Escolar Documentos
Profissional Documentos
Cultura Documentos
Service Manual
Table of Contents
Part Ⅰ : Technical Information .......................................................................1
1. Summary ......................................................................................................................1
2. Specifications ..........................................................................................................5
2.1 Specification Sheet...........................................................................................................5
2.2 Capacity Curve in Different Outdoor Temperature .........................................................21
2.3 Cooling and Heating Data Sheet in Rated Frequency ...................................................21
3. Outline Dimension Diagram ......................................................................22
3.1 Indoor Unit ......................................................................................................................22
3.2 Outdoor Unit ...................................................................................................................23
4. Refrigerant System Diagram ....................................................................26
5. Electrical Part.........................................................................................................28
5.1 Wiring Diagram...............................................................................................................28
5.2 PCB Printed Diagram .....................................................................................................37
6. Function and Control ......................................................................................38
6.1 Remote Controller Introduction of YAN1F1 ...................................................................38
6.2 Remote Controller Introduction of YB1FA(MOTO) .........................................................42
6.3 Brief Description of Modes and Functions......................................................................46
Table of Contents
Service Manual
Appendix: ......................................................................................................................139
Appendix 1: Reference Sheet of Celsius and Fahrenheit ..................................................139
Appendix 2: Configuration of Connection Pipe...................................................................139
Appendix 3: Pipe Expanding Method .................................................................................140
Appendix 4: List of Resistance for Temperature Sensor ....................................................141
Table of Contents
Service Manual
A1 Panel
A6 Panel
B6 Panel
C2 Panel
B4 Panel
C6 Panel
Technical Information 1
Service Manual
Outdoor Unit:
GWC09QB-K3NNA1B/O
GWC09QB-K3NNA1J/O
GWH09QB-K3NNA1B/O
GWH09QB-K3NNA1J/O
GWC12QC-K3NNA1B/O
GWC12QC-K3NNA1G/O
GWH12QC-K3NNA1B/O
GWH12QC-K3NNA1D/O
GWC18QD-K3NNA1B/O
GWC18QD-K3NNA1F/O
GWH18QD-K3NNA1B/O
GWC24QE-K3NNA1B/O
GWH24QE-K3NNA1B/O
2 Technical Information
Service Manual
GWH18QD-K3NNA1D/O
GWH24QE-K3NNA1E/O
GWC24QE-K3NNA1E/O
Remote Controller:
YAN1F1
YB1FA(MOTO)
X-FAN I
Technical Information 3
Service Manual
Model List:
4 Technical Information
Service Manual
2. Specifications
2.1 Specification Sheet
1.GWH09QB-K3NNA1B
Model GWC09QB-K3NNA1B 2.GWH09QB-K3NNB6B
3.GWH09QB-K3NNC6B
1.CA419006100 2.CA435001400
Product Code CA419006000
3.CA443001000
Rated Voltage V~ 220-240 220-240
Power
Rated Frequency Hz 50 50
Supply
Phases 1 1
Power Supply Mode Indoor Indoor
Cooling Capacity W 2638 2638
Heating Capacity W / 2800
Cooling Power Input W 865 865
Heating Power Input W / 800
Cooling Power Current A 4.18 4.01
Heating Power Current A / 3.71
Rated Input W 1250 1250
Rated Current A 6.0 6.0
3
Air Flow Volume(SH/H/M/L/SL) m /h 550/490/430/330/- 550/500/445/340/-
Dehumidifying Volume L/h 0.8 0.8
EER W/W 3.05 3.05
COP W/W / 3.5
SEER W/W / /
HSPF W/W / /
2
Application Area m 12-18 12-18
1.GWH09QB-K3NNA1B/I
Model of indoor unit GWC09QB-K3NNA1B/I 2.GWH09QB-K3NNB6B/I
3.GWH09QB-K3NNC6B/I
1.CA419N06100 2.CA435N01400
Indoor Unit Product Code CA419N06000
3.CA443N01000
Fan Type Cross-flow Cross-flow
Diameter Length(DXL) mm Ф98X580 Ф98X580
Fan Motor Cooling Speed(SH/H/M/L/SL) r/min 1300/1200/1050/800/- 1300/1200/1050/800/-
Fan Motor Heating Speed(SH/H/M/L/SL) r/min / 1300/1200/1050/900/-
Output of Fan Motor W 20 20
Fan Motor RLA A 0.15 0.2
Fan Motor Capacitor μF 1 1
Evaporator Form Aluminum Fin-copper Tube Aluminum Fin-copper Tube
Indoor Unit Pipe Diameter mm Ф5 Ф5
Row-fin Gap mm 2-1.4 2-1.4
Coil Length (LXDXW) mm 578X22.8X266.7 584X22.8X266.7
Swing Motor Model MP24AA MP24AA
Output of Swing Motor W 1.5 1.5
Fuse A 3.15 3.15
Sound Pressure Level (SH/H/M/L/SL) dB (A) 40/37/33/26/- 40/37/33/26/-
Sound Power Level (SH/H/M/L/SL) dB (A) 50/47/43/36/- 50/47/43/36/-
Dimension (WXHXD) mm 790X275X200 790X275X200
Dimension of Carton Box (LXWXH) mm 863X268X352 863X268X352
Dimension of Package (LXWXH) mm 866X271X367 866X271X367
Net Weight kg 8.5 8.5
Gross Weight kg 10.5 10.5
Technical Information 5
Service Manual
The above data is subject to change without notice; please refer to the nameplate of the unit.
6 Technical Information
Service Manual
Technical Information 7
Service Manual
The above data is subject to change without notice; please refer to the nameplate of the unit.
8 Technical Information
Service Manual
1.GWC12QC-K3NNA1B 1.GWH12QC-K3NNA1B
Model 2.GWC12QC-K3NNA6B 2.GWH12QC-K3NNB6B
3.GWC12QC-K3NNC2B 3.GWH12QC-K3NNC6B
1.CA419006400 2.CA427005600 1.CA419006500 2.CA435001300
Product Code
3.CA439003000 3.CA443001300
Rated Voltage V~ 220-240 220-240
Power
Rated Frequency Hz 50 50
Supply
Phases 1 1
Power Supply Mode Indoor Indoor
Cooling Capacity W 3223 3223
Heating Capacity W / 3400
Cooling Power Input W 1070 1057
Heating Power Input W / 958
Cooling Power Current A 5.0 4.9
Heating Power Current A / 4.4
Rated Input W 1500 1500
Rated Current A 8 8
3
Air Flow Volume(SH/H/M/L/SL) m /h 650/540/460/330/- 650/540/460/330/-
Dehumidifying Volume L/h 1.2 1.2
EER W/W 3.01 3.05
COP W/W / 3.55
SEER W/W / /
HSPF W/W / /
2
Application Area m 15-22 15-22
1.GWC12QC-K3NNA1B/I 1.GWH12QC-K3NNA1B/I
Model of indoor unit 2.GWC12QC-K3NNA6B/I 2.GWH12QC-K3NNB6B/I
3.GWC12QC-K3NNC2B/I 3.GWH12QC-K3NNC6B/I
1.CA419N06400 2.CA427N05600 1.CA419N06500 2.CA435N01300
Indoor Unit Product Code
3.CA439N03000 3.CA443N01300
Fan Type Cross-flow Cross-flow
Diameter Length(DXL) mm Ф98X633.5 Ф98X633.5
Fan Motor Cooling Speed(SH/H/M/L/SL) r/min 1300/1100/1000/800/- 1300/1100/1000/800/-
Fan Motor Heating Speed(SH/H/M/L/SL) r/min / 1200/1100/1000/900/-
Output of Fan Motor W 20 20
Fan Motor RLA A 0.32 0.32
Fan Motor Capacitor μF 1.5 1.5
Evaporator Form Aluminum Fin-copper Tube Aluminum Fin-copper Tube
Indoor Unit Pipe Diameter mm Ф5 Ф5
Row-fin Gap mm 2-1.4 2-1.4
Coil Length (LXDXW) mm 635X22.8X306.3 635X22.8X306.3
Swing Motor Model MP24BA MP24BA
Output of Swing Motor W 1.5 1.5
Fuse A 3.15 3.15
Sound Pressure Level (SH/H/M/L/SL) dB (A) 41/37/34/29/- 41/37/34/29/-
Sound Power Level (SH/H/M/L/SL) dB (A) 50/47/44/39/- 50/47/44/39/-
Dimension (WXHXD) mm 845X289X209 845X289X209
Dimension of Carton Box (LXWXH) mm 918X278X364 918X278X364
Dimension of Package (LXWXH) mm 921X281X379 921X281X379
Net Weight kg 10 10
Gross Weight kg 12 12
Technical Information 9
Service Manual
The above data is subject to change without notice; please refer to the nameplate of the unit.
10 Technical Information
Service Manual
Technical Information 11
Service Manual
The above data is subject to change without notice; please refer to the nameplate of the unit.
