FIRE FIGHTING SYSTEM

Hose Reel : NFPA B.S standard


Discharge/Hose : 37.85 lpm. ( 24 lpm ).
Pressure : 2.20 bar ( 4.50 bar).

Hydrant :-
Discharge/Hydrant : 946.50 lpm.(250 gpm)
Pressure : 4.5 bar.

Extinguishers : -
DCP/CO2 :- Distance= 23m.

Location:
CO2 :- Kitchen, Electrical, Telephone, Boiler, Liquid Storage, Airports, Chemical plants,
Petrochemical Industries, Food storage, Engine Room, Quench Tanks, Spray Booth,
Control Room…

DCP :- Machine Room, Airports, Chemical plants, Petrochemical Industries, Service


Stations, Office Building, Vehicles, Farms, Pumping station, Liquid storage, Wood
working, Rolling mill, Warehouse, Garages, Homes……

Auto DCP:- Pump, Garbage, Electrical, Telephone, Transformer,…..

FIRE ALARM SYSTEM

Spacing of Detectors :

S :- Distance= 9m (81 m2 ) ( 4.5m from wall ).


H:- Distance= 7m (50 m2 ) ( 3.5m from wall ).
O:- Distance= 9m (80 m2 ) ( 4.5m from wall ).

Location:
S :- Office, Corridor, Factory, Warehouse,
H :- Kitchen, Pump, Car parking, Garbage, Gas cylinder Rm,
O :- Electrical, Telephone,……
SPRINKLER SYSTEM
DESIGN DATA:
1. FIRST CHECK THE OPERATING AREA……………………..
2. OCCUPANCY HAZARD WHETHER L.H, O.H- (1,2), E.H- (1,2).
3. MIN.FLOW DENSITY:
a) LIGHT HAZARD : 4.1 lpm/sq.mtr.
b) ORDINARY HAZARD-1 : 6.1 lpm/sq.mtr.
c) ORDINARY HAZARD-11 : 8.1 lpm/sq.mtr.
d) EXTRA HAZARD-1 : 12.2 lpm/sq.mtr.
e) EXTRA HAZARD-11 : 16.3 lpm/sq.mtr.

4. DESIGN AREA OF WATER APPLICATION:


a) LIGHT HAZARD : 139.0 sq.mtr.
b) ORDINARY HAZARD-1 : 139.0 sq.mtr.
c) ORDINARY HAZARD-11 : 139.0 sq.mtr.
d) EXTRA HAZARD-1 : 232.0 sq.mtr.
e) EXTRA HAZARD-11 : 232.0 sq.mtr.

5. NUMBER OF ACTIVE SPRINKLERS: NO. OF SPRINKLERS WITHIN THE DESIGN AREA.

6. MAX. AREA/ SPRINKLER: DESIGN AREA / NO. OF ACTIVE SPRINKLERS.

7. FLOW THR. SPRINKLER : MAX. AREA/SPR x FLOW DENSITY.

8. CALC. SPR. WATER FLOW RATE :


FLOW THR. SPRINKLER x NUMBER OF ACTIVE SPRINKLERS.

ADD SPR. WATER FLOW RATE WITH - IF AVAILABLE ANY EXTERNAL HYDRANTS OR
INTERNAL HYDRANTS.
EXAMPLE:
1. SPRINKLER OPERATING AREA : CAR PARKING

2. OCCUPANCY HAZARD -1.

3. MIN.FLOW DENSITY: ORDINARY HAZARD-1 : 6.1 lpm/sq.mtr.

4. DESIGN AREA OF WATER APPLICATION: 142 sq.mtr.

5. NUMBER OF ACTIVE SPRINKLERS: 12 NOS.

6. MAX. AREA/ SPRINKLER: 142 / 12 = 11.8 sq.mtr.

7. FLOW THR. SPRINKLER: 11.8 x 6.1 lpm/sq.mtr = 71.98 lpm.

8. CALC. SPR. WATER FLOW RATE: 71.98 x 12 Nos. = 863.76 lpm. = 228 gpm.

ESFR Sprinkler( Most Remote )


Coverage :- 3.0m x 3.0m .
Pressure : 3.5 – 5.2 bar.
Area of Operation – For 12 sprinklers operating
simultaneously.
DRY PIPE VALVE :

 Only Upright Sprinklers shall be used.


