STEEL BEAM DESIGN

3RD FLOOR - FRAME C & D - 1

REACTIONS:
MOMENTS: CRITICAL LOAD CASE

ML = 13.12 KN-M 20 DL + 0.75LL + 0.525SL+Z


MC = 72.654 KN-M DESIGN MOMENTS:

MR = 116.387 KN-M M1 = 72.654 KN-M

DESIGN SHEAR: M2 = 79.12935 KN-M

V = 92.321 KN M3 = 104.7483 KN-M

STEEL PROPERTIES
Fy = 345 MPa
M
Sx =
Lb = 0 m 0.66(Fy)
SOLUTION:
L = 5 m Sx = 460027.67 mm3 Check Actual Bending Check Actual Shear
EFFECTIVE LENGTHS
Allowable: Allowable:
DESIGN SECTION 200(bf)
L1 = √𝐹𝑦
= 1794.15 mm Fbx = 0.66(Fy) Mpa Fv = 0.40(Fy) Mpa
TRY SECTION W12X35
137900 Fbx = 227.7 Mpa Fv = 138 Mpa
A = 6645.148 mm2 Sx = 747.25 x 10^3 mm3
L2 = d = 2770.61 mm Actual: Actual:
Af Fy M V
d = 317.5 mm bf = 166.624 mm fbx =
Sx
fv =
dtw
tw = 7.62 mm tf = 13.208 mm Lc = L1 ; Lu = L2
fbx = 140.17839 Mpa fv = 38.159423 Mpa
SINCE:
COMPACTNESS OF SECTION Fbx > fbx SAFE! Fv > fv SAFE!

Bf/2tf = 6.31 < = 9.152 COMPACT!


Lc > Lb < Lu
170/√𝐹𝑦

d/tw = 41.67 < 1680/√𝐹𝑦 = 90.448 COMPACT! SECTION IS COMPACT!


Therefore: W12X35 SECTION IS SAFE!

117
STEEL BEAM DESIGN
3RD FLOOR - FRAME C & D - 2

REACTIONS:
MOMENTS: CRITICAL LOAD CASE

ML = 141.84 KN-M 21 DL + 0.75LL + 0.525SL-Z


MC = 86.949 KN-M DESIGN MOMENTS:

MR = 78.855 KN-M M1 = 86.949 KN-M

DESIGN SHEAR: M2 = 97.98375 KN-M

V = 104.035 KN M3 = 127.656 KN-M

STEEL PROPERTIES
Fy = 345 MPa
M
Sx =
Lb = 0 m 0.66(Fy)
SOLUTION:
L = 6 m Sx = 560632.41 mm3 Check Actual Bending Check Actual Shear
EFFECTIVE LENGTHS
Allowable: Allowable:
DESIGN SECTION 200(bf)
L1 = √𝐹𝑦
= 1794.15 mm Fbx = 0.66(Fy) Mpa Fv = 0.40(Fy) Mpa
TRY SECTION W12X35
137900 Fbx = 227.7 Mpa Fv = 138 Mpa
A = 6645.148 mm2 Sx = 747.25 x 10^3 mm3
L2 = d
Fy = 2770.61 mm Actual: Actual:
Af M V
d = 317.5 mm bf = 166.624 mm fbx =
Sx
fv =
dtw
tw = 7.62 mm tf = 13.208 mm Lc = L1 ; Lu = L2
fbx = 170.83439 Mpa fv = 43.001219 Mpa
SINCE:
COMPACTNESS OF SECTION Fbx > fbx SAFE! Fv > fv SAFE!

Bf/2tf = 6.31 < = 9.152 COMPACT!


Lc > Lb < Lu
170/√𝐹𝑦

d/tw = 41.67 < 1680/√𝐹𝑦 = 90.448 COMPACT! SECTION IS COMPACT!


Therefore: W12X35 SECTION IS SAFE!