12 Technical Information
Service Manual
1.GWH18QD-K3NNA1B
Model GWC18QD-K3NNA1B 2.GWH18QD-K3NNB6B
3.GWH18QD-K3NNC6B
1.CA419006700 2.CA435001200
Product Code CA419006600
3.CA443001200
Rated Voltage V~ 220-240 220-240
Power
Rated Frequency Hz 50 50
Supply
Phases 1 1
Power Supply Mode Indoor Indoor
Cooling Capacity Btu/h 17400 17500
Heating Capacity Btu/h / 19200
Cooling Power Input W 1670 1698
Heating Power Input W / 1631
Cooling Power Current A 7.75 7.88
Heating Power Current A / 7.56
Rated Input W 2150 2150
Rated Current A 9.97 11.09
Air Flow Volume(SH/H/M/L/SL) m3/h 900/855/825/765/- 850/820/790/730/-
Dehumidifying Volume L/h 1.8 1.8
EER Btu/h.W 10.42 10.31
COP Btu/h.W / 11.77
SEER W/W / /
HSPF W/W / /
2
Application Area m 23-34 23-34
1.GWH18QD-K3NNA1B/I
Model of indoor unit GWC18QD-K3NNA1B/I 2.GWH18QD-K3NNB6B/I
3.GWH18QD-K3NNC6B/I
1.CA419N06700 2.CA435N01200
Indoor Unit Product Code CA419N06600
3.CA443N01200
Fan Type Cross-flow Cross-flow
Diameter Length(DXL) mm Ф106X706 Ф106X706
Fan Motor Cooling Speed(SH/H/M/L/SL) r/min 1350/1200/1100/900/- 1300/1150/1000/850/-
Fan Motor Heating Speed(SH/H/M/L/SL) r/min / 1250/1150/1050/900/-
Output of Fan Motor W 35 35
Fan Motor RLA A 0.35 0.15
Fan Motor Capacitor μF 2.5 2.5
Evaporator Form Aluminum Fin-copper Tube Aluminum Fin-copper Tube
Indoor Unit Pipe Diameter mm Ф7 Ф7
Row-fin Gap mm 2-1.4 2-1.4
Coil Length (LXDXW) mm 715X25.4X304.8 715X25.4X304.8
Swing Motor Model MP35CJ MP35CJ
Output of Swing Motor W 2.5 2.5
Fuse A 3.15 3.15
Sound Pressure Level (SH/H/M/L/SL) dB (A) 47/43/41/36/- 46/44/41/35/-
Sound Power Level (SH/H/M/L/SL) dB (A) 57/53/51/46/- 56/54/51/45/-
Dimension (WXHXD) mm 970X300X224 970X300X224
Dimension of Carton Box (LXWXH) mm 1038X380X305 1038X380X305
Dimension of Package (LXWXH) mm 1041X383X320 1041X383X320
Net Weight kg 13.5 13.5
Gross Weight kg 16.5 16.5
Technical Information 13
Service Manual
The above data is subject to change without notice; please refer to the nameplate of the unit.
14 Technical Information
Service Manual
Technical Information 15
Service Manual
The above data is subject to change without notice; please refer to the nameplate of the unit.
16 Technical Information
Service Manual
Technical Information 17
Service Manual
The above data is subject to change without notice; please refer to the nameplate of the unit.
18 Technical Information
Service Manual
1.GWC24QE-K3NNA1B
1.GWH24QE-K3NNA1B
2.GWC24QE-K3NNA6B
Model 2.GWH24QE-K3NNB6B
3.GWC24QE-K3NNB4B
3.GWH24QE-K3NNC6C
4.GWC24QE-K3NNC2B
1.CA419005600 CA419005601
1.CA419005500 2.CA435001500
Product Code 2.CA427006100 3.CA434007000
3.CA443001100
4.CA439002500
Rated Voltage V~ 220-240 220-240
Power
Rated Frequency Hz 50 50
Supply
Phases 1 1
Power Supply Mode Indoor Indoor
Cooling Capacity W 6448 6448
Heating Capacity W / 6500
Cooling Power Input W 2140 2140
Heating Power Input W / 1805
Cooling Power Current A 9.93 9.93
Heating Power Current A / 8.37
Rated Input W 3300 3300
Rated Current A 15.31 15.31
Air Flow Volume(SH/H/M/L/SL) m3/h 1250/1100/960/820/- 1150/1050/860/760/-
Dehumidifying Volume L/h 2 2
EER W/W 3.01 3.01
COP W/W / 3.60
SEER W/W / /
HSPF W/W / /
Application Area m2 27-42 27-42
1.GWC24QE-K3NNA1B/I
1.GWH24QE-K3NNA1B/I
2.GWC24QE-K3NNA6B/I
Model of indoor unit 2.GWH24QE-K3NNB6B/I
3.GWC24QE-K3NNB4B/I
3.GWH24QE-K3NNC6C/I
4.GWC24QE-K3NNC2B/I
1.CA419N05600 CA419N05601 1.CA419N05500
Indoor Unit Product Code 2.CA427N06100 3.CA434N07000 2.CA435N01500
4.CA439N02500 3.CA443N01100
Fan Type Cross-flow Cross-flow
Diameter Length(DXL) mm Φ108X830 Φ108X830
Fan Motor Cooling Speed(SH/H/M/L/SL) r/min 1300/1150/1000/850/- 1200/1100/900/800/-
Fan Motor Heating Speed(SH/H/M/L/SL) r/min / 1150/1100/900/850/-
Output of Fan Motor W 35 35
Fan Motor RLA A 0.35 0.35
Fan Motor Capacitor μF 3 3
Indoor Unit Evaporator Form Aluminum Fin-copper Tube Aluminum Fin-copper Tube
Pipe Diameter mm Ф7 Φ7
Row-fin Gap mm 2-1.4 2-1.4
Coil Length (LXDXW) mm 850X25.4X381 850X25.4X381
Swing Motor Model MP35CJ MP35CJ
Output of Swing Motor W 2.5 2.5
Fuse A 3.15 3.15
Sound Pressure Level (SH/H/M/L/SL) dB (A) 50/46/42/38/- 50/46/42/38/-
Sound Power Level (SH/H/M/L/SL) dB (A) 60/56/52/48/- 60/56/52/48/-
Dimension (WXHXD) mm 1078X325X246 1078X325X246
Dimension of Carton Box (LXWXH) mm 1145X410X335 1145X410X335
Dimension of Package (LXWXH) mm 1148X413X350 1148X413X350
Net Weight kg 17 17
Gross Weight kg 20.5 20.5
Technical Information 19
Service Manual
The above data is subject to change without notice; please refer to the nameplate of the unit.
20 Technical Information
Service Manual
110
120
100
100
90
80
Capacity ratio(%)
80
60
Heating:
Pressure of gas pipe
Rated heating condition(°C) Inlet and outlet pipe Fan speed
connecting indoor and Fan speed of
(DB/WB) Model temperature of heat exchanger of outdoor
outdoor unit indoor unit
unit
Indoor Outdoor P (MPa) T1 (°C) T2 (°C)
in:61~65 in:1~2
20/- 7/6 09K 2.3~2.5 Super High High
out:30~37 out:2~4
in:55~65 in:1~3
20/- 7/6 12K 2.8~3.2 Super High High
out:25~32 out:2~5
in:75~85 in:1~3
20/- 7/6 18/24K 1.8~2.1 Super High High
out:37~43 out:2~5
Instruction:
T1: Inlet and outlet pipe temperature of evaporator
T2: Inlet and outlet pipe temperature of condenser
P: Pressure at the side of big valve
Connection pipe length: 5 m.
Technical Information 21
Service Manual
W D
09K 12K
168.5 462 159.5
131 542 172
Φ55 Φ55
Ф55 Ф55
54 43 43
54
143 80
150 90
18K 24K
38 38
190 43 43
181
154 79
Unit:mm
Model W H D
09K 790 275 200
12K 845 289 209
18K 970 300 224
24K 1078 325 246
22 Technical Information
Service Manual
660 255
428
720 310
440
286
Unit:mm
712 257
540
776 320
510
286
Unit:mm
Technical Information 23
Service Manual
GWC18QD-K3NNA1B/O GWC18QD-K3NNA1F/O
763 257
540
848 320
540
286
Unit:mm
846 300
680
913 378
345
Unit:mm
550
24 Technical Information
Service Manual
GWH18QD-K3NNA1D/O
847 300
680
931 378
549
348
Unit: mm
GWC24QE-K3NNA1E/O GWH24QE-K3NNA1E/O
955
340
700
890 396
860
364
Unit: mm
Technical Information 25
Service Manual
Gas pipe
side
Valve
Discharge
Heat
exchanger
(evaporator) Suction Accumlator Heat
Compressor exchanger
(condenser)
Liquid pipe
side
Valve
Capillary Strainer
COOLING
Gas pipe
side
Valve
4-Way valve
Discharge
COOLING
HEATING
26 Technical Information
Service Manual
Gas pipe
side
Valve
Discharge
Heat
exchanger
(evaporator) Suction Accumlator
Compressor
Liquid pipe
side
Valve
Throttle Valve Strainer
COOLING
Gas pipe
side
Valve
4-Way valve
Discharge
COOLING
HEATING
Technical Information 27
Service Manual
5. Electrical Part
5.1 Wiring Diagram
●Instruction
Note: Jumper cap is used to determine fan speed and the swing angle of horizontal lover for this model.
