Você está na página 1de 1

NOTE:

PURSUANT 70 SECTION 4 OF ANNEX "A" OF THE


REVISED NPLEMBVIING RULES AND REGULATION OF RA. Mt
APPROK BY RE AUTHORIZED OPIVH OfF7CLALS OF DETAILED
OVGINEERING SLAMS AND DESIGN UNDERTAKEN BY CONSULTANTS
NEITHER LYAIMESHES THE RESPONSIBILITY OF THE LATTER

GENERAL CONSTRUCTION NOTES


FOR 77 ETECHMLYLIA7EGRITYOF THE SURVEYSAND DESIGN
(ION TRANSFER ANY PART OF THAT RESPONSITILITY TO THE
APPROVINGOFFICIALS

RE DIMON =SWAP? SHALL BE HELD FULLY RESPONSIBLE


GENERAL NOTES NOTES ON CONCRETE MIXES & PLACING TYPICAL BAR BENDING AND CUTTING DETAILS FOR SLABS FOR THE FAILURE OF ME FACILITY/TES/STRUCTURES
DUE TO FAULTY DESIGN EXCEPT FEW THE CHANGES WOE
3. IF SLABS ARE REINFORCED BOTHWAYS BARS ALONG THE SHORTER SPAN SHALL BE PLACED
WITHOUT RECONFORAIITYOF RE CONSULTANTS
1.0 STANDARDS AND REFERENCES 1. ALL CONCRETE SHALL DEVELOP A MIN. COMPRESSIVE STRENGTH AT THE END OF TWENTY
EIGHT (28) DAYS W/ CORRESPONDING MAXIMUM SIZE AGGREGATE & SLUMPS AS FOLLOWS. BELOW THOSE ALONG THE LONG SPAN AT THE CENTER AND OVER THE LONGER SPAN
THE FOLLOWING SHALL GOVERN THE DESIGN, FABRICATION AND CONSTRUCTION OF THE PROJECT. FOR REINFORCING BARS NEAR THE SUPPORTS. THE SPACING OF THE BARS AT THE COLUMN
LOCATION 28 DAYS STRENGTH MAX. SIZE OF MAX. SLUMP STRIPS SHALL NOT BE MORE THAN ONE AND A HALF (1 1/2) SLAB THICKNESS
1.1 NATIONAL STRUCTURAL CODE OF THE PHIUPPINES (N.S.C.P.). VOL. 1, 6TH EDITION, AGGREGATE
2010. 4. TEMPERATURE BARS FOR SLAB SHALL BE GENERALLY PLACED NEAR THE FACE IN TENSION
2.0 DESIGN CRITERIA ALL OTHERS. INCLUDING AND SHALL NOT BE LESS THAN 0.0025 x GROSS CROSS-SECTIONAL AREA (Ag) OF THE SLAB JOINT HOOP SPACE 0 "2Sh" WHEN THERE
SUSPENDED SLABS. 3000 PSI (20.7 MPa) 20mm 100mm (SEE SCHEDULE BELOW) ARE BEAMS HAVING WIDTH OF AT LEAST
2.1 LOADINGS COLUMNS 3000 PSI (20.7 MPa) 20mm 100mm ONE-HALF THE COLUMN WIDTH & DEPTHS
A. DEAD LOAD NOT LESS THAN THREE QUARTERS OF THE
CONCRETE 23.56kN/m BEAMS. SLABS 3000 PSI (20.7 MPa) 20mm 100mm SCHEDULE OF MINIMUM SLAB REINFORCEMENT DEEPEST BEAM THAT FRAME INTO FOUR
STEEL 76.93kN/rn SLAB ON FILL 2500 PSI 20mm 100mm SIDES OF THE COLUMN. ALL OTHER
150mm THK. CHB WALL
(17.5 MPa) THICKNESS MINIMUM TEMPERATURE BARS
2.73 kPa CONDITIONS USE HOOPS 0 "Sh" CENTERS.
100mm THK. CHB WALL 2.11 kPa 100 mm 10 mm 0 0 250mm EACH WAY
2. MAINTAIN MINIMUM CONCRETE COVER FOR REINFORCING STEEL AS FOLLOWS.
B. LIVE LOAD SUSPENDED SLABS ------------------------------------------------------------------------------ 125 mm 10 mm 0 0 225mm EACH WAY
20mm
ROOF 1.00 kPa
1.90 kPa
SLAB ON GRADE------------------------------------------------------------------------------------------- 4Ornm 150 mm 10 mm 0 0 185mm EACH WAY
CLASSROOMS
TOILETS 2.40 kPa WALLS ABOVE GRADE ---------------------------------------------------------------------------------- 25rnrn
4Ornm 175 mm 10 mm 0 0 150mm EACH WAY
CORRIDORS ABOVE, STAIRS 3.80 kPa BEAM STIRRUPS AND COLUMN TIES -------------------------------------------------------
CORRIDORS ON GROUND 4.80 kPa WHERE CONCRETE IS EXPOSED TO 200 mm 10 mm 0 0 140mm EACH WAY FOR COL. BAR SPLICES SEE TABLE