 Horizontal sidewall shall be used .
 Not more than 750 gal. System shall be controlled by one dry pipe valve.
 Gridded dry system shall not be installed.
 Quick opening device shall be installed , where the system exceeds 500 gallons.
 Compressed air shall be restored in the system within 30 min.
 System air pressure as per manfacturer is 1.4 bar.
 Not more than 1000 sprinklers shall be controlled by one preaction valve.
 Water shall be delivered in 60 sec.
 Where system consists of 600 sprinklers or has more than 275 sprinkler in any fire area shall be
controlled by two 6”dry pipe valve.
 Dry system can be manifolded to a deluge valve, the protected area not exceeding 3716 m2.
 Density shall remain the same but 30 % increase in area of operation.

EXAMPLE:
FOR ORDINARY HAZARD –II.
AREA OF OPERATION AS PER NFPA –13 is 139 M2.
IN DRY SYSTEM:
30 % INCREASE IS TO BE CONSIDERED - 181 M2.
COVERAGE OF SPRINKLER – 12 M2.
DENSITY – 8.1 lpm/m2. same as per NFPA 13.
NUMBER OF SPRINKLERS – 16 Nos.
FLOW THROUGH SPRINKLER – COVERAGE AREA x DENSITY
= 12 x 8.1 = 97.2 lpm.
Total Capacity = 97.2 x 16 Nos. of sprinklers.
= 1556 lpm ( 410 gpm) THEORETICAL CALCAULATION.
----------------------------------------------------------------------------------------------------------------------------
OH – I
 CAR PARK
OH – II
 SHOW ROOM
 STORE
 SHOPS
 FOOD FACTORY
 LIBRARY
EH – II
 PIPE FACTORY.
LIGHT HAZARD – 4831 M2 .
ORDINARY HAZARD – 4831 M2.
EXTRA HAZARD – 3716 M2.
STORAGE – 3716 M2.

SUPPORTS FOR STEEL PIPING :


PIPE SIZE MAX.SPACING HANGER ROD dia.
Upto 25mm 2.0 mtrs. 8mm(5/16”)
32-50mm 3.0 mtrs. 10 mm(3/8”)
65-75mm 3.6 mtrs. 12 mm(1/2”)
100-150mm 4.0 mtrs. 16 mm(5/8”)
200-300mm 4.5 mtrs. 20 mm(3/4”)
350mm& over 5.0 mtrs. 22 mm(7/8”)
FOAM SYSTEM:
 Foam is an aggregate of air-filled bubbles formed from aqueous solution and lower in density than
flammable liquids.
 Forms floating blanket on flammable liquid & cooling effect for fuels(prevent air) & (prevents
reignition).
 Galvanised pipe for non-corrosive area.

NFPA-11 – LOW EXPANSION FOAM SYSTEM:

FLOATING ROOF TANK:


Top Seal System Design:
Min. application Rate : 12.20 lpm/m2. & Min discharge Time – 20 min.
Spacing----- i) 305mm Foam Dam – 12.2 mtr. ii) 610 mm Foam Dam – 24.4 mtr.

FIXED ROOF TANK:


Tank Dia. Flash Pt. below 37.8° C Flash Pt. Higher than 37.8° C
Mtrs.
Up to 24 01 01
24 – 36 02 01
36 – 42 03 02
42 – 48 04 02
48 – 54 05 02
54 – 60 06 03
Over 60 06 03
Plus one outlet for add. 465 m2. Plus one outlet for add. 697 m2.

FLASH POINT TYPE 1 TYPE 2


37.8 °C -93.3° C ( 4.10 lpm/m2). 20 30
Below 37.8 ° C ( 4.10 lpm/m2). 30 55
Crude Petroleum ( 4.10 lpm/m2). 30 55

Hose Stream Requirements


Diameter of Largest Tank No. of Hose Streams
Upto 19.5 mtrs. 01
19.5 – 36 mtrs. 02
Over 36 mtrs. 03

Hose Stream Operating time


Diameter of Largest Tank Min. Operating time
Upto 10.5 mtrs. 10 min.
10.5 – 28.5 mtrs. 20 min.
Over 28.5 mtrs. 30 min.