● Indoor Unit
N(1)
AP2 AC-L
K1(K3) COMP BK 2 BK
JUMP
PRINTED CIRCUIT BOARD YEGN
CONNECTING
SWING-UD PG PGF YEGN XT CABLE
PE
EVAPORATOR
M2
M1
STEPPING 6363244401
MOTOR FAN MOTOR
28 Technical Information
Service Manual
BU(WH) POWER
TUBE TEMP. ROOM TEMP. RECEIVER AND N
SENSOR SENSOR DISPLAY BOARD BN(BK)
L
AP1 DISPLAY YEGN(GN)
0 0
RT1 PE
RT2
EARTH-PLATE
YEGN
DISP1 DISP2 PE YEGN
T-SENSOR
EVAPORATOR
CAP AP2 N1 BU
XT
BU
PRINTED CIRCUIT BOARD N(1)
JUMP
OUTDOOR UNIT
AC-L BK BK
K1(K3) 2
COMP
VT 4 VT
4WAY
SWING-UD OG OG
PG PGF OFAN 5
C0NNECTING
TERMINAL CABLE
BLOCK
M2
M1
STEPPING
MOTOR FAN MOTOR 6363220101
TUBE ROOM
TEMP. TEMP. RECEIVER AND
SENSOR SENSOR DISPLAY BOARD BN(BK)
L
AP1 DISPLAY BU(WH)
θ θ N
YEGN(GN)
RT1 RT2
POWER
N(1)
Technical Information 29
Service Manual
BN(BK)
L
ROOM
BU(WH)
TUBE N
TEMP. TEMP. RECEIVER AND YEGN(GN)
SENSOR SENSOR DISPLAY BOARD
AP1 DISPLAY POWER
0 0
PE
RT2 EARTH-PLATE
RT1
YEGN YEGN
PE
T-SENSOR DISP1 DISP2 EVAPORATOR
L101
OUTDOOR UNIT
CAP XT
N1 BU BU
N(1)
JUMP AP2 K1 L(AC-L) BK 2 BK
PRINTED CIRCUIT BOARD COMP
VT 4 VT
4WAY
(SWING) OG 5 OG
SWING-UD OFAN
PG PGF CONNECTING
TERMINAL CABLE
BLOCK
M2
M1
STEPPING
MOTOR FAN MOTOR 6363243802
TUBE ROOM
TEMP. TEMP. RECEIVER AND
SENSOR SENSOR DISPLAY BOARD BN(BK)
L
AP1 DISPLAY BU(WH)
θ θ N
YEGN(GN)
RT1 RT2
POWER
BK BK
AP2 COMP 2
JUMP
PRINTED CIRCUIT BOARD L(AC-L) BN 3 BN
YEGN
(SWING) CONNECTING
SWING-UD YEGN XT CABLE
PG PGF
PE
EVAPORATOR
M2
M1
STEPPING
MOTOR FAN MOTOR 6363244802
30 Technical Information
Service Manual
TUBE ROOM
TEMP. TEMP. RECEIVER AND
SENSOR SENSOR DISPLAY BOARD BN(BK)
L
AP1 DISPLAY BU(WH)
θ θ N
YEGN(GN)
RT1 RT2
POWER
OUTDOOR UNIT
BK BK
AP2 COMP 2
JUMP
PRINTED CIRCUIT BOARD L(AC-L) BN 3 BN
YEGN
(SWING) CONNECTING
SWING-UD YEGN XT CABLE
PG PGF
HEALTH-L HEALTH-N PE
EVAPORATOR
M2
M1 RD BU
COLD PLASMA
STEPPING GENERATOR 63632448
MOTOR FAN MOTOR
BN(BK)
L
TUBE ROOM RECEIVER AND BU(WH)
TEMP. TEMP. DISPLAY BOARD N
SENSOR SENSOR YEGN(GN)
AP2 DISPLAY
POWER
0 0
PE
RT1 RT2 EARTH-PLATE
YEGN
PE
YEGN
T-SENSOR DISP1 DISP2 L101 EVAPORATOR
XT
CAP N1 BU N(1) BU
OUTDOOR UNIT
BK BK
JUMP AP1 COMP 2
BN 3 BN
PRINTED CIRCUIT BOARD L(AC-L)
VT VT
(SWING) 4WAY 4
SWING-UD OG OG
PG PGF OFAN 5
CONNECTING
TERMINAL CABLE
BLOCK
M2
M1
STEPPING
MOTOR FAN MOTOR 6363243702
Technical Information 31
Service Manual
● Outdoor Unit
C(U)
M1 M2
BK E YEGN E YEGN
COMP FAN
S(X) MOTOR R(M,V) MOTOR
E E
YE C1 BU RD
(BK) BU BN C2
XT1
BU
BU
N(1)
INDOOR UNIT
BK (BN)
2 BK
YEGN
E
63613294
61413297
C(T,U)
M1
E YEGN
S(W,X) COMP
MOTOR R(M,V)
E
BK YE BU
C1
YEGN M2
BU E YEGN
E FAN
MOTOR
E
INDOOR UNIT
XT1 BU
BU BN
N(1) BU
BK C2
2 RD
VT 4
OG XT2
5
YV
OG
32 Technical Information
Service Manual
(3) GWC12QC-K3NNA1G/O
NOTE:
Motor ground
C COMP. FAN only applies
MOTOR to the iron
shell motor.
COMP PE YEGN M
BK PE YEGN
S R(M) PE
PE
YE C1 BU RD
BN
TERMINAL BU C2
BLOCK
BU N(1)
INDOOR UNIT
BU(BK)
BK BK
2
YEGN XT
PE 6363357901
(4) GWH12QC-K3NNA1D/O
NOTE:
Motor ground
C COMP. only applies
to the iron
COMP PE YEGN FAN shell motor.
BK MOTOR
S R(M) PE
M PE YEGN
YE C1 BU PE
CAP. BN
YEGN RD C2
BU(BK)
PE CAP.
INDOOR UNIT
XT1
BU
BU XT2
N(1) BU TERMINAL
BLOCK VT
BK
2 4-WAY
VT VT VALVE
4 4YV
OG OG
5
TERMINAL 6363361501
BLOCK
Technical Information 33
Service Manual
C(T,U) COMP.
COMP YEGN
PE
S(W,X) R(M,V) PE
BK
YE BU FAN MOTOR
C1
YEGN M YEGN
PE
PE
INDOOR UNIT
CAP. PE
XT BU
BU
N(1) RD BN
BK
2
BK(BU) (BN)
VT C2
4 VT 4YV
VT
OG 5 4-WAY VALVE CAP.
TERMINAL WH
BOARD (OG)
6363302101
(6) GWC24QE-K3NNA1B/O
5BK
C COMP.
COMP. PE 6YEGN
S R(M) FAN MOTOR
3BU PE M2 PE
YEGN
4YE
1BU
C1 PE
RD BN
(BN)
XT1 C2
BU 2BU
N(1) BK (BU)
BK 9BU
INDOOR UNIT
2
7BK 6 1
BN 3
8BN
KM CONTACTOR
YEGN 4 0
PE
WH (OG)
63613899
34 Technical Information
Service Manual
(7) GWC24QE-K3NNA1E/O
%.
&7
&203
&203 3( <(*1
3(
6; 50
%8
<(
& )$102725
%8
&$3
-
0 3(
<(*1
3(
;7 %8 %. 5' %1
%8
1 %8 %8
&
,1'22581,7
%. %.
%1 &$3
%1
.0 $&&217$&725
<(*1 7(50,1$/
%2$5'
%.
3(
(8) GWH24QE-K3NNA1B/O
CAP. CAP.
AC CONTACTOR
YEGN BU 6 1
BU
INDOOR UNIT
PEXT
KM
BU N(1) HP 4 0
BK 1 P 2 BK
BK
2 HIGH PRESSURE
BN BN SWITCH
3
VT VT 4YV VT
4
OG WH(OG) 4-WAY VALVE
5
TERMINAL
BLOCK 6361000001201
Technical Information 35
Service Manual
(9) GWH24QE-K3NNA1E/O
CAP. CAP.
YEGN BU
AC CONTACTOR
6 1
BU
INDOOR UNIT
PEXT
KM
BU N(1) HP 4 0
BK 1 P 2 BK
BK
2 HIGHPRESSURE
BN BN SWITCH
3
VT VT 4YV VT
4
OG OG 4-WAY VALVE
5
TERMINAL
BLOCK 63610000012
These wiring diagrams are subject to change without notice; please refer to the one supplied with the unit.
36 Technical Information
Service Manual
4 5 6 7 8 9 10
3 11
2
12
13
1
14
Technical Information 37
Service Manual
1 ON/OFF button
2 MODE button
WIFI
3 FAN button
4 SWING button
1
3 5 TURBO button
2
5
6 ▲/ button
▲
4
6
7 7 SLEEP button
8
9
8 TEMP button
11 10
9 I FEEL button
12 10 LIGHT button
11 CLOCK button
38 Technical Information
Service Manual
1. ON/OFF button
Press this button can turn on or turn off the air conditioner. After turning on the air conditioner, operation indicator " "on indoor unit’s
display is ON (green indicator. The colour is different for different models), and indoor unit will give out a sound.
2. MODE button
Press this button to select your required operation mode.
● When selecting auto mode, air conditioner will operate automatically according to ex-factory setting. Set temperature can’t be adjusted and
will not be displayed as well. Press "FAN" button can adjust fan speed. Press "SWING" button can adjust fan blowing angle.
● After selecting cool mode, air conditioner will operate under cool mode. Cool indicator " "on indoor unit is ON. Press "▲" or " " button
▲
to adjust set temperature. Press "FAN" button to adjust fan speed. Press "SWING" button to adjust fan blowing angle.
● When selecting dry mode, the air conditioner operates at low speed under dry mode. Dry indicator " " on indoor unit is ON. Under dry
mode, fan speed can’t be adjusted. Press "SWING" button to adjust fan blowing angle.
● When selecting fan mode, the air conditioner will only blow fan, no cooling and no heating. All indicators are OFF. Press "FAN" button to
adjust fan speed. Press "SWING" button to adjust fan blowing angle.
● When selecting heating mode, the air conditioner operates under heat mode. Heat indicator " " on indoor unit is ON. Press "▲" or " "
▲
button to adjust set temperature. Press "FAN" button to adjust fan speed. Press "SWING" button to adjust fan blowing angle. (Cooling only
unit won’t receive heating mode signal. If setting heat mode with remote controller, press ON/OFF button can’t start up the unit).
Note:
● For preventing cold air, after starting up heating mode, indoor unit will delay 1~5 minutes to blow air (actual delay time is depend on indoor
ambient temperature).
● Set temperature range from remote controller: 16~30℃ ; Fan speed: auto, low speed, medium speed, high speed.
3. FAN button
Pressing this button can set fan speed circularly as: auto (AUTO), low( ) ,medium( ), high( ).