EARTH BUT POURED AGAINST FORMS ----------------------------------------------------- 5Ornm OF MIN. LAP SPUCE LENGTH OF
C. WIND LOAD (NSCP 2010) COLUMN REINFORCEMENT
WHERE CONCRETE IS DEPOSITED
BASIC WIND VELOCITY. V = 250 KPH DIRECTLY AGAINST EARTH -------------------------------------------------------------------------- 75mm (SPACING OF TIES ALONG THIS REGION
P = qh [(GCpf)-(GCpi)] (DESIGN WIND PRESSURE) 5. UNLESS OTHERWISE NOTED IN THE PLANS ALL BEDDED SLABS SHALL BE REINFORCED
SHALL NOT BE LESS THAN 100mm)
3. CONCTRETE SHALL BE DEPOSITED IN ITS FINAL POSITION WITHOUT SEGREGATION. RE-HAND WITH 10mm 0 AT 250rnrn O.0 EACH WAY TO CENTER OF SLAB AND CONSTRUCTION
WHERE: qh = VELOCITY PRESSURE. kPa)
GCpf = EXTERNAL PRESSURE COEFFICIENT LING OR PLACING SHALL BE DONE PREFERABLY WITH BUGGIES, BUCKETS OR JOINTS FOR SAME SHALL NOT BE LESS THAN 3.65 METER APART
GCpi = INTERNAL PRESSURE COEFFICIENT WHEELBARROWS. NO CHUTES WILL BE ALLOWED EXCEPT TO TRANSFER CONCRETE FROM 6. PROVIDE EXTRA REINFORCEMENTS FOR CORNER SLAB (TWO ADJACENT DISCONTINUOUS
D. SEISMIC LOAD (NSCP 2010)
HOPPERS TO BUGGIES, WHEELBARROWS OR BUCKETS IN WHICH CASE THEY SHALL NOT
EXCEED SIX (6) METERS IN AGGREGATE LENGTH.
EDGES) AS SHOWN BELOW.
NOTE:
7. CONCRETE SLAB REINFORCEMENTS SHALL BE PROPERLY SUPPORTED WITH 10rnrn0 STEEL ALL CONCRETE REINF. DETAIL SHOULD BE
Cvl 4. NO DEPOSITING OF CONCRETE SHALL BE ALLOWED WITHOUT THE USE OF VIBRATORS CHAIR OR APPROVED EQUIVALENT SPACED AT 1.0 METER ON CENTER BOTHWAYS
V= W (DESIGN BASE SHEAR) DONE IN ACCORDANCE WITH THE LATEST
RT UNLESS AUTHORIZED IN WRITING BY THE DESIGNERS AND ONLY FOR UNUSUAL CONDITIONS EDITION OF ACI DETAILING MANUAL
WHERE VIBRATIONS ARE EXTREMELY DIFFICULT TO ACCOMPLISH.
2.50 Cal
Vmax W Vrnin = 0.11 CalW
R 5. ALL ANCHOR BOLTS, DOWELS. AND OTHER INSERTS, SHALL BE PROPERLY POSITIONED &
0.80 ZNvI 012x1000 LONG AT
Vrnin 0 . 8
W (ZONE 4) SECURED IN PLACE PRIOR TO PLACING OF CONCRETE.
MID-DEPTH OF SLAB
6. ALL CONCRETE SHALL BE KEPT MOIST FOR A MINIMUM OF SEVEN CONSECUTIVE DAYS DOWN INTO EDGE BEAM. EXTENDED 4-
AT EACH CORNER
WHERE: W = TOTAL DEAD LOAD 0 120 1800 LONG TOP BARS BEND
IMMEDIATELY AFTER POURING BY THE USE OF WET BURLAP, FOG SPRAYING, CURING 1 -0 2 TO P &
TYPICAL COLUMN ELEV. SHOWING
T = NATURAL PERIOD = (h r ,) 2 / 3 ; BARS MIN. OF 1.200 (4 . -0") INTO BARS.
COMPOUNDS OR OTHER APPROVED METHODS. BOTT. BARS
WHERE: C = NUMERICAL COEFFICIENT
h = BUILDING HEIGHT 4-012 BOTT. BARS DOWELS AND TIES SPACING
7. STRIPPING OF FORMS AND SHORES:
I = IMPORTANCE FACTOR = 1.50 FOUNDATION ------------------------------------------------------------------------------------- 2 4 HRS. Ar 1-012 EA.
R = NUMERICAL FACTOR = 8.50
SEISMIC COEFFICIENT Cv = 0 . 4 4 Nv SUSPENDED SLAB EXCEPT WHEN
Ca = 0.64N ADDITIONAL LOADS ARE IMPOSED --------------------------------------------------------------- B DAYS
NEAR SOURCE FACTOR (10krn) Nv = 1.2 WALLS ------------------------------------------------------------------------------------------------------------- 21 DAYS
TOP & BOT.
Na = 1.0 BEAMS ------------------------------------------------------------------------------------------------------------- 14 DAYS

