Hydrant :-
Discharge/Hydrant : 946.50 lpm.(250 gpm)
Pressure : 4.5 bar.
Extinguishers : -
DCP/CO2 :- Distance= 23m.
Location:
CO2 :- Kitchen, Electrical, Telephone, Boiler, Liquid Storage, Airports, Chemical plants,
Petrochemical Industries, Food storage, Engine Room, Quench Tanks, Spray Booth,
Control Room…
Spacing of Detectors :
Location:
S :- Office, Corridor, Factory, Warehouse,
H :- Kitchen, Pump, Car parking, Garbage, Gas cylinder Rm,
O :- Electrical, Telephone,……
SPRINKLER SYSTEM
DESIGN DATA:
1. FIRST CHECK THE OPERATING AREA……………………..
2. OCCUPANCY HAZARD WHETHER L.H, O.H- (1,2), E.H- (1,2).
3. MIN.FLOW DENSITY:
a) LIGHT HAZARD : 4.1 lpm/sq.mtr.
b) ORDINARY HAZARD-1 : 6.1 lpm/sq.mtr.
c) ORDINARY HAZARD-11 : 8.1 lpm/sq.mtr.
d) EXTRA HAZARD-1 : 12.2 lpm/sq.mtr.
e) EXTRA HAZARD-11 : 16.3 lpm/sq.mtr.
ADD SPR. WATER FLOW RATE WITH - IF AVAILABLE ANY EXTERNAL HYDRANTS OR
INTERNAL HYDRANTS.
EXAMPLE:
1. SPRINKLER OPERATING AREA : CAR PARKING
8. CALC. SPR. WATER FLOW RATE: 71.98 x 12 Nos. = 863.76 lpm. = 228 gpm.
EXAMPLE:
FOR ORDINARY HAZARD –II.
AREA OF OPERATION AS PER NFPA –13 is 139 M2.
IN DRY SYSTEM:
30 % INCREASE IS TO BE CONSIDERED - 181 M2.
COVERAGE OF SPRINKLER – 12 M2.
DENSITY – 8.1 lpm/m2. same as per NFPA 13.
NUMBER OF SPRINKLERS – 16 Nos.
FLOW THROUGH SPRINKLER – COVERAGE AREA x DENSITY
= 12 x 8.1 = 97.2 lpm.
Total Capacity = 97.2 x 16 Nos. of sprinklers.
= 1556 lpm ( 410 gpm) THEORETICAL CALCAULATION.
----------------------------------------------------------------------------------------------------------------------------
OH – I
CAR PARK
OH – II
SHOW ROOM
STORE
SHOPS
FOOD FACTORY
LIBRARY
EH – II
PIPE FACTORY.
LIGHT HAZARD – 4831 M2 .
ORDINARY HAZARD – 4831 M2.
EXTRA HAZARD – 3716 M2.
STORAGE – 3716 M2.
Type – 1 outlet : Delivers foam gently on the liquid surface without submergence of foam or agitation
of liquid surface. ( Porous tube –Moeller tube chamber)
Type – 11 outlet: Does not Delivers foam gently on the liquid surface lessens submergence of foam or
agitation of liquid surface.( Air foam deflector w/chamber)
NFPA : 16 & 16A
Warehouse:
Dimension: 80’ x 50’
Foam conc. : 3% AFFF.
Appl. Rate : 0.16 gpm/ft2 .
NOTE:
NFPA 16 – SYSTEM TO BE DESIGNED FOR THE WHOLE AREA.(OPEN NOZZLE W/ DELUGE
VALVE ) – 10 MIN. DISCHARGE DURATION.
NFPA – 16A – SYSTEM TO BE DESIGNED FOR DEMAND AREA 5,000 FT2
( CLOSED SPRINKLER W/ ALARM CHECK VALVE) – 10 MINUTES DISCHARGE DURATION.
NFPA – 30 – FOAM SYSTEM FOR FLAMABLE LIQUIDS OR SOLID PILE.
APPLICATION RATE : 0.30 GPM/ FT2 OVER 2,000 FT2 .
DISCHARGE DURATION : 15 – 20 MINUTES.
R = 11,385 cfm.
From the equipment list 12,000 cfm is selected.
Hence 170 gpm @ 59 psi is required from data sheet.
Nozzles uses a plate to slice small jets of water & contains a variety of droplet sizes.