Auto
Caution:
● Under AUTO speed, air conditioner will select proper fan speed automatically according to ex-factory setting.
● Fan speed under dry mode is low speed.
4. SWING button
Press this button can select up&down swing angle. Fan blow angle can be selected circularly as below:
no display
(horizontal louvers stops at current position)
● When selecting " ", air conditioner is blowing fan automatically. Horizontal louver will automatically swing up & down at maximum angle.
● When selecting " 、 、 、 、 ", air conditioner is blowing fan at fixed position. Horizontal louver will stop at the fixed position.
● When selecting " 、 、 " , air conditioner is blowing fan at fixed angle. Horizontal louver will send air at the fixed angle.
● Hold " "button above 2s to set your required swing angle. When reaching your required angle, release the button.
Note:
● " 、 、 " may not be available. When air conditioner receives this signal, the air conditioner will blow fan automatically.
5. TURBO button
Under COOL or HEAT mode, press this button to turn to quick COOL or quick HEAT mode. " " icon is displayed on remote controller.
Press this button again to exit turbo function and " " icon will disappear.
6. ▲/
▲
button
● Press "▲" or " " button once increase or decrease set temperature 1℃ . Holding "▲" or " " button, 2s later, set temperature on remote
▲ ▲
controller will change quickly. On releasing button after setting is finished, temperature indicator on indoor unit will change accordingly.
(Temperature can’t be adjusted under auto mode)
● When setting TIMER ON, TIMER OFF or CLOCK, press "▲" or "▲" button to adjust time. (Refer to CLOCK, TIMER ON, TIMER OFF
buttons) When setting TIMER ON, TIMER OFF or CLOCK, press "▲" or "▲" button to adjust time. (Refer to CLOCK, TIMER ON, TIMER
OFF buttons)
Technical Information 39
Service Manual
7. SLEEP button
Under COOL, HEAT or DRY mode, press this button to start up sleep function. " " icon is displayed on remote controller. Press this button
again to cancel sleep function and " " icon will disappear.
8. TEMP button
By pressing this button, you can see indoor set temperature, indoor ambient temperature or outdoor ambient temperature on indoor unit’s
display. The setting on remote controlleris selected circularly as below:
no display
● When selecting " " or no display with remote controller, temperature indicator on indoor unit displays set temperature.
● When selecting " " with remote controller, temperature indicator on indoor unit displays indoor ambient temperature.
● When selecting " " with remote controller, temperature indicator on indoor unit displays outdoor ambient temperature.
Note:
● Outdoor temperature display is not available for some models. At that time, indoor unit receives " "signal, while it displays indoor set
temperature.
● It’s defaulted to display set temperature when turning on the unit.There is no display in the remote controller.
● Only for the models whose indoor unit has dual-8 display.
● When selecting displaying of indoor or outdoor ambient temperature, indoor temperature indicator displays corresponding temperature and
automatically turn to display set temperature after three or five seconds.
9. I FEEL button
Press this button to start I FEEL function and " " will be displayed on the remote controller. After this function is set, the remote controller
will send the detected ambient temperature to the controller and the unit will automatically adjust the indoor temperature according to the
detected temperature. Press this button again to close I FEEL function and " " will disappear.
● Please put the remote controller near user when this function is set. Do not put the remote controller near the object of high temperature
or low temperature in order to avoid detecting inaccurate ambient temperature.
10. LIGHT button
Press this button to turn off display light on indoor unit. " " icon on remote controller disappears. Press this button again to turn on
display light. " " icon is displayed.
Release this button when reaching your required time. Press "CLOCK" button to confirm the time. " " icon stops blinking.
Note:
● Clock time adopts 24-hour mode.
● The interval between two operation can’t exceeds 5s. Otherwise, remote controller will quit setting status. Operation for TIMER ON/TIMER
OFF is the same.
confirm it. The word "ON" will stop blinking. " " icon resumes displaying. Cancel TIMER ON: Under the condition that TIMER ON is
started up, press "TIMER ON" button to cancel it.
● TIMER OFF button
"TIMER OFF" button can set the time for timer off. After pressing this button," " icon disappears and the word "OFF" on remote
controller blinks. Press "▲" or " " button to adjust TIMER OFF setting. After each pressing "▲" or " " button,
▲ ▲
TIMER OFF setting will increase or decrease 1min. Hold "▲" or " " button, 2s later, the time will change quickly until reaching your
▲
required time. Press "TIMER OFF" word "OFF" will stop blinking. " " icon resumes displaying. Cancel TIMER OFF. Under the condition
that TIMER OFF is started up, press "TIMER OFF" button to cancel it.
Note:
● Under on and off status, you can set TIMER OFF or TIMER ON simultaneously.
● Before setting TIMER ON or TIMER OFF, please adjust the clock time.
● After starting up TIMER ON or TIMER OFF, set the constant circulating valid. After that, air conditioner will be turned on or turned off
according to setting time. ON/OFF button has no effect on setting. If you don’t need this function, please use remote controller to cancel it.
40 Technical Information
Service Manual
2. 8 ℃ heating function
Under heating mode, press "TEMP" and "CLOCK" buttons simultaneously to start up or turn off 8℃ heating function. When this function is
started up, " " and "8℃ " will be shown on remote controller, and the air conditioner keep the heating status at 8℃ . Press "TEMP" and
"CLOCK" buttons simultaneously again to exit 8℃ heating function.
Note:
● Under 8℃ heating function, fan speed is defaulted at auto speed and it can’t be adjusted.
● Under 8℃ heating function, set temperature can’t be adjusted. Press "TURBO" button and the remote controller won’t send signal.
● Sleep function and 8℃ heating function can’t operate at the same time. If 8℃ heating function has been set under cooling mode, press
sleep button will cancel 8℃ heating function. If sleep function has been set under cooling mode, start up the 8℃ heating function will
cancel sleep function.
● Under ℉ temperature display, the remote controller will display 46 ℉ heating.
Operation guide
1. After putting through the power, press "ON/OFF" button on remote controller to turn on the air conditioner.
2. Press "MODE" button to select your required mode: AUTO, COOL, DRY, FAN, HEAT.
3. Press "▲" or " " button to set your required temperature. (Temperature can’t be adjusted under auto mode).
▲
4. Press "FAN" button to set your required fan speed: auto, low, medium and high speed.
5. Press "SWING" button to select fan blowing angle.
1. Press the back side of remote controller marked with " ", as shown in the fig, and then push signal sender battery
out the cover of battery box along the arrow direction.
2. Replace two 7# (AAA 1.5V) dry batteries, and make sure the position of "+" polar and "-" polar reinstall
are correct.
3. Reinstall the cover of battery box. remove
Note:
Cover of battery box
● During operation, point the remote control signal sender at the receiving window on indoor unit.
● The distance between signal sender and receiving window should be no more than 8m, and there should be no obstacles between them.
● Signal may be interfered easily in the room where there is fluorescent lamp or wireless telephone; remote controller should be close to
indoor unit during operation.
● Replace new batteries of the same model when replacement is required.
● When you don’t use remote controller for a long time, please take out the batteries.
● If the display on remote controller is fuzzy or there’s no display, please replace batteries.
Technical Information 41
Service Manual
2 MODE Button
3 +/- Button
4 FAN Button
5 Button
1 2
6 CLOCK Button
3
7 TIMER ON/TIMER-OFF Button
4
5
6 8 X-FAN Button
8 7 9 TEMP Button
10 9 10 TURBO Button
12 11
11 LIGHT Button
12 SLEEP Button
Up&down swing
2. MODE Button
Press this button to select your required operation mode.
AUTO COOL DRY FAN HEAT
42 Technical Information
Service Manual
● When selecting auto mode, Air conditioner will start auto operation according to indoor ambient temperature.Set temperature can’t be
adjusted and will not be displayed as well. Press "FAN" button can adjust fan speed. Press " " button can adjust fan blowing angle.
● After selecting cool mode, air conditioner will operate under cool mode. Cool indicator " " on indoor unit is ON. Press "+" or "-" button
to adjust set temperature. Press "FAN" button to adjust fan speed. Press " " button to adjust fan blowing angle.
● When selecting dry mode, the air conditioner operates at low speed under dry mode. Dry indicator " " on indoor unit is ON. Under dry
mode, fan speed can’t be adjusted. Press " " button to adjust fan blowing angle.
● When selecting fan mode, the air conditioner will only blow fan, no cooling and no heating.All indicators are OFF.Operation indicator is
ON.Press "FAN" button to adjust fan speed. Press " " button to adjust fan blowing angle.
● When selecting heating mode, the air conditioner operates under heat mode. Heat indicator " " on indoor unit is ON. Press “+” or “-“
button to adjust set temperature Press “FAN” button to adjust fan speed. Press " " button to adjust fan blowing angle.(Cooling only unit
won’t receive heating mode signal. If setting heat mode with remote controller, press ON/OFF button can’t start up the unit).
Note:
● For preventing cold air, after starting up heating mode, indoor unit will delay 1~5minutes to blow air (actual delay time is depend on
indoor ambient temperature).
● Set temperature range from remote controller: 16~30 ; Fan speed: auto, low speed,medium speed, high speed.
4. FAN Button
Pressing this button can set fan speed circularly as: auto (AUTO), low( ) ,medium( ),high( ).
Auto
Note:
● Under AUTO speed, the IDU fan motor will adjust the fan speed (high, medium or low speed) according to ambient temperature.
● Fan speed under dry mode is low speed.
5. Button
Pressing this button can select up&down swing angle. Fan blow angle can be selected circularly as below:
no display
(horizontal louvers
stops at current position)
● When selecting " " , air conditioner is blowing fan automatically. Horizontal louver will automatically swing up & down at
maximum angle.