118
STEEL BEAM DESIGN
3RD FLOOR - FRAME B & E - 1

REACTIONS:
MOMENTS: CRITICAL LOAD CASE

ML = 56.286 KN-M 20 DL + 0.75LL + 0.525SL+Z


MC = 54.292 KN-M DESIGN MOMENTS:

MR = 91.954 KN-M M1 = 54.292 KN-M

DESIGN SHEAR: M2 = 61.704 KN-M

V = 44.776 KN M3 = 82.7586 KN-M

STEEL PROPERTIES
Fy = 345 MPa
M
Sx =
Lb = 0 m 0.66(Fy)
SOLUTION:
L = 5 m Sx = 363454.55 mm3 Check Actual Bending Check Actual Shear
EFFECTIVE LENGTHS
Allowable: Allowable:
DESIGN SECTION 200(bf)
L1 = √𝐹𝑦
= 1783.21 mm Fbx = 0.66(Fy) Mpa Fv = 0.40(Fy) Mpa
TRY SECTION W12X30
137900 Fbx = 227.7 Mpa Fv = 138 Mpa
A = 5670.9564 mm2 Sx = 632.54 x 10^3 mm3
L2 = d
Fy = 2367.96 mm Actual: Actual:
Af M V
d = 312.42 mm bf = 165.608 mm fbx =
Sx
fv =
dtw
tw = 6.604 mm tf = 11.176 mm Lc = L1 ; Lu = L2
fbx = 130.83536 Mpa fv = 21.701982 Mpa
SINCE:
COMPACTNESS OF SECTION Fbx > fbx SAFE! Fv > fv SAFE!

Bf/2tf = 7.41 < = 9.152 COMPACT!


Lc > Lb < Lu
170/√𝐹𝑦

d/tw = 47.31 < 1680/√𝐹𝑦 = 90.448 COMPACT! SECTION IS COMPACT!


Therefore: W12X30 SECTION IS SAFE!

119
STEEL BEAM DESIGN
3RD FLOOR - FRAME B & E - 2

REACTIONS:
MOMENTS: CRITICAL LOAD CASE

ML = 126.15 KN-M 21 DL + 0.75LL + 0.525SL-Z


MC = 93.23 KN-M DESIGN MOMENTS:

MR = 39.935 KN-M M1 = 93.23 KN-M

DESIGN SHEAR: M2 = 101.53425 KN-M

V = 99.119 KN M3 = 113.535 KN-M

STEEL PROPERTIES
Fy = 345 MPa
M
Sx =
Lb = 0 m 0.66(Fy)
SOLUTION:
L = 6 m Sx = 498616.6 mm3 Check Actual Bending Check Actual Shear
EFFECTIVE LENGTHS
Allowable: Allowable:
DESIGN SECTION 200(bf)
L1 = √𝐹𝑦
= 1783.21 mm Fbx = 0.66(Fy) Mpa Fv = 0.40(Fy) Mpa
TRY SECTION W12X30
137900 Fbx = 227.7 Mpa Fv = 138 Mpa
A = 5670.9564 mm2 Sx = 632.54 x 10^3 mm3
L2 = d
Fy = 2367.96 mm Actual: Actual:
Af M V
d = 312.42 mm bf = 165.608 mm fbx =
Sx
fv =
dtw
tw = 6.604 mm tf = 11.176 mm Lc = L1 ; Lu = L2
fbx = 179.49063 Mpa fv = 48.040887 Mpa
SINCE:
COMPACTNESS OF SECTION Fbx > fbx SAFE! Fv > fv SAFE!

Bf/2tf = 7.41 < = 9.152 COMPACT!


Lc > Lb < Lu
170/√𝐹𝑦

d/tw = 47.31 < 1680/√𝐹𝑦 = 90.448 COMPACT! SECTION IS COMPACT!


Therefore: W12X30 SECTION IS SAFE!

120
STEEL BEAM DESIGN
3RD FLOOR - FRAME A & F - 1

REACTIONS:
MOMENTS: CRITICAL LOAD CASE

ML = 75.979 KN-M 21 DL + 0.75LL + 0.525SL-Z


MC = 36.667 KN-M DESIGN MOMENTS:

MR = 50.023 KN-M M1 = 36.667 KN-M

DESIGN SHEAR: M2 = 42.9671 KN-M

V = 59.516 KN M3 = 68.3811 KN-M

STEEL PROPERTIES
Fy = 345 MPa
M
Sx =
Lb = 0 m 0.66(Fy)
SOLUTION:
L = 5 m Sx = 300312.25 mm3 Check Actual Bending Check Actual Shear
EFFECTIVE LENGTHS
Allowable: Allowable:
DESIGN SECTION 200(bf)
L1 = √𝐹𝑦
= 1783.21 mm Fbx = 0.66(Fy) Mpa Fv = 0.40(Fy) Mpa
TRY SECTION W12X30
137900 Fbx = 227.7 Mpa Fv = 138 Mpa
A = 5670.9564 mm2 Sx = 632.54 x 10^3 mm3
L2 = d
Fy = 2367.96 mm Actual: Actual:
Af M V
d = 312.42 mm bf = 165.608 mm fbx =
Sx
fv =
dtw
tw = 6.604 mm tf = 11.176 mm Lc = L1 ; Lu = L2
fbx = 108.10557 Mpa fv = 28.846149 Mpa
SINCE:
COMPACTNESS OF SECTION Fbx > fbx SAFE! Fv > fv SAFE!

Bf/2tf = 7.41 < = 9.152 COMPACT!


Lc > Lb < Lu
170/√𝐹𝑦

d/tw = 47.31 < 1680/√𝐹𝑦 = 90.448 COMPACT! SECTION IS COMPACT!


Therefore: W12X30 SECTION IS SAFE!

121
STEEL BEAM DESIGN
3RD FLOOR - FRAME A & F - 2

REACTIONS:
MOMENTS: CRITICAL LOAD CASE

ML = 92.058 KN-M 21 DL + 0.75LL + 0.525SL-Z


MC = 62.712 KN-M DESIGN MOMENTS:

MR = 27.53 KN-M M1 = 62.712 KN-M

DESIGN SHEAR: M2 = 68.6914 KN-M

V = 75.864 KN M3 = 82.8522 KN-M

STEEL PROPERTIES
Fy = 345 MPa
M
Sx =
Lb = 0 m 0.66(Fy)
SOLUTION:
L = 6 m Sx = 363865.61 mm3 Check Actual Bending Check Actual Shear
EFFECTIVE LENGTHS
Allowable: Allowable:
DESIGN SECTION 200(bf)
L1 = √𝐹𝑦
= 1783.21 mm Fbx = 0.66(Fy) Mpa Fv = 0.40(Fy) Mpa
TRY SECTION W12X30
137900 Fbx = 227.7 Mpa Fv = 138 Mpa
A = 5670.9564 mm2 Sx = 632.54 x 10^3 mm3
L2 = d
Fy = 2367.96 mm Actual: Actual:
Af M V
d = 312.42 mm bf = 165.608 mm fbx =
Sx
fv =
dtw
tw = 6.604 mm tf = 11.176 mm Lc = L1 ; Lu = L2
fbx = 130.98334 Mpa fv = 36.76968 Mpa
SINCE:
COMPACTNESS OF SECTION Fbx > fbx SAFE! Fv > fv SAFE!

Bf/2tf = 7.41 < = 9.152 COMPACT!


Lc > Lb < Lu
170/√𝐹𝑦

d/tw = 47.31 < 1680/√𝐹𝑦 = 90.448 COMPACT! SECTION IS COMPACT!


Therefore: W12X30 SECTION IS SAFE!

122
STEEL BEAM DESIGN
3RD FLOOR - FRAME 1, 2 & 5

REACTIONS:
MOMENTS: CRITICAL LOAD CASE

ML = 71.453 KN-M 11 DL + 0.7SL-X


MC = 18.125 KN-M DESIGN MOMENTS:

MR = 1.452 KN-M M1 = 18.125 KN-M

DESIGN SHEAR: M2 = 21.77025 KN-M

V = 54.722 KN M3 = 64.3077 KN-M

STEEL PROPERTIES
Fy = 345 MPa
M
Sx =
Lb = 0 m 0.66(Fy)
SOLUTION:
L = 5 m Sx = 282422.92 mm3 Check Actual Bending Check Actual Shear
EFFECTIVE LENGTHS
Allowable: Allowable:
DESIGN SECTION 200(bf)
L1 = = 1914.49 mm Fbx = 0.66(Fy) Mpa Fv = 0.40(Fy) Mpa
TRY SECTION W16X40
√𝐹𝑦
137900 Fbx = 227.7 Mpa Fv = 138 Mpa
A = 7612.888 mm2 Sx = 1060.24 x 10^3 mm3
L2 = d
Fy = 2243.1 mm Actual: Actual:
Af M V
d = 406.4 mm bf = 177.8 mm fbx =
Sx
fv =
dtw
tw = 7.747 mm tf = 12.827 mm Lc = L1 ; Lu = L2
fbx = 60.653909 Mpa fv = 17.380998 Mpa
SINCE:
COMPACTNESS OF SECTION Fbx > fbx SAFE! Fv > fv SAFE!