I
CLE LAP SPLICE LENGTH:
Z = SEISMIC ZONE = 0.40 (ZONE 4) COLUMNS --------------------------------------------------------------------------------------------------------- 21 DAYS AT ANY LEVEL NO MORE THAN
S = SOIL TYPE = D ALTERNATE BARS SHOULD BE
8. THE CONTRACTOR SHALL SUBMIT THE SCHEDULE OF POURING AND THE LOCATION OF THE _____ 1-012 EA. SPUCED. MIN. DISTANCE BET.
CONSTRUCTION JOINTS TO THE STRUCTURAL ENGINEER AT LEAST (4) DAYS PRIOR TO THE TOP & BOT. TWO ADJACENT BARS SPUCES

-
.1
2.2 DESIGN STRESSES POURING FOR APPROVAL. -
A. CONCRETE FOR FOOTING, COLUMNS, BEAMS AND SLAB ON FILL SECTION "A" SHALL BE 600rnrn.

I
COMPRESSIVE STRENGTH 0 28 DAYS fc' = 20.7 MPa (3.000 psi ) 9. THE CONTRACTOR SHALL FURNISH AND MAINTAIN ADEQUATE FORMS AND SHORINGS UNTIL THE IN TWO WAY SLAB EXTEND
B. REINFORCING STEEL BARS fy = 275 MPa (41000 pal ) CONCRETE MEMBERS HAVE ATTAINED THEIR WORKING CONDITION AND STRENGTH. BARS UP TO BEAM SUPPORT L/4
a. FOR BARS 15mrne MID GREATER INTERMEDIATE GRADE DEFORMED BAR
fy ■ 230 MPa (33. 000 psi) OMIT TRIMMER BARS WHERE
b. FOR BARS LESS THAN 16mm0 (STRUCTURAL GRADE DEFORMED BAR)
C. STRUCTURAL STEEL, ASTM -A36
OPENING IS FRAMED BY BEAM TOP BARS 0 SUPP RT (CONT.)
FOR TRUSSES. BRACINGS. & STRUTS
fy - 248 MIN. (38.800 psi ) NOTES ON FOOTINGS TYPICAL SLAB REQ'D. BOTT. BARS 0 SUPPORT
D. PURUNS fy = 248 MIN. (38.000 peD
TYPICAL CORNER SLAB DETAIL OPENING DET
COLD FORMED UGHT GAGE SHAPES 1. FOOTINGS ARE DESIGNED FOR AN AL LOW ABLE SOIL BEARING PRESSURE OF 96
E. MASONRY UNIT (CHB) fm' ■ 3. 45 MPa (500 psi)
KPa ( 2000 psf). CONTRACTOR SHALL REPORT TO THE ENGINEER, IN WRMNG, THE ACTUAL
NON- LOAD BEARING CHB WALLS
SOIL CONDITIONS UNCOVERED AND CONFIRM ACTUAL BEARING CAPACITY OF SOIL BEFORE
F. WELDS-USED E-60xx ELECTRODE
G. STRUCTURAL BOLTS. ASTM -A307 DEPOSITING CONCRETE.
a. Ft = 96.60 MPa (1 4.000 psi) b. Fv = 69 MPa (10,000 psi) 2. FOOTING SHALL REST AT LEAST 1500rnm BELOW NATURAL GRADE LINE UNLESS OTHERWISE
NOTES ON COLUMNS
INDICATED IN PLANS. NO FOOTING SHALL REST ON FILL. PUC BOTTOM BARS
1. PROVIDE EXTRA SETS OF TIES AT 100rnrn O.C. FOR TIED COLUMN REINFORCEMENT AT MID SPAN
3. MINIMUM CONCRETE PROTECTION FOR REINFORCEMENTS SHALL BE 75mm CLEAR ABOVE AND BELOW BEAM-COLUMN CONNECTIONS FOR A DISTANCE FROM FACE OF