Large amount of small droplets have a greater surface area than large droplets. Water
Mist turns to steam, it expands to 1700 times, forcing oxygen away from the flame.
Nozzles:
Spacing between Nozzles.( 2.44 mtrs.)
Distance from Wall & Nozzle – 1.22 mtrs.
Max. distance between Ceiling & Nozzles. – 0.30 mtrs.
CO2 SYSTEM:
CO2 is colorless odourless gas, electrically non conductive & non corrosive inert
clean agent
CO2 is approximately 50% heavier than air & 0.03% by volume present in the
atmosphere.
Certain Conc. Will support human or animal life.
Extinguishes fire by reducing oxygen content & will not support combustion.
Temp. of CO2 from Nozzle -110°F(-78.8°C).
Clean up cost is negligible( completely vaporizes).
STORAGE OF CYLINDERS:
High Pressure – ambient temperature 70°F(21°C) & internal pressure 850 psig.
Low Pressure - ambient temperature 0°F(17.8°C) & internal pressure 300 psig.
PIPING: Black or G.I conforming to ASTM A-53 Seamless or Electric Welded.
TOTAL FLOODING:
Deep-Seated Fire ( Paper, Baled cotton, clothing.. smoldering fire conditions-class
A) are extinguished by prolonged action of a high concentration of carbon dioxide.
Retaining the agent in the protected space affects the fire ability to Re-ignite. After
the design conc. is reached , the conc. shall be maintained for a substantial period of
time, but not less than 20 minutes.
The system shall be designed to achieve 30% conc. in 2 Min. with the remainder
occurring in 7 Min.
Example: L= 13.72m, W= 9.15m, H= 4.57m.
Volume = 573.71 m3.
Flooding factor = 50% - 1.33 kg CO2/ft3.
573.71 x 1.33 = 763.04 kg CO2 . reqd.
For 30% conc. in two min.- 0.043 Lb. CO2/ft3 (0.688 kg CO2/ft3 )factor to
by multiplied. = 573.71 x 0.688
= 394.72 kg required in 2 min.
= 197.36 kg/min. reqd.
Total Discharge = 763.04 / 197.36 = 3.87 Minutes.
Any Leakage in room shall be calculated for 20 min. using the leakage calculation
chart in NFPA-12.
SURFACE FIRE( Flammable liquid, gases, and solids):
They are subject to prompt extinguishment when carbon dioxide is quickly
introduced into the enclosure in sufficient quantity to overcome leakage.
Conc. shall be in no case less than 34% and the agent quantity should be discharged
within one minute.
Volume ( m3) Kg CO2 / m3. Calc. Qty not less than- kg.
Upto 3.96 1.15 ------
3.97 – 14.15 1.07 4.50
14.16 – 45.28 1.01 15.10
45.29 – 127.35 0.90 45.40
127.36 – 1415.0 0.80 113.50
Over 1415.0 0.77 1135.00
Local application system are used for the extinguishment of surface fires in
flammable liquids, gases & solids where the hazard is not enclosed. Since the hazard
is not totally enclosed the qty of CO2 shall be increased by 40%(multiplied by 1.4).
The minimum effective discharge time for agent shall be 30 seconds.
Rate by Area method used to protect two dimensional surfaces.
Dip Tank: L - 0.84m x W - 1.30m = 2 Nozzles are reqd.
Each Nozzle covering 0.85 x 0.85 mtrs.( check the selection chart from NFPA-12)
Flow rate reqd. = 12.7 kg/min.x 2 nos. = 25.4 kg/min.
Total Flow Rate reqd. = 25.4 x 1.4 x .5 = 17.78 kg.
Rate by Volume Method used to protect three dimensional hazard and shall be
based on assumed enclosure volume(2 feet{0.61m} greater than the extreme
dimensions of the specific hazard)
Flow rate shall be = 1 lb/min/ft3(16 kg/min/m3).
Test Cell : L = 3.05m, W = 0.91, H = 0.91m.
Assumed Volume : [3.05+0.61+0.61]x[0.91+0.61+0.61]x[0.91+0.61]
= 4.27x2.13x1.52 m = 13.82m3.
Flow Rate = 16kg/min/m3 = 221.1 kg/min. reqd.
Agent Supply = 221.1x1.4x0.50 = 154.80 kg.