● When selecting " ", air conditioner is blowing fan at fixed position. Horizontal louver will stop at the fixed
position.
● When selecting " ”, air conditioner is blowing fan at fixed angle. Horizontal louver will send air at the fixed angle.
● Hold " " button above 2s to set your required swing angle. When reaching your required angle, release the button.
Note:
" " may not be available. When air conditioner receives this signal, the air conditioner will blow fan automatically.
6. CLOCK Button
Press this button to set clock time. " " icon on remote controller will blink. Pess "+" or "-" button within 5s to set clock time. Each
pressing of "+" or "-" button, clock time will increase or decrease 1 minute. Hold "+" or "-" button, 2s later, time will change quickly.
Release this button when reaching your required time. Press “CLOCK" button to confirm the time. " " icon stops blinking.
Note:
● Clock time adopts 24-hour mode.
● The interval between two operation can’t exceeds 5s. Otherwise, remote controller will quit setting status. Operation for TIMER
ON/TIMER OFF is the same.
7. TIMER-ON/TIMER-OFF Button
● TIMER ON button
TIMER ON button
“TIMER ON” button can set the time for timer on. After pressing this button, " " icon disappears and the word “ON" on remote
Technical Information 43
Service Manual
controller blinks. Press "+" or "-"button to adjust TIMER ON setting. After each pressing "+" or "-"button, TIMER ON setting will increase
or decrease 1min. Hold "+" or "-"button, 2s later, the time will change quickly
until reaching your required time. Press “ TIMER ON”to confirm it. The word “ON" will stop blinking. " " icon resumes displaying.
Cancel TIMER ON: Under the condition that TIMER ON is started up, press “TIMER ON” button to cancel it.
● TIMER OFF button
"TIMER OFF" button can set the time for timer off. After pressing this button, " " icon disappears and the word "OFF" on remote
controller blinks. Press "+" or "-" button to adjust TIMER OFF setting. After each pressing "+" or "-" button, TIMER OFF setting will
increase or decrease 1min. Hold "+" or "-" button, 2s later, the time will change
quickly until reaching your required time. Press "TIMER OFF" to confirm it .The word "OFF"will stop blinking " " icon resumes
displaying. Cancel TIMER OFF. Under the condition that TIMER OFF is started up, press “TIMER OFF” button to cancel it.
Note:
● Under on and off status, you can set TIMER OFF or TIMER on simultaneously.
● Before setting TIMER ON or TIMER OFF, please adjust the clock time.
● After starting up TIMER ON or TIMER OFF, set the constant circulating valid. After that, air conditioner will be turned on or turned off
according to setting time. ON/OFF button has no effect on setting. If you don’t need this function, please use remote controller to cancel
it.
8. X-FAN Button
Press this button under cool and dry mode to start up x-fan function, and " " icon on remote controller will be displayed. Press this
button again to cancel x-fan function, and " "icon will disappear.
Note:
● When x-fan function is on, if the air conditioner is turned off, indoor fan will still operate at low speed for a while to blow the residual
water inside the air duct.
● During x-fan operation, press X-FAN button to turn off x-fan function. Indoor fan will stop operation immediately.
9. TEMP Button
By pressing this button, you can see indoor set temperature, indoor ambient temperature or outdoor ambient temperature on indoor
unit’s display. The setting on remote controlleris selected circularly as below:
no display
When selecting " " or no display with remote controller, temperature indicator on indoor unit displays set temperature;
When selecting " " with remote controller, temperature indicator on indoor unit displays indoor ambient temperature;
When selecting " " with remote controller, temperature indicator on indoor unit displays outdoor ambient temperature.
Note:
● Outdoor temperature display is not available for some models. At that time, indoor unit receives" " signal, while it displays
indoor set temperature.
● It’s defaulted to display set temperature when turning on the unit.There is no display in the remote controller.
● Only for the models whose indoor unit has dual-8 display
44 Technical Information
Service Manual
Operation Guide
1. After putting through the power, press “ON/OFF” button on remote controller to turn on
1 2
the air conditioner.
2. Press "MODE" button to select your required mode:AUTO,COOL,DRY,FAN,HEAT. 3
3. Press “+” or “-“ button to set your required temperature. (Temperature can’t be 4
5
adjusted under auto mode).
4. Press ‘FAN” button to set your required fan speed: auto, low, medium and high speed.
5. Press " " button to select fan blowing angle.
Technical Information 45
Service Manual
Start cooling
Tpreset +1 ˚C Tamb.
Original operating status
Tpreset –1 ˚C
Stop cooling
Graphic instruction: 6 min. 3 min. 6 min.
(Same as below)
Compressor
Indicates operation
Outdoor fan motor
Indicates stop
Indoor fan motor Set fan speed
In cooling mode, the 4-way valve is de-energized (4-way valve is not available for cooling only unit). Temperature setting range is 16~30℃ .
② Display: Operation icon, cooling icon, set temperature.
③ Protection function
◆ Freeze protection
46 Technical Information
Service Manual
During operation, when controller detected that Ttube≤0℃ for a consecutive period of time, the system enters into freeze protection. In
that case, the compressor and the ODU fan stop operation, while the IDU operates at set fan speed. If freeze protection is released and
the compressor has been out of operation for 3 mins, the unit will resume its previous operation status.
Freeze protection period
Compressor 3 min
Outdoor fan motor
Indoor fan motor Set fan speed
◆ Overcurrent protection ( this protection function is not available for those models whose cooling capacity ≤12000Btu/h)
During operation process, if controller detected that system current exceeds the limit value for 3s consecutively (overcurrent), only the
fan operates. About 3 mins later, if overcurrent is released, the system will resume original operation.
If overcurrent protection occurs for 6 times consecutively, and resume operation time won’t exceed 6min every time, overcurrent protec-
tion information will be displayed. After turning off the unit, display won’t be displayed.
If turn on the unit again, the system will be restated up again. Overcurrent protection information will be eliminated.
Please refer to maintenance part for display information and disposal method for details.
Tamb.
Cooling
Tpreset+2
Drying
Tpreset-2
6 min 6min. Stop
4min. 4min.
Compressor
Outdoor fan motor
Indoor fan motor Low speed
Technical Information 47
Service Manual
(5) Heating mode(no heating mode is not available for cooling only unit)
① Operation conditioner and process for heating mode
◆ When Tamb-Tcompensation≤Tpreset-1℃ , unit will operate in heating mode. 4-way valve will be energized while compressor and
outdoor fan starts operation at the same time. Indoor fan will start some time later so that air condition won’t blow out cold air.
◆ When Tamb-Tcompensation≥Tpreset+1℃ , compressor and outdoor fan will stop operation while 4-way valve is still power on. Indoor
fan will continue operation for a while at set fan speed to blow out the residual heat so that temperature within the air conditioner won’t
be too high.
◆ When Tpreset-1℃< Tamb-Tcompensation < Tpreset+1℃ , system will maintain its previous working status.
In heating mode, 4-way valve is energized. Temperature setting range is 16~30℃ .
Stop heating
Tpreset+4
Original operating status
Tpreset+2
Tamb.
min. min. min. Start heating
Compressor
Outdoor unit
Intdoor unit min. Set fan speed min. Set fan speed
Reversing valve
48 Technical Information
Service Manual
Controller has general timer function and clock timer function. When you select the remote controller with general timer function, only
the general timer function of controller can be activated; when you select the remote controller with clock timer, only the clock timer
function of controller can be activated.
① General timer: The precision of general timer is 0.5hour. 24hours circulated timer can’t be set.
◆ Timer ON: Timer ON can be set at unit OFF. If selected ON time is reached, the unit will start to operate according to previous
setting status. Time setting range is 0.5~24hr in 30-minute increments.
◆ Timer OFF: Timer OFF can be set at unit ON. If selected OFF time is reached, the unit will stop. Time setting range is 0.5~24hr in
30-minute increments.
② Clock timer: The precision of clock timer is 1minute. 24hours circulated timer can be set.
◆ Timer ON: If timer ON is set during operation of the unit, the unit will continue to operate. If timer ON is set at unit OFF, upon ON
time reaches, the unit will start to run according to previous setting status.
◆ Timer OFF: If timer OFF is set at unit OFF, the system will keep standby status. If timer OFF is set at unit ON, upon OFF time
reaches, the unit will stop operation.
◆ Timer change:
Although timer has been set, the unit still can be turned on/off by pressing ON/OFF button on the remote controller. You can also reset
the timer.
If timer ON and timer OFF are set at the same time during operation of the unit, the unit will keep running at current status till OFF
time reaches. Upon ON time reached, the system will be turned on automatically. The unit will operate circularly like that every
24hours.
If timer ON and timer OFF are set at unit OFF status, the system keep OFF status till ON time reaches. Upon OFF time reaches, the
system will be turned OFF automatically. The unit will operate circularly like that every 24hours.
(2) Emergency operation switch
After pressing this button, the system will operate according under auto mode and the IDU fan motor operates at auto speed. Swing
motor operates when the IDU fan motor operates. Press this button again to turn off the unit.
Emergency
operation switch OFF status Press ON status(Auto mode)
Press
Technical Information 49
Service Manual
◆ When air conditioner is in auto defrosting, heating icon will be on and off.
◆ If turn off light button, all display will be turned off.
50 Technical Information
Service Manual
10. Pipe pliers, pipe cutter 11. Pipe expander, pipe bender 12. Soldering appliance, refrigerant container
8. Installation
8.1 Installation Dimension Diagram
At least 15cm
At least 15cm
cm
00
At least 250cm
3
st
lea tio
n
At
Space to the
tr uc
obs
o the
et
ac
Sp
Space to the obstruction
the
to n
At least 50cm
e
ac tio
Sp truc
s st
ob
t lea
A cm
30
Space to th
e wall
n At least 50cm
tio cm
tr uc 0
obs t 20
he le as Space to the ob
struction
ot At
et
ac
Sp
Installation procedures
Start installation
Finish installation
Note: this flow is only for reference; please find the more detailed installation steps in this section.
