Electronic Modular Control Panel II+ (EMCP II+) for EUI Engines
Número de Mídia -RENR1200-01 Data de Publicação -10/01/1999 Data de Atualização -10/09/2001

i01174918

Alarm Mode
SMCS - 4490; 7451

The alarm mode alerts the operator when an alarm fault is occurring. An alarm fault is not critical but
an alarm fault is potentially serious. An alarm fault precedes certain dedicated shutdown faults. An
alarm fault can be protective relaying functions that have been enabled as an alarm fault.

When an alarm fault exists the GSC+ automatically activates alarm mode. The operator is alerted by
the FLASHING fault alarm indicator. Press the "ALARM CODES" key in order to identify the
alarm fault. A corresponding fault code is then shown on the upper display. This fault code can be an
AL fault code, a SP fault code or a diagnostic fault code. "Spare 1" indicator, "Spare 2" indicator or
"Spare 3" indicator may be flashing. The fault alarm indicator may also be flashing. For more
information on fault codes, see System Operation, "Fault Description". When the GSC+ is in alarm
mode, the engine is able to start or the engine is able to run.

The AL fault codes that are shown on the GSC+ indicate the current status of the generator set. The
GSC+ does not show the AL fault codes after the fault has been corrected. Diagnostic fault codes are
logged in the GSC+ fault log for viewing by service personnel.

ote: When the operator overrides a shutdown fault to be an alarm fault, the corresponding
dedicated fault shutdown indicator is on continuously. The fault shutdown indicator stays on
continuously if the particular fault occurs. When the fault shutdown indicator is ON
CONTINUOUSLY, the normal shutdown response has been overridden by the operator. The
shutdown fault is treated as an alarm fault. For shutdown faults that are overridden, the fault is not
displayed on the wall. The dedicated shutdown indicator remains ON CONTINUOUSLY until the
fault is corrected and the engine control switch (ECS) is turned to the "OFF/RESET" position. The
dedicated shutdown faults that can be overridden are low oil pressure and high coolant temperature.
See Systems Operation, "Setpoint Programming OP5 (P03)". For more information, see System
Operation, "Shutdown Mode".

Alarm faults do not have an immediate adverse effect on the generator set. However, the operator
should investigate the cause of the alarm fault condition at the earliest opportunity. If the operation
of the generator set is mandatory then the procedure to start and stop is identical to normal mode.
The GSC+ will respond to the operator input that is from the instrument panel and the engine
sensors.

Alarm Mode Sequence

https://sisweb.cat.com/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisw... 31/08/2010
Pesquisa de Mídia - RENR1200 - Electronic Modular Control Panel II+ (EMCP II+... Página 2 de 2

1. An alarm fault occurs.

2. The GSC+ detects the alarm fault and the GSC+ FLASHES the fault alarm indicator. The
GSC+ does not change the status or operation of the generator set.

3. Pressing the "ALARM CODES" key causes the upper display to show a corresponding fault
code.

4. Correct the alarm fault. See Testing And Adjusting, "Fault Identification".

5. After the alarm fault has been corrected, the GSC+ turns OFF the fault alarm indicator and the
GSC+ removes the fault code from the upper display. The GSC+ now returns to normal mode.