Type – 1 outlet : Delivers foam gently on the liquid surface without submergence of foam or agitation
of liquid surface. ( Porous tube –Moeller tube chamber)
Type – 11 outlet: Does not Delivers foam gently on the liquid surface lessens submergence of foam or
agitation of liquid surface.( Air foam deflector w/chamber)
NFPA : 16 & 16A

1)Deluge Foam Water Sprinkler and Foam Water Spray system


2)Closed Foam Water Sprinkler System.

Warehouse:
Dimension: 80’ x 50’
Foam conc. : 3% AFFF.
Appl. Rate : 0.16 gpm/ft2 .

Flow: 0.16 x 4,000 = 640 gpm.

Discharge Duration: 10 min.(for both 1 & 2)

640gpm x 10 = 6400 gallons.(water requirement)

Foam reqd. shall be for 3% = 6400 x 0.03 = 192 gallons of foam.

No. of sprinklers = 40 nos.

Ratio proportioner size shall be for 640 gpm.


4“ Ratio proportioner flow rate is 200 – 1600 gpm.

NOTE:
NFPA 16 – SYSTEM TO BE DESIGNED FOR THE WHOLE AREA.(OPEN NOZZLE W/ DELUGE
VALVE ) – 10 MIN. DISCHARGE DURATION.
NFPA – 16A – SYSTEM TO BE DESIGNED FOR DEMAND AREA 5,000 FT2
( CLOSED SPRINKLER W/ ALARM CHECK VALVE) – 10 MINUTES DISCHARGE DURATION.
NFPA – 30 – FOAM SYSTEM FOR FLAMABLE LIQUIDS OR SOLID PILE.
APPLICATION RATE : 0.30 GPM/ FT2 OVER 2,000 FT2 .
DISCHARGE DURATION : 15 – 20 MINUTES.

HIGH EXPANSION FOAM SYSTEM:


ROOM SIZE: L=100 ft, W=30 ft, HT = 7 ft
VOLUME = 100 x 30 x 9(2ft extra has to be considered always)
= 27,000 ft3.
FILL TIME = 3 MINUTES.
FORMULA:
R = RATE OF DICHARGE = (V/T) x Cn x Cl
Cn= 1.15 (constant)
Cl = 1.1 (slight leakage) constant.
T = 3 Minutes.
V = 27,000 ft3 .

R = 11,385 cfm.
From the equipment list 12,000 cfm is selected.
Hence 170 gpm @ 59 psi is required from data sheet.

FOR 170 gpm – 3” proportioner is selected.


Foam Bladder tank capacity:
170 gpm x 0.02(2% mix ratio) x 15 min. = 51 gallons of Foam( reqd.)
WATER MIST SYSTEM

High pressure system: 500 psi( 34.5 bar) or greater.


Intermediate Pressure system : Greater than 12.1 bar less than 34.5 bar.
Local Application system : Discharge on object.
Low Pressure system : 12.1 bar or less.

Max. pressure designed at 54°C.

Fike requirement : Protection space upto 260 m3.


Each nozzle – 2.1 gpm @ 21 bar.
Protecting area of nozzle – 2.4 mtr x 2.4 mtr. w/ ceiling ht. of 4.9 mtr.
Available in 70 & 107 Gallons.
70 gallons – 6500 ft3.( 6 nozzles).
107 gallons – 9,175 ft3 ( 9 nozzles).

Nozzles uses a plate to slice small jets of water & contains a variety of droplet sizes.
Large amount of small droplets have a greater surface area than large droplets. Water
Mist turns to steam, it expands to 1700 times, forcing oxygen away from the flame.

Time for protection – 10 min.( Machinery space).


Time for protection – 20 min.( Gas Turbine Generator).

Nitrogen cylinders charged to 128 bar.

34 bar is set to burst the safety disc water container.


Pipe : G.I ASTM A 795 Seamless black or G.I.