Bf/2tf = 6.93 < = 9.152 COMPACT!


Lc > Lb < Lu
170/√𝐹𝑦

d/tw = 52.46 < 1680/√𝐹𝑦 = 90.448 COMPACT! SECTION IS COMPACT!


Therefore: W16X40 SECTION IS SAFE!

123
STEEL BEAM DESIGN
3RD FLOOR - FRAME 2 & 5

REACTIONS:
MOMENTS: CRITICAL LOAD CASE

ML = 61.571 KN-M 11 DL + 0.7SL-X


MC = 18.608 KN-M DESIGN MOMENTS:

MR = 10.336 KN-M M1 = 18.608 KN-M

DESIGN SHEAR: M2 = 22.20335 KN-M

V = 50.956 KN M3 = 55.4139 KN-M

STEEL PROPERTIES
Fy = 345 MPa
M
Sx =
Lb = 0 m 0.66(Fy)
SOLUTION:
L = 5 m Sx = 243363.64 mm3 Check Actual Bending Check Actual Shear
EFFECTIVE LENGTHS
Allowable: Allowable:
DESIGN SECTION 200(bf)
L1 = √𝐹𝑦
= 2190.72 mm Fbx = 0.66(Fy) Mpa Fv = 0.40(Fy) Mpa
TRY SECTION W12X40
137900 Fbx = 227.7 Mpa Fv = 138 Mpa
A = 7548.372 mm2 Sx = 843.93 x 10^3 mm3
L2 = d
Fy = 3519.42 mm Actual: Actual:
Af M V
d = 302.26 mm bf = 203.454 mm fbx =
Sx
fv =
dtw
tw = 7.493 mm tf = 13.081 mm Lc = L1 ; Lu = L2
fbx = 65.661725 Mpa fv = 22.498777 Mpa
SINCE:
COMPACTNESS OF SECTION Fbx > fbx SAFE! Fv > fv SAFE!

Bf/2tf = 7.78 < = 9.152 COMPACT!


Lc > Lb < Lu
170/√𝐹𝑦

d/tw = 40.34 < 1680/√𝐹𝑦 = 90.448 COMPACT! SECTION IS COMPACT!


Therefore: W12X40 SECTION IS SAFE!

124
STEEL BEAM DESIGN
3RD FLOOR - FRAME 3 & 4

REACTIONS:
MOMENTS: CRITICAL LOAD CASE

ML = 39.848 KN-M 19 DL + 0.75LL + 0.525SL-X


MC = 12.224 KN-M DESIGN MOMENTS:

MR = 75.752 KN-M M1 = 12.224 KN-M

DESIGN SHEAR: M2 = 18.004 KN-M

V = 38.874 KN M3 = 68.1768 KN-M

STEEL PROPERTIES
Fy = 345 MPa
M
Sx =
Lb = 0 m 0.66(Fy)
SOLUTION:
L = 5 m Sx = 299415.02 mm3 Check Actual Bending Check Actual Shear
EFFECTIVE LENGTHS
Allowable: Allowable:
DESIGN SECTION 200(bf)
L1 = = 1925.43 mm Fbx = 0.66(Fy) Mpa Fv = 0.40(Fy) Mpa
TRY SECTION W16X45 √𝐹𝑦

137900 Fbx = 227.7 Mpa Fv = 138 Mpa


A = 8580.628 mm2 Sx = 1191.34 x 10^3 mm3
L2 = d
Fy = 2508.27 mm Actual: Actual:
Af M V
d = 408.94 mm bf = 178.816 mm fbx =
Sx
fv =
dtw
tw = 8.763 mm tf = 14.351 mm Lc = L1 ; Lu = L2
fbx = 57.226988 Mpa fv = 10.847929 Mpa
SINCE:
COMPACTNESS OF SECTION Fbx > fbx SAFE! Fv > fv SAFE!