FOR CONCRETE DEPOSITED THE GROUND AND 50nun FOR CONCRETE CONNECTION EQUAL TO THE GREATER OF THE OVERALL THICKNESS OF COLUMN, EXTRA TOP BARS
3. IN THE INTERPRETATION OF THE DRAWING. INDICATED DIMENSIONS SHALL GOVERN AND DEPOSITED AGAINST A FORMWORK. 1/6 THE CLEAR HEIGHT OF COLUMN OR 450rnrn. 0 SUPPORT
DISTANCES AND SIZES SHALL NOT BE SCALED FOR CONSTRUCTION PURPOSES. IN CASES WHERE THE SOIL CONDITION IS SUCH THAT THE MINIMUM ALLOWABLE SOIL
PRESSURE OF 96 KPa (2,000 psf) CAN NOT BE ATTAINED AT PRACTICAL DEPTHS, THE USE OF 2. COLUMN TIES SHALL BE PROTECTED EVERYWHERE BY A COVERING OF CONCRETE CAST TYP. DETAIL OF COL. LAP SPLICE
4. IN REFERENCE TO OTHER DRAWINGS, SEE ARCHITECTURAL DRAWINGS FOR
DEPRESSIONS IN FLOOR SLABS, OPENINGS IN THE WALLS AND SLABS, INTERIOR
MICROPILES, BORED PILES, OR DRIVEN PILES MAY BE ADOPTED IN LIEU OF STANDARD ISOLATED MONOLITHICALLY WITH THE CORE WITH THE MINIMUM THICKNESS OF 40rnrn AND NOT
LESS THAN 40 TIMES THE MAXIMUM SIZE OF COARSE AGGREGATE IN MILLIMETERS. & EXT. GIRDER TO COL. CONNECT.
FOOTINGS.
PARTIONS, LOCATION OF DRAINS ETC.
3. WHERE COLUMNS CHANGE IN SIZE, VERTICAL REINFORCEMENTS SHALL SHALL BE OFFSET
5. IN CASE OF DISCREPANCIES AS TO THE LAYOUT, DIMENSIONS. AND ELEVATIONS BETWEEN AT A SLOPE OF NOT MORE THAN 1 IN 6 AND EXTRA 10mm TIES AT 100mm SHALL BE
THE STRUCTURAL PLANS, AND ARCHITECTURAL DRAWINGS, THE CONTRACTOR SHALL NOTIFY PROVIDED THRU OUT THE OFFSET REGION. NOTES ON BEAMS AND GIRDERS
BOTH THE STRUCTURAL ENGINEER AND THE ARCHITECT.
NOTES ON REINFORCEMENT 4. UNLESS OTHERWISE INDICATED IN THE PLANS. LAP SPUCES FOR VERTICAL COLUMN
6. ALL CONCRETE WORK SHALL BE DONE IN ACCORDANCE WITH THE ACI.318 95 BUILDING REINFORCEMENT SHALL BE MADE WITHIN THE CENTER HALF OF COLUMN HEIGHT, AND 1. UNLESS , OTHERWISE NOTED IN PLANS. CAMBER ALL BEAMS AND GIRDER AT LEAST &writ.
CODE REQUIREMENTS FOR REINFORCED CONCRETE AND ALL STRUCTURAL STEEL WORK 1. UNLESS OTHERWISE NOTED IN PLANS, THE YIELD STRENGTH OF REINFORCING BARS SHALL BE: THE SPLICE LENGTH SHALL NOT BE LESS THAN 40 BAR DIAMETERS. WELDING OR FOR EVERY 4.50M OF SPAN , EXCEPT CANTILEVERS FOR WHICH THE CAMBER SHALL BE