Nozzles:
 Spacing between Nozzles.( 2.44 mtrs.)
 Distance from Wall & Nozzle – 1.22 mtrs.
 Max. distance between Ceiling & Nozzles. – 0.30 mtrs.
CO2 SYSTEM:

 CO2 is colorless odourless gas, electrically non conductive & non corrosive inert
clean agent
 CO2 is approximately 50% heavier than air & 0.03% by volume present in the
atmosphere.
 Certain Conc. Will support human or animal life.
 Extinguishes fire by reducing oxygen content & will not support combustion.
 Temp. of CO2 from Nozzle -110°F(-78.8°C).
 Clean up cost is negligible( completely vaporizes).

STORAGE OF CYLINDERS:

High Pressure – ambient temperature 70°F(21°C) & internal pressure 850 psig.
Low Pressure - ambient temperature 0°F(17.8°C) & internal pressure 300 psig.
PIPING: Black or G.I conforming to ASTM A-53 Seamless or Electric Welded.
TOTAL FLOODING:
Deep-Seated Fire ( Paper, Baled cotton, clothing.. smoldering fire conditions-class
A) are extinguished by prolonged action of a high concentration of carbon dioxide.
Retaining the agent in the protected space affects the fire ability to Re-ignite. After
the design conc. is reached , the conc. shall be maintained for a substantial period of
time, but not less than 20 minutes.

Design Conc. Lb. CO2/ft3 kg CO2/ft3 Specific Hazard


50% 0.100 1.60 Dry electrical hazards in general
(Spaces 0 – 2000ft3/ 156.6 m3)
50% 0.083 1.33 Dry electrical hazards
(Spaces 0 – 2000ft3/ 156.6 m3)
65% 0.125 2.00 Record or Bulk paper storage, ducts
& covered trenches.
75% 0.166 2.66 Fur storage vaults, dust collectors. ..

The system shall be designed to achieve 30% conc. in 2 Min. with the remainder
occurring in 7 Min.
Example: L= 13.72m, W= 9.15m, H= 4.57m.
Volume = 573.71 m3.
Flooding factor = 50% - 1.33 kg CO2/ft3.
573.71 x 1.33 = 763.04 kg CO2 . reqd.
For 30% conc. in two min.- 0.043 Lb. CO2/ft3 (0.688 kg CO2/ft3 )factor to
by multiplied. = 573.71 x 0.688
= 394.72 kg required in 2 min.
= 197.36 kg/min. reqd.
Total Discharge = 763.04 / 197.36 = 3.87 Minutes.
Any Leakage in room shall be calculated for 20 min. using the leakage calculation
chart in NFPA-12.
SURFACE FIRE( Flammable liquid, gases, and solids):
They are subject to prompt extinguishment when carbon dioxide is quickly
introduced into the enclosure in sufficient quantity to overcome leakage.
Conc. shall be in no case less than 34% and the agent quantity should be discharged
within one minute.

Volume ( m3) Kg CO2 / m3. Calc. Qty not less than- kg.
Upto 3.96 1.15 ------
3.97 – 14.15 1.07 4.50
14.16 – 45.28 1.01 15.10
45.29 – 127.35 0.90 45.40
127.36 – 1415.0 0.80 113.50
Over 1415.0 0.77 1135.00

Example: L= 13.72m, W= 9.15m, H= 4.57m.


Volume = 573.71 m3.
Flooding factor = 34% - 0.80 kg CO2/ft3.
573.71 x 0.80 = 459.00 kg CO2 . reqd.
For more Design conc. for common liquids and gases refer to conc. chart shown in
NFPA-12 which shall be multiplied with the Material Conversion factor.