Bf/2tf = 6.23 < = 9.152 COMPACT!


Lc > Lb < Lu
170/√𝐹𝑦

d/tw = 46.67 < 1680/√𝐹𝑦 = 90.448 COMPACT! SECTION IS COMPACT!


Therefore: W16X45 SECTION IS SAFE!

125
STEEL BEAM DESIGN
3RD FLOOR - FLOOR BEAM - HALLWAY

REACTIONS:
MOMENTS: CRITICAL LOAD CASE

ML = 0 KN-M 8 DL + LL
MC = 76.906 KN-M DESIGN MOMENTS:

MR = 0 KN-M M1 = 76.906 KN-M

DESIGN SHEAR: M2 = 76.906 KN-M

V = 49.164 KN M3 = 0 KN-M

STEEL PROPERTIES
Fy = 345 MPa
M
Sx =
Lb = 0 m 0.66(Fy)
SOLUTION:
L = 5 m Sx = 337751.43 mm3 Check Actual Bending Check Actual Shear
EFFECTIVE LENGTHS
Allowable: Allowable:
DESIGN SECTION 200(bf)
L1 = √𝐹𝑦
= 1589.02 mm Fbx = 0.66(Fy) Mpa Fv = 0.40(Fy) Mpa
TRY SECTION W10X30
137900 Fbx = 227.7 Mpa Fv = 138 Mpa
A = 5703.2144 mm2 Sx = 530.94 x 10^3 mm3
L2 = d
Fy = 2865.07 mm Actual: Actual:
Af M V
d = 266.7 mm bf = 147.574 mm fbx =
Sx
fv =
dtw
tw = 7.62 mm tf = 12.954 mm Lc = L1 ; Lu = L2
fbx = 0 Mpa fv = 24.191858 Mpa
SINCE:
COMPACTNESS OF SECTION Fbx > fbx SAFE! Fv > fv SAFE!

Bf/2tf = 5.7 < = 9.152 COMPACT!


Lc > Lb < Lu
170/√𝐹𝑦

d/tw = 35 < 1680/√𝐹𝑦 = 90.448 COMPACT! SECTION IS COMPACT!


Therefore: W10X30 SECTION IS SAFE!

126
STEEL BEAM DESIGN
3RD FLOOR - FLOOR BEAM - OFFICE

REACTIONS:
MOMENTS: CRITICAL LOAD CASE

ML = 0 KN-M 8 DL + LL
MC = 56.742 KN-M DESIGN MOMENTS:

MR = 0 KN-M M1 = 56.742 KN-M

DESIGN SHEAR: M2 = 56.742 KN-M

V = 36.273 KN M3 = 0 KN-M

STEEL PROPERTIES
Fy = 345 MPa
M
Sx =
Lb = 0 m 0.66(Fy)
SOLUTION:
L = 5 m Sx = 249196.31 mm3 Check Actual Bending Check Actual Shear
EFFECTIVE LENGTHS
Allowable: Allowable:
DESIGN SECTION 200(bf)
L1 = √𝐹𝑦
= 1572.61 mm Fbx = 0.66(Fy) Mpa Fv = 0.40(Fy) Mpa
TRY SECTION W10X22
137900 Fbx = 227.7 Mpa Fv = 138 Mpa
A = 4187.0884 mm2 Sx = 380.18 x 10^3 mm3
L2 = d
Fy = 2060.39 mm Actual: Actual:
Af M V
d = 259.08 mm bf = 146.05 mm fbx =
Sx
fv =
dtw
tw = 6.096 mm tf = 9.144 mm Lc = L1 ; Lu = L2
fbx = 0 Mpa fv = 22.967019 Mpa
SINCE:
COMPACTNESS OF SECTION Fbx > fbx SAFE! Fv > fv SAFE!

Bf/2tf = 7.99 < = 9.152 COMPACT!


Lc > Lb < Lu
170/√𝐹𝑦

d/tw = 42.5 < 1680/√𝐹𝑦 = 90.448 COMPACT! SECTION IS COMPACT!


Therefore: W10X22 SECTION IS SAFE!

127