Você está na página 1de 5

test report

Test Object - Device Settings

Substation/Bay:
Substation: Substation address:

Bay: Bay address:

Device:
Name/description: Manufacturer:
Device type: Device address:
Serial/model number:

Test Equipment
Type Serial Number

Test Module

Test Results

Title: Checking of Drop off Voltage at Red Phase by Decreasing Voltage

Fault Calculator:
Table Inputmode Parameters (All values are secondary)
Direct V L1-E 38.60 V 0.00 ° 50.000 Hz
V L2-E 63.50 V -120.00 ° 50.000 Hz
V L3-E 63.50 V 120.00 ° 50.000 Hz
I L1 0.000 A 0.00 ° 50.000 Hz
I L2 0.000 A -120.00 ° 50.000 Hz
I L3 0.000 A 120.00 ° 50.000 Hz

Generator Settings
V L1-E 38.600V 0.00° +90°
V L2-E 63.500V -120.00°
V L3-E
V L3-E 63.500V 120.00°
I L1 0.000A 0.00°
V L1-E
I L2 0.000A -120.00° 180° 0°
I L3 0.000A 120.00°
V L2-E

80.0 V -90° 32.0 A

Binary Inputs
Trip Start Overload
0->1 1->0 0
0.189s n/a

Comment
Rated Voltage : 110V, 50 Hz

Title: Checking of Pick Up Voltage at Red Phase by Increasing Voltage

Fault Calculator:
Table Inputmode Parameters (All values are secondary)
Direct V L1-E 52.90 V 0.00 ° 50.000 Hz
V L2-E 63.50 V -120.00 ° 50.000 Hz
V L3-E 63.50 V 120.00 ° 50.000 Hz
I L1 0.000 A 0.00 ° 50.000 Hz
I L2 0.000 A -120.00 ° 50.000 Hz
I L3 0.000 A 120.00 ° 50.000 Hz

Generator Settings
V L1-E 52.900V 0.00° +90°
V L2-E 63.500V -120.00°
V L3-E
V L3-E 63.500V 120.00°
I L1 0.000A 0.00°
V L1-E
I L2 0.000A -120.00° 180° 0°
I L3 0.000A 120.00°
V L2-E

80.0 V -90° 32.0 A

Binary Inputs
Trip Start Overload
1->0 1->0 0
0.148s n/a

Comment
Rated Voltage : 110V, 50 Hz

Title: Checking of Drop off Voltage at Yellow Phase by Decreasing Voltage

Fault Calculator:
Table Inputmode Parameters (All values are secondary)
Direct V L1-E 63.50 V 0.00 ° 50.000 Hz
V L2-E 37.60 V -120.00 ° 50.000 Hz
V L3-E 63.50 V 120.00 ° 50.000 Hz
I L1 0.000 A 0.00 ° 50.000 Hz
I L2 0.000 A -120.00 ° 50.000 Hz
I L3 0.000 A 120.00 ° 50.000 Hz
Generator Settings
V L1-E 63.500V 0.00° +90°
V L2-E 37.600V -120.00°
V L3-E
V L3-E 63.500V 120.00°
I L1 0.000A 0.00°
V L1-E
I L2 0.000A -120.00° 180° 0°
I L3 0.000A 120.00° V L2-E

80.0 V -90° 32.0 A

Binary Inputs
Trip Start Overload
0->1 1->0 0
0.237s n/a

Comment
Rated Voltage : 110V, 50 Hz

Title: Checking of Pick Up Voltage at Yellow Phase by Increasing Voltage

Fault Calculator:
Table Inputmode Parameters (All values are secondary)
Direct V L1-E 63.50 V 0.00 ° 50.000 Hz
V L2-E 51.20 V -120.00 ° 50.000 Hz
V L3-E 63.50 V 120.00 ° 50.000 Hz
I L1 0.000 A 0.00 ° 50.000 Hz
I L2 0.000 A -120.00 ° 50.000 Hz
I L3 0.000 A 120.00 ° 50.000 Hz

Generator Settings
V L1-E 63.500V 0.00° +90°
V L2-E 51.200V -120.00°
V L3-E
V L3-E 63.500V 120.00°
I L1 0.000A 0.00°
V L1-E
I L2 0.000A -120.00° 180° 0°
I L3 0.000A 120.00°
V L2-E

80.0 V -90° 32.0 A

Binary Inputs
Trip Start Overload
1->0 1->0 0
0.114s n/a

Comment
Rated Voltage : 110V, 50 Hz

Title: Checking of Drop off Voltage at Blue Phase by Decreasing Voltage

Fault Calculator:
Table Inputmode Parameters (All values are secondary)
Direct V L1-E 63.50 V 0.00 ° 50.000 Hz
V L2-E 63.50 V -120.00 ° 50.000 Hz
V L3-E 38.80 V 120.00 ° 50.000 Hz
I L1 0.000 A 0.00 ° 50.000 Hz
I L2 0.000 A -120.00 ° 50.000 Hz
I L3 0.000 A 120.00 ° 50.000 Hz

Generator Settings
V L1-E 63.500V 0.00° +90°
V L2-E 63.500V -120.00°
V L3-E 38.800V 120.00°
I L1 0.000A 0.00° V L3-E
V L1-E
I L2 0.000A -120.00° 180° 0°
I L3 0.000A 120.00°
V L2-E

80.0 V -90° 32.0 A

Binary Inputs
Trip Start Overload
0->1 1->0 1->0
0.083s n/a n/a

Comment
Rated Voltage : 110V, 50 Hz

Title: Checking of Pick Up Voltage at Blue Phase by Increasing Voltage

Fault Calculator:
Table Inputmode Parameters (All values are secondary)
Direct V L1-E 63.50 V 0.00 ° 50.000 Hz
V L2-E 63.50 V -120.00 ° 50.000 Hz
V L3-E 53.00 V 120.00 ° 50.000 Hz
I L1 0.000 A 0.00 ° 50.000 Hz
I L2 0.000 A -120.00 ° 50.000 Hz
I L3 0.000 A 120.00 ° 50.000 Hz

Generator Settings
V L1-E 63.500V 0.00° +90°
V L2-E 63.500V -120.00°
V L3-E 53.000V 120.00° V L3-E
I L1 0.000A 0.00°
V L1-E
I L2 0.000A -120.00° 180° 0°
I L3 0.000A 120.00°
V L2-E

80.0 V -90° 32.0 A

Binary Inputs
Trip Start Overload
1->0 1->0 0
0.125s n/a

Comment
Rated Voltage : 110V, 50 Hz

Title: Checking of Typical Operating Time


Fault Calculator:
Table Inputmode Parameters (All values are secondary)
Direct V L1-E 63.50 V 0.00 ° 50.000 Hz
V L2-E 63.50 V -120.00 ° 50.000 Hz
V L3-E 63.50 V 120.00 ° 50.000 Hz
I L1 0.000 A 0.00 ° 50.000 Hz
I L2 0.000 A -120.00 ° 50.000 Hz
I L3 0.000 A 120.00 ° 50.000 Hz

Generator Settings
V L1-E 63.500V 0.00° +90°
V L2-E 63.500V -120.00°
V L3-E
V L3-E 63.500V 120.00°
I L1 0.000A 0.00°
V L1-E
I L2 0.000A -120.00° 180° 0°
I L3 0.000A 120.00°
V L2-E

80.0 V -90° 32.0 A

Binary Inputs
Trip Start Overload
1->0 1->0 1->0
0.057s n/a n/a

Comment
At Rated Voltage

Summary
7 tests passed, 0 tests failed, 0 tests not assessed 100.00% passed
Test passed (manually assessed!)