LOCAL APPLICATION SYSTEM:

Local application system are used for the extinguishment of surface fires in
flammable liquids, gases & solids where the hazard is not enclosed. Since the hazard
is not totally enclosed the qty of CO2 shall be increased by 40%(multiplied by 1.4).
The minimum effective discharge time for agent shall be 30 seconds.
 Rate by Area method used to protect two dimensional surfaces.
Dip Tank: L - 0.84m x W - 1.30m = 2 Nozzles are reqd.
Each Nozzle covering 0.85 x 0.85 mtrs.( check the selection chart from NFPA-12)
Flow rate reqd. = 12.7 kg/min.x 2 nos. = 25.4 kg/min.
Total Flow Rate reqd. = 25.4 x 1.4 x .5 = 17.78 kg.
 Rate by Volume Method used to protect three dimensional hazard and shall be
based on assumed enclosure volume(2 feet{0.61m} greater than the extreme
dimensions of the specific hazard)
Flow rate shall be = 1 lb/min/ft3(16 kg/min/m3).
Test Cell : L = 3.05m, W = 0.91, H = 0.91m.
Assumed Volume : [3.05+0.61+0.61]x[0.91+0.61+0.61]x[0.91+0.61]
= 4.27x2.13x1.52 m = 13.82m3.
Flow Rate = 16kg/min/m3 = 221.1 kg/min. reqd.
Agent Supply = 221.1x1.4x0.50 = 154.80 kg.
Example:

TOTAL FLOOD - SURFACE DESIGN (AS PER NFPA 12 - SEC. A2.2.3)

1. Room Dimension : 8.85 X 6.4 X 8.98 mtr.


: 29.04’ X 21.0’ X 29.46’
Volume : 17965.89 ft3
Design Concentration : 34 %
: 0.050 lbs/min./ ft3
CO2 Required : 17965.89 X 0.050
: 899 lbs
: 408 kg.

2. Pit Dimension

A) 8.85 X 2.35 X 2.83 mtr. = 29.04’ x 7.7’ x 9.29’


B) 8.85 x 2.25 x 2.83 mtr. = 29.04’ X 7.39’ X 9.29’
Volume : 2077.32 ft3 + 1993.69 ft3
: 4071.0 ft3
Design Concentration : 34 %
: 4071.0 X 0.050 = 204 lbs
= 92.7kg.
TOTAL FLOOD PORTION

 For Room : 899 Lbs


 For Pit : 204 lbs.
Total : 1103 lbs.

As per NFPA 12 : Sec. 3.3.2.3, if part of the hazard is to be protected by Total Flooding,
discharge rate shall be divided by 1.4 and by time taken for Local Application discharge
in minutes.
TOTAL = 1103 = 1576 lbs. (Required)
0.7

LOCAL APPLICATION PORTION

Exhaust Fan Dimension : 1.2 X 1.2 X 1.3 Mtr.


: 3.94’ X 3.94’ X 4.27’
Volume : 3.94’ x 3.94’ x (4.27’+2.0’)
refer to NFPA 12 [3-5.3.1]
Perimeter area = 2(4.27’ x 3.94’) + 2(3.94’ x 3.94’)
= 2 x 16.82 + 2 x 15.52
= 33.64 + 31.04
= 64.68 ft2
Open area = 3.94’ X 3.94’ = 15.52 ft2.
% Open Area = 15.52 = 0.24%
64.68

Flow Rate Required = (0.24 X 0.75) + 0.25 = 0.43 lbs/min/ft3

Agent Supply = 97.33 X 0.43 = 41.85 lbs X 1.4 X 0.5


= 29.3 lbs
= 30 lbs (Reqd)

LOCAL APPLICATION PORTION

Louver For Vent System


V = 1.5 X 6.0 X 1.0 mtr.
= 4.92’ X 19.69’ X (3.28’ + 2.0’)
= 511.50 ft3
Perimeter Area = 2(3.28’ X 4.92’) + 2(4.92’ X 19.69)
= 32.28 + 193.74
= 226.02 ft2
Open Area = 4.92’ x 19.69’ = 96.87 ft2

% Open Area = 96.87 226.02 = 0.43 (43%)

Flow Rate Required = (0.43 X 0.75) + 0.25 = 0.57 lbs/min/ ft3

Agent Supply = 511.50 ft3 x 0.57 = 291.56


= 292 lbs
= 292 X 1.4 X 0.5
= 205 lbs (Reqd)

TOTAL CO2 REQUIRED :-


i. For Room +
ii. For Pit : 1576 lbs
iii. For Fan : 30 lbs
iv. For Louver : 205 lbs.
: 1811 lbs
2000 lbs Stored

