch position for the entire sensor length
is known.
A shorter section of sensor cable exposed to an overheat
condition will require a higher temperature to achieve an
alarm than a longer length of sensor cable exposed to
the same overheat condition.
The maximum length of sensor cable per zone depends
on the maximum ambient temperature defined on the
nomogram. Regardless of ambient, however, the
maximum length of cable connected to a single AAM is
3280 ft. (1000 m). If cable length exceeds 3280 ft., the

-4-
alarm condition could be reached at room temperature
KIDDE-FENWAL, INC.
(70º F (20º C)) for most switch settings. Refer to the 400 MAIN ST. ASHLAND, MA 01721
UL
TM
AlarmLine Addressable Linear Heat Detector Installation,
R

ADDRESSABLE ALARMLINE MODULE


CAT NO. 73-100001-003
Operation, and Maintenance Manual, P/N PRODUCT MUST BE INSTALLED AND OPERATED
FM

06-235820-003 for more information. IN ACCORDANCE WITH KIDDE-FENWAL INSTALLATION


MANUAL 73.04 AND JURISDICTION OF LOCAL AUTHORITY.
APPROVED

DATE OF MANUFACTURE: DEVICE


ALL TERMINALS ARE POWER LIMITED ADDRESS # _ _ _ _
S A T L
P.C. LINE SENSOR CABLE
Alarm Maximum Specified Sensor

WHT

ORN
RED
BLU
Configuration Ambient Alarm Cable A B A B
Setting Temp. (F) Temp. (F) Length (Ft.)
TB1 4 3 2 1 4 3 2 1 TB2

3200

ORANGE
2900

WHITE
2600

BLUE

RED
2300
2000
1650
INTERCONNECT CABLE
1300 EARTH P.C.LINE P.C.LINE 16 AWG, 4 CONNECTOR
1000
GROUND OUT IN (IF REQUIRED)
1 825
650
2
500
3 95 WEATHERPROOF
75 4 3 2 1
105 JUNCTION BOX
4 300 4 3 2 1
85
115
265 (IF REQUIRED)
5 95 230
120 200
6 105 165
130
115 130
7 140 SENSOR CABLE
120 100
8 150 80
130
140
160 65 Figure 4. Wiring the AAM to a Panel
9 50
165
150
10 175
160 35
185
ADDRESSABLE ALARMLINE MODULE WIRING
165 25
11 175 195
185 205 20
12 195 210
220 The Addressable AlarmLine Module (P/N 73-100001-
13 230
240 10 003) may connected to any fire control panel that accepts
14 250

15
257 SmartOne addressable devices. The module is wired
16
5
directly to the SLC loop of the panel as shown in Figure
3
4. Refer to the AlarmLine Addressable Linear Heat
Figure 2. Example for Type “T” Cable (Feet/Fahrenheit) Detector Installation, Operation, and Maintenance
Manual, P/N 06-235820-003 for complete wiring
S A T L
information.
NEMA-4 ENCLOSURE
Alarm Maximum Specified Sensor
Configuration Ambient Alarm Cable
Settng Temp. (F) Temp. (F) Length (Ft.)
The NEMA-4 polycarbonate enclosure (P/N 73-100003-
3200
2900
2600
001) is designed to mount the Addressable AlarmLine TM

2300
2000 Module in areas requiring additional protection from wet
and/or dusty environments. This enclosure is rated as
1650
1300
1000
825
follows:
1

• UL 508 Type 4, Type 4X, Type 6, Type 12, and Type


650
2
500
3
75
95
105
13
4 300

5
85
95
115
265
230 • NEMA Type 4, Type 4X, Type 6, Type 12, and Type
6 105
120
130
200
165 13
130
• CSA Type 4, Type 4X, Type 6, Type 12, and Type 13
115
7 140
120 100
150 80
8

9
130
140
160 65 • Flammability rating UL94-5V
• IEC 529, IP66
165 50
150
10 175
160 35
185
11
165
175 195 25
20
The enclosure is equipped with a clear cover so that the
185 205
12 195 210
220
AAM alarm/trouble status indicator LED can be viewed.
13

14
230
240
250
10
The cover also provides a molded-in wire-lead hole for
15
257
5
tamper resistant installation. Mounting holes for the
16
3 enclosure are molded directly under the cover screws. A
Figure 3. Example for Type “T” Cable (Feet/Fahrenheit) cover gasket assures watertight and dust-tight seals.

-5-
The impact-resistant, glass-filled, polycarbonate
enclosure material is easily punched, drilled, or sawed to
provide access for field wiring.
For further installation information, refer to the AlarmLine
Addressable Linear Heat Detector Installation, Operation,
and Maintenance Manual, P/N 06-235820-003.

ENCLOSURE
4.330

BRACKET

AAM
4.330

COVER
TM

e
Lin
MOUNTING HOLE rm
Ala
FOR #8 SCREW (TYP.)

TM

SELF-TAPPING SCREWS e
On
art
Sm

TINNERMAN CLIPS

#8-32 SCREWS

CROSS-POINT, CAPTIVE
COVER SCREWS

Figure 5. NEMA-4 Enclosure with AAM

This literature is provided for informational purposes only. KIDDE-FENWAL, INC.


assumes no responsibility for the product’s suitability for a particular application. The TM
product must be properly applied to work correctly.
If you need more information on this product, or if you have a particular problem or ques-
tion, contact KIDDE-FENWAL, INC., Ashland, MA 01721. Telephone: (508) 881-2000.
KIDDE-FENWAL INC.
400 MAIN STREET, ASHLAND, MA 01721
K-73-02 Rev BB © 2008 Kidde-Fenwal Inc. Printed in USA TEL: (508) 881-2000 FAX: (508) 881-8920
www.Kidde-Fenwal.com