Wall
Mark in the middle of it Level meter
Wall Cut off Fig.4
Space Space the hole
to the to the
12K: wall wall
above above
150mm 150mm 5. Connect the Pipe of Indoor Unit
Left Right (1) Aim the pipe joint at the corresponding bellmouth.(As show
Φ55mm Φ55mm
Rear piping hole Rear piping hole
in Fig.5)
(2) Pretightening the union nut with hand.
Wall Wall (3) Adjust the torque force by referring to the following sheet.
Mark in the middle of it Level meter
Space Space Place the open-end wrench on the pipe joint and place the
to the to the torque wrench on the union nut. Tighten the union nut with
wall wall
18K: above above torque wrench.(As show in Fig.6)
150mm 150mm
(4) Wrap the indoor pipe and joint of connection pipe with
Left Right insulating pipe, and then wrap it with tape.(As show in Fig.7)
Φ55mm Φ55mm
Rear piping hole Rear piping hole
Open-end
Wall Wall
Mark in the middle of it Level meter wrench
Space Space
to the to the Union nut
wall wall Pipe joint Union nut Pipe
24K: above above Torque wrench Pipe
150mm 150mm
Fig.1
Drain hose
Outlet pipe
Cable-cross
hole
Liquid
Fig.14 Band pipe
Power connection Fig.12 Drain hose
wire
Connection pipe Drain hose
Band
(3) Remove the wire clip; connect the power connection wire
and signal control wire(Only for cooling and heating unit) to the
wiring terminal according to the color; tighten the screw and
then fix the power connection wire with wire clip.(As show in
Fig.13) Fig.15
Indoor power cord
N(1) 2 3 N(1) 2 3 4 5
Drain vent Chassis
blue black brown yellow- yellow- blue black brown violet orange
Outdoor drain joint green green
Drain hose
At least 3cm above the floor
Fig.18 Fig.19 Indoor unit connection Indoor unit connection
2. Install Drain Joint(Only for cooling and heating unit)
(1) Connect the outdoor drain joint into the hole on the chassis.
(2) Connect the drain hose into the drain vent. Grounding Wiring board
wire
(As show in Fig.19)
N(1) 2 4 5
(2) Fix the power connection wire and signal control wire(only
Screw
for cooling and heating unit) with wire clip.
Note:
Foot holes Handle (1) After tightening the screw, pull the power cord slightly to
Fig.21 check if it is firm.
Fig.20
(2) Never cut the power connection wire to prolong or shorten
the distance.
58 Installation and Maintenance
Service Manual
(2) If the outdoor unit is higher than the wall hole, you must set Refrigerant charging Valve cap
a U-shaped curve in the pipe before pipe goes into the room, vent
in order to prevent rain from getting into the room.(As show in Nut of refrigerant
Fig.24) Charging vent
Vacuum pump
The drain hos
can't raise Inner hexagon
upwards spanner
Wall
Fig.28 Close
Open
Fig.25
U-shaped curve
Fig.24 2. Leakage Detection
Drain hose (1) With leakage detector:
Note: Check if there is leakage with leakage detector.
(1) The through-wall height of drain hose shouldn't be higher (2) With soap water:
than the outlet pipe hole of indoor unit.(As show in Fig.25) If leakage detector is not available, please use soap water for
(2) Slant the drain hose slightly downwards. The drain hose leakage detection. Apply soap water at the suspected position
can't be curved, raised and fluctuant, etc.(As show in Fig.26) and keep the soap water for more than 3min. If there are air
(3) The water outlet can't be placed in water in order to drain bubbles coming out of this position, there's a leakage.
smoothly.(As show in Fig.27)
8.8 Check after Installation and Test
Operation
1. Check after Installation
Check according to the following requirement after finishing
The drain hose can't be fluctuant
installation.
No. Items to be checked Possible malfunction
The water outlet Has the unit been The unit may drop, shake or
can't be placed 1
The drain hose in water installed firmly? emit noise.
can't be fluctuant
The water Have you done the It may cause insufficient cooling
outlet can't be 2
fluctuant Fig.27 refrigerant leakage test? (heating) capacity.
Is heat insulation of It may cause condensation and
3
Fig.26 pipeline sufficient? water dripping.
It may cause condensation and
4 Is water drained well?
water dripping.
Is the voltage of power
8.7 Vacuum Pumping and Leak supply according to the It may cause malfunction or
5
Detection voltage marked on the damage the parts.
nameplate?
Is electric wiring and
1. Use Vacuum Pump It may cause malfunction or
(1) Remove the valve caps on the liquid valve and gas valve 6 pipeline installed
damage the parts.
and the nut of refrigerant charging vent. correctly?
(2) Connect the charging hose of piezometer to the refrigerant Is the unit grounded
7 It may cause electric leakage.
charging vent of gas valve and then connect the other charging securely?
hose to the vacuum pump. Does the power cord It may cause malfunction or
8
(3) Open the piezometer completely and operate for 10-15min follow the specification? damage the parts.
to check if the pressure of piezometer remains in -0.1MPa. Is there any obstruction It may cause insufficient cooling
9
(4) Close the vacuum pump and maintain this status for 1-2min in air inlet and air outlet? (heating).
to check if the pressure of piezometer remains in -0.1MPa. If The dust and
the pressure decreases, there may be leakage. sundries caused It may cause malfunction or
10
(5) Remove the piezometer, open the valve core of liquid valve during installation are damaging the parts.
and gas valve completely with inner hexagon spanner. removed?
(6) Tighten the screw caps of valves and refrigerant charging The gas valve and liquid
It may cause insufficient cooling
vent.(As show in Fig.28) 11 valve of connection pipe
(heating) capacity.
are open completely?
2. Test Operation
(1) Preparation of test operation
● The client approves the air conditioner installation.
● Specify the important notes for air conditioner to the client.
(2) Method of test operation
● Put through the power, press ON/OFF button on the remote
controller to start operation.
● Press MODE button to select AUTO, COOL, DRY, FAN and
HEAT to check whether the operation is normal or not.
● If the ambient temperature is lower than 16℃ , the air
conditioner can’t start cooling.
9. Maintenance
9.1 Error Code
Display Method Possible Causes(For specific maintenance
No. Malfunction
of Indoor Unit A/C Status method, please refer to the following procedure of
Name
(Error Code) troubleshooting)
1. The wiring terminal between indoor ambient temperature
The unit will stop operation as it sensor and main board is loosened or poorly contacted;
Indoor ambient
reaches the temperature point. 2. There’s short circuit due to trip-over of the parts on
temperature
During cooling and drying operation, controller;
1 sensor is F1
except IDU fan motor operates, other 3. Indoor ambient temperature sensor is damaged (Please
open/short-
loads stop operation; During heating check it by referring to the resistance table for temperature
circuited
operation, the system stops operation. sensor)
4. Main board is broken.
1. The wiring terminal between indoor evaporator
The unit will stop operation as it temperature sensor and main board is loosened or poorly
Indoor
reaches the temperature point. contacted;
evaporator
During cooling and drying operation, 2. There’s short circuit due to the trip-over of the parts on
temperature
2 F2 except IDU fan operates, other controller;
sensor is
loads stop operation; During heating 3.Indoor evaporator temperature sensor is damaged
open/short-
operation, the complete unit stops (Please check it by referring to the resistance table for
circuited
operation. temperature sensor)
4. Main board is broken.
1. The feedback terminal of PG motor is not connected
tightly.
IDU fan, ODU fan, compressor and
Blocked 2. The control terminal of PG motor is not connected
electric heat tube stop operation.
3 protection of H6 tightly.
Horizontal louver stops at the current
IDU fan motor 3. Fan blade rotates unsmoothly.
position.
4. Malfunction of motor
5. Main board is broken.
1. There’s not jumper cap on the main board.
Malfunction Operation of remote controller or
2. Jumper cap is not inserted properly and tightly.
4 protection of C5 control panel is available, but the unit
3. Jumper cap is damaged.
jumper cap won’t act.
4. Controller is damaged.
1. Unstable supply voltage. Normal fl uctuation shall be
within 10% of the rated voltage on the nameplate.
2. Supply voltage is too low and load is too high.
Overcurrent 3. Measure the current of live wire on main board. If the
protection(This current isn’t higher than the overcurrent protection value,
protection please check the controller.
During cooling and drying operation,
function is not 4. The indoor and outdoor heat exchangers are too dirty,
except IDU fan motor operates, other
5 available for E5 or the air inlet and air outlet are blocked.
loads stop operation; During heating
those models 5. The fan motor is not running. Abnormal fan speed: fan
operation, the system stops operation.
whose cool- speed is too low or the fan doesn’t run
ing capacity 6. The compressor is not running normally. There is
≤12000Btu/h) abnormal sound, oil leakage or the temperature of the
shell is too high, etc.
7. There’s blockage in the system (filth blockage, ice plug,
greasy blockage, Y-valve hasn’t been opened completely)
1. Outdoor and indoor heat exchangers are too dirty or the
air inlet/outlet is blocked
2. Fan motor is not working. Abnormal fan speed; fan
speed is too low or the fan doesn’t run.
Overload 3. Compressor doesn’t work normally. Strange noise or
6 E8 Unit stops working.
malfunction leakage occurs. Temperature of the shell is too high.
4. System is blocked inside (dirt block, ice block, oil block,
Y-valve not fully open)
5.Temperature sensor of main board doesn’t sense
correctly.