Theoretical Calculation:
1" – 320 lbs/min = 320/2.2 = 145.455 kg/min.
Specific gravity = 1.53 ( 0.60)
= 145.455/ 1.53 = 95.068 lpm = 25.117 gpm.
= 25.117 / (13.5 x 0.60) = 3.10
For 3.10 pressure drop ^p = 10 psi = 0.6896 bar
For 10 mtr head of water/ 1.53 = 6.536 mtr.(constant)
= 0.6896 x 6.536 = 4.51 mtr. ~ 15 feet.
Description Flow in Flow in Specific Flow in Flow in Specific Liquid Pressure Equivalent Equivalent
lbs/min kg/min gravity of ltr/min gal/min gravity flow drop head of CO2 length in mtr.
CO2 factor for factor
CO2
11kv 320 145.46 1.53 95.068 25.117 0.60 3.10 0.6896 6.536 4.51
MCC 526 239 1.53 156.3 41.3 0.60 5.097 1.86 6.536 12.17
3.3kv 420.1 190.95 1.53 124.8 32.97 0.60 4.07 1.1724 6.536 7.66

FM 200 SYSTEM
Chemical Properties : CF3CHFCF3( Heptafluoropropane)
Temp. range – 0°C – 54.4°C.
Pipe : Sch.40 Steel pipe – Black or Galvanized.
Fittings : Class 300 lb. Malleable or Ductile Iron fittings.
Agent Reqd.:
Class A( Wood, Paper, Cloth..) – 7% Conc. By volume.
Class B( Flammable liquids.) – ??? Conc. By volume.
Class C( Electrical.) – 7% Conc. By volume.
Class D( Metal.) – Not Applicable.
Fuel
Gasoline – 8.5% Conc. By volume.
Hydraulic Oil – 7.2% Conc. By volume.
Transformer Oil – 8.8% Conc. By volume.
Diesel – 8.2% Conc. By volume.
n- Heptane – 8.0% Conc. By volume.
Ethylene – 10.2% Conc. By volume.

Agent Required
W= V { C }
S {100 – C }
W= Agent Weight in kg.
V = Hazard Volume in m3.
C = Volumetric conc.(% by volume).
S = Specific Vapor Volume in m3/kg.

Agent Required
C = 100 WS.
V + WS
W= Agent Weight in kg.
V = Hazard Volume in m3.
C = Volumetric conc.(% by volume).
S = Specific Vapor Volume in m3/kg.
Temp °C Specific FM200 Wt. Requirements per
Volume Hazard Volume
7% 8% 9%
15 0.1347 0.5589 0.6457 0.7344
20 0.1373 0.5483 0.6335 0.7205
21.1 0.1378 0.5463 0.6315 0.7175
25 0.1399 0.5382 0.6217 0.7071
30 0.1425 0.5284 0.6104 0.6943

NOEL: No Observed Effect Level= 9%.


LOAEL: Lowest Observable Adverse Effect Level= 10.5%.
Nozzle Flow Rate = 7.7 – 9.1 kg/sec./Nozzle.
Discharge Time: Max. Time – 10 seconds.
Min. Time - 6 seconds.
Minimum Nozzle Pressure – 55 psig.
Liquid arrival Time within 1.0 Sec. & Runout Time within 2.10 Sec.
Total Agent before 1st Tee – 40% before & "Must" be 10% Minimum.
Container( fill density range)

Container Size Minimum Maximum


4.5 kg(10 lbs) 3.6 4.5
9.1 kg(20 lbs) 5.4 9.5
15.9 kg(35 lbs) 10.0 17.2
27.2 kg(60 lbs) 16.8 29.0
45.3 kg(100 lbs) 26.3 45.4
56.7i kg(125i lbs) 33.1 57.6
97.5i kg(215i lbs) 58.1 101.2
97.5 kg(215 lbs) 55.8 97.5
170 kg(375 lbs) 97.5 170.1
295 kg(650 lbs) 168.7 294.8
454 kg(1000 lbs) 260.0 454.5

Nozzle Area Coverage: Ceiling ht/0.3 to 3.05 mtrs.