ACCORDING WITH AISC SPECIFICATION (9th EDITION) IN SO FAR AS THEY DO NOT CONFLICT A. FOOTINGS, FOOTING BEAMS AND GIRDERS ----- f y = 2 7 5 M P a ( 4 0 . 0 0 0 p s i ) APPROVED MECHANICAL DEVICES MAY BE USED PROVIDED THAT NOT MORE THAN AS NOTED IN PLANS OR AS ORDERED BY THE ENGINEER BUT IN NO CASE LESS THAN
WITH THE LOCAL BUILDING CODE REQUIREMENT. B. CO L UMNS AND SHEA R W AL L S - - - - - - - - - - - - - - - - - - - f y = 2 7 5 M P a ( 4 0 . 0 0 0 p s i ) ALTERNATE BARS ARE WELDED OR MECHANICALLY SPUCED AT ANY LEVEL AND THE 20mm FOR EVERY 3.0M OF FREE SPAN.
VERTICAL DISTANCES BETWEEN THESE WELDS OR SPLICES OF ADJACENT BARS IS NOT
C. BEAMS AND GI RDER ------------------------ fy = 275 MPa ( 40.000 psi ) LESS THAN 600mm. 2. TYPICAL BARS BENDING AND CUTTING DETAILS FOR BEAMS SHALL BE AS
7. ACI REFERS TO AMERICAN CONCRETE INSTITUTE. AISC TO AMERICAN INSTITUTE OF STEEL
SHOW N IN FIG. B-1.
CONSTRUCTION AND ASTM TO AMERICAN SOCIETY FOR TESTING MATERIALS. D. NON-LOAD BEARING WALL PARTITIONS, BEDDED SLABS, FLOOR & ROOF SLABS,
CONSTRUCTION NOTES AND TYPICAL DETAILS APPLY TO ALL DRAWINGS UNLESS OTHERWISE PARAPETS, CATCH BASIN, SIDE WALK. ----------------- f y = 2 2 7 . 5 M P a ( 3 3 , 0 0 0 p s i )
SHOWN OR NOTED. MODIFY TYPICAL DETAILS AS DIRECTED TO MEET SPECIAL CONDITIONS. 2. ALL REINFORCING BARS SIZE 10mm OR LARGER SHALL BE DEFORMED IN ACCORDANCE WITH
ASTM A 706. BARS SMALLER THAN 10mm MAY BE PLAIN.
9. SHOP DRAWINGS WITH ERECTION AND PLACING DIAGRAMS OF ALL STRUCTURAL STEELS,
MISCELLANEOUS IRON. PRE-CAST CONCRETE. ETC. SHALL BE SUBMITTED FOR ENGINEERS 3. SPLICES SHALL BE SECURELY WIRED TOGETHER & SHALL LAP OR EXTEND IN ACCORDANCE
APPROVAL BEFORE FABRICATION. WI TABLE A & TABLE B (TABLE OF LAP SPLICE & ANCHORAGE LENGTH) UNLESS OTHERWISE
L2
SHOWN ON DRAWINGS, SPLICES SHALL BE STAGGERED WHENEVER POSSIBLE.
10 CONTRACTOR SHALL NOTE AND PROVIDE ALL MISCELLANEOUS CURBS. SILLS, STOOLS, L2/3 L3/3
EQUIPMENT'S AND MECHANICAL BASES THAT ARE REQUIRED BY THE ARCHITECTURAL
ELECTRICAL, AND MECHANICAL DRAWINGS. NOTES ON CONCRETE SLABS
11. ALL RESULTS OF MATERIAL TESTING FOR CONCRETE, REINFORCING BARS, & STRUCTURAL ................. =NENE ....
STEEL MUST BE NOTED & APPROVED BY THE STRUCTURAL DESIGNER. 1. ALL SLAB REINFORCEMENTS SHALL BE 20mm CLEAR MINIMUM FROM BOTTOM AND FROM 111111!IIINNA
THE TOP OF SLAB.
2. UNLESS OTHERWISE SHOWN, REINFORCEMENT IN CONTINUOUS ELEVATED SLAB
SHALL BE CUT AS FOLLOWS:

BENT BAR BENT BAR


L1
L2
L1/4
FIG. B-1
1114 r TOP BAR 1-TOP BAR

fp
L BOTTOM BAR
L BOTTOM BAR

JOINT VE NTURE OF DESIGNED: SU BM ITT ED, REVIEWED AS TO RECOMMENDING APPROVAL APPROVED:(FOR ISSUANCE) PROJECT & LOCATION / BARANGAY: SHEET CONTENTS: SET NO. SHEET NO
DESIGN CONCEPT:

UNITEDTECHNOLOGIESCONSOLIDATEDPARTNERSHIP
I VARIOUS DPWH
ABLO . RACINES- REPUBLIC OF THE PHILIPPINES PROPOSED PROJECTS
PBL RACINES (SEE COVER SHEET) (SEE COVER SHEET)
STANDARD TWO-STOREY
PERTCONSULTINTERNATIONAL DEPARTMENT OF PUBLIC WORKS AND HIGHWAYS
JOSOIHINE P. ISTURIS DANTE B. POTANTE RAUL C. ASIS GENERAL NOTES
STRUCTURAL DESIGN MANAGING PARTNER
d,NCH I E F,
SCHOOL BUILDING
SCHEMA ENGINEERS AND ASSOCIATES POSITION: STRUCTURAL ENGINEER
PRC No.: 0014064 TIN No.: 108.321.474
BUILDINGS DIVISION, Kt DIRECTOR IV, BOD UNDERSECRETARY ( 6-CLASSROOMS )
PTR No.:2181624
(REVISED 3-24-17)

• lib. ap04
a .

Você também pode gostar