Zero-crossing
1. Quick de-energization and energization. Wrong
inspection
Operation of remote controller or judgement by the controller because the electric-
circuit
7 U8 control panel is available, but the unit discharging of capacitor is slow.
malfunction
won’t act. 2. Zero-crossing inspection circuit of main board for
of the IDU fan
controller is abnormal.
motor
1. Outdoor and indoor heat exchangers are too dirty or the
air inlet/outlet is blocked.
2. Fan motor is not working Abnormal fan speed; fan
speed is too low or the fan doesn't run.
Overload 3. Compressor doesn't work normally.Strange noise or
8 protection for H3 The entire unit stops. leakage occurs.Temperature of the shell is too high.
compressor 4. System is blocked inside(dirt block, ice block, oil block,
Y-valve not fully open).
5. High pressure switch is abnormal.
6. The refrigerant is leaking and cause overheating
protection to compressor.
No
No Is malfunction
eliminated
No
No Is malfunction Yes
eliminated
Replace it with a
temperature sensor with
the same model
Yes
No Is malfunction
eliminated
Yes
End
No Is malfunction Yes
eliminated
Yes
No Is malfunction Yes
eliminated
No Is malfunction Yes
eliminated
Yes
Is the motor started up
No
Measure the voltage of this foot to
neutral wire on the mainboard Replace PG motor
No
No Is malfunction Yes
eliminated
End
Start
No Appearance of the
Is there jumper cap on the mainboard?
jumper cap
No Is malfunction
eliminated
No Is malfunction Yes
eliminated
Is malfunction Yes
eliminated
Yes
No
End
Start
No No
Is the supply voltage too low Yes Adjust the supply voltage to maintain it Is malfunction Yes
with overload? within normal range eliminated
No No
Is the indoor / outdoor Yes Clean the indoor and outdoor heat Is malfunction Yes
heat exchanger dirty,or are the air inlet exchangers and remove the blockage eliminated
and outlet blocked? of air inlet and outlet
No
No
The fan is abnormal? Fan Yes Check the motor and reinstall the Is malfunction Yes
speed is too low or fan doesn’t rotate motor to have the fan run normally eliminated
No No
Yes No
No No
No
End
5. High temperature and overload protection (AP1 below means control board of outdoor unit) E8
Main detection points:
● If the outdoor ambient temperature is in normal range;
● If the indoor and outdoor fan are running normally;
● If the radiating environment of indoor and outdoor unit is good.
Malfunction diagnosis process:
Start
No
No
No
No
Yes
Yes
Yes Replace fan
Fan capacitor is broken? capacitor
Replace outdoor
mainboard
No
No
Replace mainboard
End
Start
Yes
End
Start
No
No
No No
No
No
No
No
Check whether high Yes Replace high pressure switch Malfunction is Yes
pressure switch is normal eliminated.
No No
No
No
Replace a main
board of the
same model.
End
27 28 29 30 10
9 11
8
X-FAN
I
I
12
7
6 13
4
14
3
15
16
2 17
1 18
19
20
A1
/B6
/C2
pan
21
el 22
A6
pan
el
C6
pan
23
el
24
26
25
The component picture is only for reference; please refer to the actual product.
Part Code
Description
No. GWC09QB-K3NNA1B/I GWH09QB-K3NNA1B/I Qty
Product Code CA419N06000 CA419N06100
1 Front Case Assy 20022495 20022495 1
2 Display Board 30565231 30565231 1
3 Front Case Assy 20022495 20022495 1
4 Helicoid Tongue 26112508 26112508 1
5 Left Axile Bush 10512037 10512037 1
6 Rear Case assy 22202560 22202560 1
7 Drainage Hose 0523001408 0523001408 1
8 Ring of Bearing 26152022 26152022 1
9 O-Gasket sub-assy of Bearing 7651205102 7651205102 1
10 Evaporator Support 24212180 24212180 1
11 Evaporator Assy 01002678 01002678 1
12 Wall Mounting Frame 01252043 01252043 1
13 Cross Flow Fan 10352059 10352059 1
14 Fan Motor 150120874 150120874 1
15 Connecting pipe clamp 2611216401 2611216401 1
16 Rubber Plug (Water Tray) 76712012 76712012 1
17 Stepping Motor 1521212901 1521212901 1
18 Crank 73012005 73012005 1
19 Electric Box Assy 20402660 20402679 1
20 Axile Bush 10542036 10542036 1
21 Terminal Board 42010276 42010268 1
22 Jumper 4202300113 4202300113 1
23 Main Board 30135964 30135968 1
24 Electric Box Cover Sub-Assy 02601070 02601070 1
25 Shield Cover of Electric Box Cover 20112207 01592135 1
26 Electric Box Cover 20112207 20112207 1
27 Power Cord 400203495 400203495 1
28 Connecting Cable / 40020536 0
29 Connecting Cable 40020540 40020540 0
30 Remote Controller 30510474 30510474 1
Part Code
Description
No. GWC09QB-K3NNA1J/I GWH09QB-K3NNA1J/I Qty
Product Code CA419N15100 CA419N15000
1 Front Case Assy 20022495 20022495 1
2 Display Board 30565231 30565231 1
3 Front Case Assy 20022495 20022495 1
4 Helicoid Tongue 26112508 26112508 1
5 Left Axile Bush 10512037 10512037 1
6 Rear Case assy 20162010 20162010 1
7 Drainage Hose 0523001408 0523001408 1
8 Ring of Bearing 26152022 26152022 1
9 O-Gasket sub-assy of Bearing 7651205102 7651205102 1
10 Evaporator Support 24212180 24212180 1
11 Evaporator Assy 01100100095 01100100095 1
12 Wall Mounting Frame 01252043 01252043 1
13 Cross Flow Fan 10352059 10352059 1
14 Fan Motor 150120874 150120874 1
15 Connecting pipe clamp 2611216401 2611216401 1
16 Rubber Plug (Water Tray) 76712012 76712012 1
17 Stepping Motor 1521212901 1521212901 1
18 Crank 73012005 73012005 1
19 Electric Box Assy 20402660 20402679 1
20 Axile Bush 10542036 10542036 1
21 Terminal Board 42010276 42010268 1
22 Jumper 4202300113 4202300113 1
23 Main Board 30135964 30135968 1
24 Electric Box Cover Sub-Assy 01402065 01402065 1
25 Shield Cover of Electric Box Cover 01592150 01592150 1
26 Electric Box Cover 20112207 20112207 1
27 Power Cord 400203495 400203495 1
28 Connecting Cable / 40020536 0
29 Connecting Cable 40020540 40020540 0
30 Remote Controller 30510474 30510474 1
Part Code
Description
No. GWC12QC-K3NNA1G/I GWH12QC-K3NNA1D/I Qty
Product Code CA419N15300 CA419N15200
1 Front Case Assy 20022489 20022489 1
2 Display Board 30565231 30565231 1
3 Front Case Assy 20022489 20022489 1
4 Helicoid Tongue 26112507 26112507 1
5 Left Axile Bush 10512037 10512037 1
6 Rear Case assy 22202375 22202375 1
7 Drainage Hose 05230014 05230014 1
8 Ring of Bearing 26152022 26152022 1
9 O-Gasket sub-assy of Bearing 7651205102 7651205102 1
10 Evaporator Support 24212179 24212179 1
11 Evaporator Assy 01002976 01002976 1
12 Wall Mounting Frame 01252484 01252484 1
13 Cross Flow Fan 10352056 10352056 1
14 Fan Motor 15012146 15012146 1
15 Connecting pipe clamp 2611216401 2611216401 1
16 Rubber Plug (Water Tray) 76712012 76712012 1
17 Stepping Motor 1521210701 1521210701 1
18 Crank 73012005 73012005 1
19 Electric Box Assy 20102000471 10000202018 1
20 Axile Bush 10542036 10542036 1
21 Terminal Board 42010276 42010268 1
22 Jumper 4202300107 4202300107 1
23 Main Board 30145022 30145024 1
24 Electric Box Cover Sub-Assy 01402065 01402065 1
25 Shield Cover of Electric Box Cover 01592150 01592150 1
26 Electric Box Cover 20112207 20112207 1
27 Power Cord 400203495 400203495 1
28 Connecting Cable 40020540 40020540 0
29 Connecting Cable / 40020536 0
30 Remote Controller 30510516 30510516 1
Part Code
Description
No. GWH09QB-K3NNB6B/I GWH12QC-K3NNB6B/I Qty
Product Code CA435N01400 CA435N01300
1 Front Case Assy 00000200040 00000200045 1
2 Display Board 30565281 30565281 1
3 Front Case Assy 00000200040 00000200045 1
4 Helicoid Tongue 26112508 26112436 1
5 Left Axile Bush 10512037 10512037 1
6 Rear Case assy 20162010 00000100093 1
7 Drainage Hose 0523001408 05230014 1
8 Ring of Bearing 26152022 26152022 1
9 O-Gasket sub-assy of Bearing 7651205102 7651205102 1
10 Evaporator Support 24212180 24212179 1
11 Evaporator Assy 0100200004402 01002976 1
12 Wall Mounting Frame 01252043 01252484 1
13 Cross Flow Fan 10352059 10352056 1
14 Fan Motor 150120874 1501214603 1
15 Connecting pipe clamp 2611216401 2611216401 1
16 Rubber Plug (Water Tray) 76712012 76712012 1
17 Stepping Motor 1521212901 1521210701 1
18 Crank 73012005 73012005 1
19 Electric Box Assy 10000202553 10000202538 1