Example:
2. Pit Dimension
As per NFPA 12 : Sec. 3.3.2.3, if part of the hazard is to be protected by Total Flooding,
discharge rate shall be divided by 1.4 and by time taken for Local Application discharge
in minutes.
TOTAL = 1103 = 1576 lbs. (Required)
0.7
Theoretical Calculation:
1" – 320 lbs/min = 320/2.2 = 145.455 kg/min.
Specific gravity = 1.53 ( 0.60)
= 145.455/ 1.53 = 95.068 lpm = 25.117 gpm.
= 25.117 / (13.5 x 0.60) = 3.10
For 3.10 pressure drop ^p = 10 psi = 0.6896 bar
For 10 mtr head of water/ 1.53 = 6.536 mtr.(constant)
= 0.6896 x 6.536 = 4.51 mtr. ~ 15 feet.
Description Flow in Flow in Specific Flow in Flow in Specific Liquid Pressure Equivalent Equivalent
lbs/min kg/min gravity of ltr/min gal/min gravity flow drop head of CO2 length in mtr.
CO2 factor for factor
CO2
11kv 320 145.46 1.53 95.068 25.117 0.60 3.10 0.6896 6.536 4.51
MCC 526 239 1.53 156.3 41.3 0.60 5.097 1.86 6.536 12.17
3.3kv 420.1 190.95 1.53 124.8 32.97 0.60 4.07 1.1724 6.536 7.66
FM 200 SYSTEM
Chemical Properties : CF3CHFCF3( Heptafluoropropane)
Temp. range – 0°C – 54.4°C.
Pipe : Sch.40 Steel pipe – Black or Galvanized.
Fittings : Class 300 lb. Malleable or Ductile Iron fittings.
Agent Reqd.:
Class A( Wood, Paper, Cloth..) – 7% Conc. By volume.
Class B( Flammable liquids.) – ??? Conc. By volume.
Class C( Electrical.) – 7% Conc. By volume.
Class D( Metal.) – Not Applicable.
Fuel
Gasoline – 8.5% Conc. By volume.
Hydraulic Oil – 7.2% Conc. By volume.
Transformer Oil – 8.8% Conc. By volume.
Diesel – 8.2% Conc. By volume.
n- Heptane – 8.0% Conc. By volume.
Ethylene – 10.2% Conc. By volume.
Agent Required
W= V { C }
S {100 – C }
W= Agent Weight in kg.
V = Hazard Volume in m3.
C = Volumetric conc.(% by volume).
S = Specific Vapor Volume in m3/kg.
Agent Required
C = 100 WS.
V + WS
W= Agent Weight in kg.
V = Hazard Volume in m3.
C = Volumetric conc.(% by volume).
S = Specific Vapor Volume in m3/kg.
Temp °C Specific FM200 Wt. Requirements per
Volume Hazard Volume
7% 8% 9%
15 0.1347 0.5589 0.6457 0.7344
20 0.1373 0.5483 0.6335 0.7205
21.1 0.1378 0.5463 0.6315 0.7175
25 0.1399 0.5382 0.6217 0.7071
30 0.1425 0.5284 0.6104 0.6943
CO SYSTEM
Carbon Monoxide gas
It is originated in some combustion's that take place everyday in our lives, such as coal & wood
burners and especially gasses emitted from petrol driven motors.
CO system consists of both detectors and control panel with capability of detecting and
measuring the CO gas concentration(ppm) at any time.
CO Air conc. Symptons Time of inhalation
200 ppm Light headache 2 -3 hrs.
400 ppm Dizzy 2-3 hrs.
800 ppm Faint 45 min.
1600 ppm Dead 20 min.
3200 ppm Dead 5 – 10 min.
6400 ppm Dead 10-15 min.
12800 ppm Dead 1 – 3 min.
Application:
Residential homes.
Workshop
Underground Car parks.
Tunnels…
CO Panel is micro-processor based available in 1,2,3 & 4 zones. Each zone has 12 programmable
ventilation levels and 12 for alarms. Each zone is capable of carrying 14 sensors through
3x1.5mm2 cable.
Power supply : 8 -20 V DC 15 V nominal
Max. Power consumption : 80mA.
Standby consumption : 10mA.
DETECTOR:
Heating period consumption : 138mA.
Cooling period consumption : 22mA.
Normal resolution: 9 ppm at 20°C.
Proposed 7 AH Battery.