Você está na página 1de 6

EARTH RESISTANCE STATUS OF S/Stns.

Earth resistance of (in ohm)

S. Name of S/Stn. LA's


Name of T/F HV- LV- Earth
No. T/F NCT NCT mat
R Y B

1 132 kv Malikpur T-1 0.03 0.03 0.02 0.02 0.02 0.02 0.03
T-2 0.03 0.02 0.03 0.02 0.02 0.02 0.03
T-3 0.03 0.02 0.02 0.08 0.08 0.08 0.03
T-4 0.02 0.03 0.03 0.03 0.03 0.03 0.02
2 132 KV Ismailabad T-1 0.04 0.05 0.06 0.1 0.1 0.1 0.04
T-2 0.03 0.05 0.04 0.02 0.02 0.02 0.03
T-3 0.07 0.01 0.07 0.04 0.04 0.04 0.07
3 132 KV Bhore T-1 0.07 0.06 0.07 0.05 0.06 0.05 0.07
T-2 0.07 0.08 0.07 0.06 0.05 0.05 0.07
T-3 0.06 0.07 0.06 0.06 0.07 0.06 0.06
T-4 0.05 0.06 0.06 0.07 0.08 0.03 0.05
4 220 KV Pehowa T-1 0.24 0.39
T-2 0.27 0.41
T-3 0.32 0.6 0.45
T-4 0.4 0.6 0.5
T-5 0.4 0.7 0.6
T-6 0.2 0.5 0.4
T-7 0.3 0.54 0.4
T-8 0.3 0.6 0.5
T-9 0.32 0.37
5 132 KV Bodhni T-1 0.04 0.03 0.04 0.03 0.04
T-2 0.04 0.04 0.03 0.03 0.03
6 132 KV Bhusthla T-1 (20/25 MVA, 132/33 KV) 0.01/0.02 0.02 0.01 0.02 0.01 0.02
T-2 (20/25 MVA, 132/33 KV) 0.01/0.02 0.02 0.01 0.02 0.03 0.01
7 132 KV Dhand T-1 (10/16 MVA, 132/11 KV) 0.04/0.02 0.02 0.03 0.02 0.03 0.02
T-2 (16/ 20 MVA, 132/11 KV) 0.02/0.03 0.04 0.02 0.02 0.02 0.03
T-3 (16/ 20 MVA, 132/ 33 KV) 0.02/0.03 0.04 0.03 0.02 0.03 0.03
T-4 (40/50 MVA, 132/33 KV) 0.02/0.03 0.03 0.03 0.02 0.02 0.02
8 132 KV Adhon T-1 (20/25 MVA, 132/33 KV) 0.02/0.01 0.01 0.01 0.01 0.02 0.02
T-2 (40/50 MVA, 132/33 KV) 0.02/0.01 0.01 0.01 0.01 0.02 0.02
T-3 (20/25 MVA, 132/33 KV) 0.02 0.02 0.02 0.01 0.02 0.02
9 132 KV Kirmich T-1 (20/25 MVA, 132/33 KV) 0.02 0.03 0.07 0.03 0.08 0.05
T-3 (40/50 MVA, 132/33 KV) 0.02 0.05 0.03 0.04 0.03 0.02
10 66 KV Pilpi T-1 (16/ 20 MVA, 66/11 LV) 0.02 0.03 0.04 0.02 0.05 0.03
T-2 (16/ 20 MVA, 66/11 LV) 0.03 0.02 0.03 0.05 0.05 0.04
11 132 KV Pipli T-1 (10/16 MVA, 132/11 KV) 0.03 0.02 0.01 0.02 0.03 0.02
T-2 (40/50 MVA, 132/33 KV) 0.02 0.03 0.05 0.02 0.02 0.08
T-3 (16/20 MVA, 132/33 KV) 0.04 0.06 0.05 0.08 0.07 0.07
12 132 KV Lukhi T-1 (20/25 MVA, 132/33 KV) 0.2/0.02 0.09 0.04 0.01 0.02 0.03
T-2 (20/25 MVA, 132/33 KV) 0.02/0.03 0.02 0.02 0.02 0.03 0.02
13 220 KV Dhurala T-1 (100 MVA, 220/132 KV) 1.01/0.02 0.01 0.01 0.02 0.02
T-2 (100 MVA, 220/132 KV) 0.02/0.03 0.02 0.03 0.02 0.02
T-3 (10/16 MVA, 132/11 KV) 0.03/0.02 0.01 0.01 0.02 0.03 0.02
Earth Remarks if
resistance earth
within limit resistance
or Not not in limit
CAPACITOR BANK STATUS OF S/Stns.

No. of
Installed Working defective
S. capacity Working
Name of S/Stn. Name of T/F capacity Remarks if not working with reason
No. capacitor status
(MVAR) (MVAR) cells
1 132 kv Malikpur T-1 6 6 0
T-2 7.2 7.2 0
T-3 6 6 0
2 132 KV Ismailabad T-1 6 6
T-2 9 7.2 CT ratio constraint
T-3 14.4 14.4 0
3 132 KV Bhore T-1 6.3 6.3 0
T-2 7.2 7.2 0
T-3 7.2 7.2 0
T-4 6 6 0
4 220 KV Pehowa T-3 6 6 0
T-4 6 6 0
T-5 3.6 3.6 0
T-6 Not Installed
T-7 7.2 7.2 0
T-8
Not Installed 20 MVAR to be installed by Power Grid
mobile capacitor bank.
5 132 KV Bodhni T-1 7.2 7.2 0
T-2 7.2 7.2 0
6 132 KV Bhusthla T-1 (20/25 MVA, 132/33 KV) 7.2 7.2 0 OK
T-2 (20/25 MVA, 132/33 KV) 7.2 7.2 0 OK
7 132 KV Dhand T-1 (10/16 MVA, 132/11 KV) 6 6 0 OK
T-2 (16/ 20 MVA, 132/11 KV) 6 6 0 OK
T-3 (16/ 20 MVA, 132/ 33 KV) Not Installed
T-4 (40/50 MVA, 132/33 KV) Not Installed
8 132 KV Adhon T-1 (20/25 MVA, 132/33 KV) 7.2 7.2 0 OK
T-2 (40/50 MVA, 132/33 KV) 7.2 7.2 0 Capacity of capacitor bank has not been
OK provided as per rated capacity of T/F.
T-3 (20/25 MVA, 132/33 KV) 14.4 14.4 0 OK
9 132 KV Kirmich T-1 (20/25 MVA, 132/33 KV) 7.2 7.2 0 OK
T-3 (40/50 MVA, 132/33 KV) Not Installed
10 66 KV Pilpi T-1 (16/ 20 MVA, 66/11 LV) 6 6 0 OK
T-2 (16/ 20 MVA, 66/11 LV) 3 3 0 OK
11 132 KV Pipli T-1 (10/16 MVA, 132/11 KV) 6 6 0 OK

T-2 (40/50 MVA, 132/33 KV) 7.2 7.2 0 OK Capacity of capacitor bank has not been
provided as per rated capacity of T/F.
T-3 (16/20 MVA, 132/33 KV) 7.2 7.2 0 OK
12 132 KV Lukhi T-1 (20/25 MVA, 132/33 KV) 7.2 7.2 0 OK
T-2 (20/25 MVA, 132/33 KV) 7.2 7.2 0 OK
13 220 KV Dhurala T-3 (10/16 MVA, 132/11 KV) Not Installed Capacitor bank has not been provided due
to less load. Load observed= 03 Amp (132