180°(13.92 m Radius) , 360°(9.04 m Radius).

Nozzle Area Coverage: Ceiling ht Below 0.30 mtrs.


180°(7.62 m Radius) , 360°(4.57 m Radius).

Nominal Pipe Size Nozzle Discharge Rate Piping Network


Min. Flow Max. Flow Min. Flow Min. Flow
Rate kg/sec. Rate kg/sec. Rate kg/sec. Rate kg/sec.
10mm 0.32 0.91 0.32 0.91
15mm 0.45 1.54 0.45 1.54
20mm 0.91 2.72 0.91 2.72
25mm 1.54 3.86 1.54 3.86
32mm 2.53 5.90 2.53 5.90
40mm 3.81 8.85 3.81 8.85
50mm 5.90 14.97 5.90 14.97
80mm ----- ----- 15.00 43.10
100mm ----- ----- 26.31 57.61

Enclosure: 12.19 x 9.15 x 3.0 mtrs.


= 340 m3.
7% @ 21.1°C x 0.546
186.0 kg.
Nozzle reqd. Flow Rate = 186kg/10 sec. = 18.6 kg/sec.

FM 200 Calculation Factors


CONC. Kg/m3.
7.00 % 0.546
7.20 % 0.563
7.50 % 0.589
7.75 % 0.621
8.00 % 0.631
8.25 % 0.653
8.50 % 0.674
8.75 % 0.696
9.00 % 0.718
9.25 % 0.741
9.50 % 0.762
9.75 % 0.783
10.0 % 0.806

CO SYSTEM
Carbon Monoxide gas
It is originated in some combustion's that take place everyday in our lives, such as coal & wood
burners and especially gasses emitted from petrol driven motors.
CO system consists of both detectors and control panel with capability of detecting and
measuring the CO gas concentration(ppm) at any time.
CO Air conc. Symptons Time of inhalation
200 ppm Light headache 2 -3 hrs.
400 ppm Dizzy 2-3 hrs.
800 ppm Faint 45 min.
1600 ppm Dead 20 min.
3200 ppm Dead 5 – 10 min.
6400 ppm Dead 10-15 min.
12800 ppm Dead 1 – 3 min.
Application:
 Residential homes.
 Workshop
 Underground Car parks.
 Tunnels…
CO Panel is micro-processor based available in 1,2,3 & 4 zones. Each zone has 12 programmable
ventilation levels and 12 for alarms. Each zone is capable of carrying 14 sensors through
3x1.5mm2 cable.
 Power supply : 8 -20 V DC 15 V nominal
Max. Power consumption : 80mA.
 Standby consumption : 10mA.
DETECTOR:
 Heating period consumption : 138mA.
 Cooling period consumption : 22mA.
 Normal resolution: 9 ppm at 20°C.

 Nominal Range: from 0 to 300 ppm.


 No. of detectors : 14 x 4 zones = 56 detectors.
 Ventilation & Alarm lvls. = 12 programmable lvls in 10 ppm steps from 20 – 100 ppm
& 50 steps from 100 – 250.
 Memory = 300 events.
 Max. cable length = 150 mtrs between central unit and the detectors.
 Response speed = 150 seconds.
 Mounting: Wall & ceiling mounting ( about 2 mtr height).
 Coverage : 300m2.
PROGRAMMING :
1. Ventilation level.
2. Alarm level.
3. Alarm memories.
4. Ventilation Alarm.
5. Disconnection memories.
6. Calibration.
7. Lines test.
BATTERY CALCULATION:
Description Device Draw(mA) Qty 24 hrs(AH)x 0.024
FACP 74 1 1.78
FARP 65 1 1.56
ISD 0.30 144 1.04
HD 0.20 08 0.04
Isolator Module 0.45 10 0.11
Control Module 0.20 12 0.06
SUB-TOTAL 4.59
5 Min (AH)
Bell 22 26 0.05
Sounder 256 03 0.07
SUB-TOTAL 0.12
GRAND TOTAL 4.71

Proposed 7 AH Battery.