20 Axile Bush 10542036 10542036 1
21 Terminal Board 42010268 42010268 1
22 Jumper 4202300117 4202300120 1
23 Main Board 30135968 30145024 1
24 Electric Box Cover Sub-Assy 01402065 01402065 1
25 Shield Cover of Electric Box Cover 01592150 01592150 1
26 Electric Box Cover 20112207 20112207 1
27 Power Cord 400203495 400203495 1
28 Connecting Cable 40020536 40020536 0
29 Connecting Cable 40020540 40020540 0
30 Remote Controller 30510474 30510474 1
Part Code
Description
No. GWH09QB-K3NNC6B/I GWH12QC-K3NNC6B/I Qty
Product Code CA443N01000 CA443N01300
1 Front Case Assy 20000300101 20000300102 1
2 Display Board 30565260 30565260 1
3 Front Case Assy 00000200040 00000200045 1
4 Helicoid Tongue 26112508 26112436 1
5 Left Axile Bush 10512037 10512037 1
6 Rear Case assy 20162010 00000100093 1
7 Drainage Hose 0523001408 05230014 1
8 Ring of Bearing 26152022 26152022 1
9 O-Gasket sub-assy of Bearing 7651205102 7651205102 1
10 Evaporator Support 24212180 24212179 1
11 Evaporator Assy 0100200004402 01002976 1
12 Wall Mounting Frame 01252043 01252484 1
13 Cross Flow Fan 10352059 10352056 1
14 Fan Motor 150120874 1501214603 1
15 Connecting pipe clamp 2611216401 2611216401 1
16 Rubber Plug (Water Tray) 76712012 76712012 1
17 Stepping Motor 1521212901 1521210701 1
18 Crank 73012005 73012005 1
19 Electric Box Assy 10000202554 10000204722 1
20 Axile Bush 10542036 10542036 1
21 Terminal Board 42010268 42010268 1
22 Jumper 4202300117 4202300120 1
23 Main Board 30135968 30145024 1
24 Electric Box Cover Sub-Assy 0140206501 0140206501 1
25 Shield Cover of Electric Box Cover 01592150 01592150 1
26 Electric Box Cover 20112207 20112207 1
27 Power Cord 400203495 400203495 1
28 Connecting Cable 40020536 40020536 0
29 Connecting Cable 40020540 40020540 0
30 Remote Controller 30510474 30510474 1
Part Code
Description
No. GWC12QC-K3NNA1B/I GWH12QC-K3NNA1B/I Qty
Product Code CA419N06400 CA419N06500
1 Front Case Assy 20022489 20022489 1
2 Display Board 30565231 30565231 1
3 Front Case Assy 20022489 20022489 1
4 Helicoid Tongue 26112507 26112507 1
5 Left Axile Bush 10512037 10512037 1
6 Rear Case assy 22202557 22202557 1
7 Drainage Hose 05230014 05230014 1
8 Ring of Bearing 26152022 26152022 1
9 O-Gasket sub-assy of Bearing 7651205102 7651205102 1
10 Evaporator Support 24212179 24212179 1
11 Evaporator Assy 01002976 01002976 1
12 Wall Mounting Frame 01252484 01252484 1
13 Cross Flow Fan 10352056 10352056 1
14 Fan Motor 15012146 15012146 1
15 Connecting pipe clamp 2611216401 2611216401 1
16 Rubber Plug (Water Tray) 76712012 76712012 1
17 Stepping Motor 1521210701 1521210701 1
18 Crank 73012005 73012005 1
19 Electric Box Assy 20102000471 20102000409 1
20 Axile Bush 10542036 10542036 1
21 Terminal Board 42010276 42010268 1
22 Jumper 4202300107 4202300107 1
23 Main Board 30145022 30145024 1
24 Electric Box Cover Sub-Assy 02601070 02601070 1
25 Shield Cover of Electric Box Cover 01592135 01592135 1
26 Electric Box Cover 20112207 20112207 1
27 Power Cord 400203495 400203495 1
28 Connecting Cable / 40020536 0
29 Connecting Cable 40020540 40020540 0
30 Remote Controller 30510474 30510474 1
Part Code
Description
No. GWC12QC-K3NNA6B/I GWC12QC-K3NNC2B/I Qty
Product Code CA427N05600 CA439N03000
1 Front Case Assy 2002273101 00000200045 1
2 Display Board 30565265 30565281 1
3 Front Case Assy 2002273101 00000200045 1
4 Helicoid Tongue 26112507 26112436 1
5 Left Axile Bush 10512037 10512037 1
6 Rear Case assy 22202375 00000100093 1
7 Drainage Hose 05230014 05230014 1
8 Ring of Bearing 26152022 26152022 1
9 O-Gasket sub-assy of Bearing 7651205102 7651205102 1
10 Evaporator Support 24212179 24212179 1
11 Evaporator Assy 01002976 01002976 1
12 Wall Mounting Frame 01252484 01252484 1
13 Cross Flow Fan 10352056 10352056 1
14 Fan Motor 15012146 1501214603 1
15 Connecting pipe clamp 2611216401 2611216401 1
16 Rubber Plug (Water Tray) 76712012 76712012 1
17 Stepping Motor 1521210701 1521210701 1
18 Crank 73012005 73012005 1
19 Electric Box Assy 10000202264 10000203363 1
20 Axile Bush 10542036 10542036 1
21 Terminal Board 42010276 42010276 1
22 Jumper 4202300120 4202300120 1
23 Main Board 30145022 30145022 1
24 Electric Box Cover Sub-Assy 01402065 01402065 1
25 Shield Cover of Electric Box Cover 01592150 01592150 1
26 Electric Box Cover 20112207 20112207 1
27 Power Cord 400203495 400203495 1
28 Connecting Cable / / 0
29 Connecting Cable 40020540 40020540 0
30 Remote Controller 30510474 30510474 1
18K
The component picture is only for reference; please refer to the actual product.
Part Code
Description
No. GWC18QD-K3NNA1B/I GWH18QD-K3NNA1B/I Qty
Product Code CA419N06600 CA419N06700
1 Decorative Strip 20192613 20192613 1
2 Front Panel 20022481S 20022481S 1
3 Display Board 30565233 30565233 1
4 Filter Sub-Assy 11122089 11122089 2
5 Decorative Board (Left) 20192612 20192612 1
6 Front Case 20022484 20022484 1
7 Guide Louver 10512734 10512734 1
8 Axile Bush 10542036 10542036 2
9 Air Louver 10512732 10512732 3
10 Helicoid Tongue 26112512 26112512 1
11 Left Axile Bush 10512037 10512037 1
12 Rear Case assy 22202556 22202571 1
13 Rubber Plug (Water Tray) 76712012 76712012 1
14 O-Gasket sub-assy of Bearing 7651205102 7651205102 1
15 Ring of Bearing 26152025 26152025 1
16 Evaporator Support 24212177 24212177 1
17 Evaporator Assy 01002686 01002686 1
18 Cross Flow Fan 10352060 10352060 1
19 Fan Motor 15012145 15012145 1
20 Motor Press Plate 26112511 26112511 1
21 Wall Mounting Frame 01362026 01362026 1
22 Connecting pipe clamp 2611218801 2611218801 1
23 Crank 73012005 73012005 1
24 Stepping Motor 1521240212 1521240212 1
25 Drainage Hose 05230014 05230014 1
26 Electric Box Assy 20102000390 10000200091 1
27 Lower Shield of Electric Box 01592139 01592139 1
28 Electric Box 20112211 20112211 1
29 Jumper 4202300116 4202300115 1
30 Main Board 30135987 30135991 1
31 Shield Cover of Electric Box 01592140 01592140 1
32 Electric Box Cover 20112209 20112209 1
33 Terminal Board 42010276 42010268 1
34 Decorative Board (Right) 20192611 20192611 1
35 Screw Cover 242520179 242520179 3
36 Electric Box Cover2 20112210 20112210 1
37 Power Cord 400203485 400203485 1
38 Connecting Cable / 4002053603 0
39 Connecting Cable 400205401 400205401 0
40 Remote Controller 30510474 30510474 1
Part Code
Description
No. GWC18QD-K3NNA1F/I GWH18QD-K3NNA1D/I Qty
Product Code CA419N14000 CA419N13900
1 Decorative Strip 20192613 20192613 1
2 Front Panel 20022481S 20022481S 1
3 Display Board 30565233 30565233 1
4 Filter Sub-Assy 11122089 11122089 2
5 Decorative Board (Left) 20192612 20192612 1
6 Front Case 20022484 20022484 1
7 Guide Louver 10512734 10512734 1
8 Axile Bush 10542036 10542036 2
9 Air Louver 10512732 10512732 3
10 Helicoid Tongue 26112512 26112512 1
11 Left Axile Bush 10512037 10512037 1
12 Rear Case assy 22202571 22202571 1
13 Rubber Plug (Water Tray) 76712012 76712012 1
14 O-Gasket sub-assy of Bearing 7651205102 7651205102 1
15 Ring of Bearing 26152025 26152025 1
16 Evaporator Support 24212177 24212177 1
17 Evaporator Assy 01002686 01002686 1
18 Cross Flow Fan 10352060 10352060 1
19 Fan Motor 1501214502 1501214502 1
20 Motor Press Plate 26112511 26112511 1
21 Wall Mounting Frame 01362026 01362026 1
22 Connecting pipe clamp 2611218801 2611218801 1
23 Crank 73012005 73012005 1
24 Stepping Motor 1521240212 1521240212 1
25 Drainage Hose 05230014 05230014 1
26 Electric Box Assy 20102000390 10000200091 1
27 Lower Shield of Electric Box 01592139 01592139 1
28 Electric Box 20112211 20112211 1
29 Jumper 4202300116 4202300115 1
30 Main Board 30135987 30135991 1
31 Shield Cover of Electric Box 01592140 01592140 1
32 Electric Box Cover 20112209 20112209 1
33 Terminal Board 42010276 42010268 1
34 Decorative Board (Right) 20192611 20192611 1
35 Screw Cover 242520179 242520179 3
36 Electric Box Cover2 20112210 20112210 1
37 Power Cord 400203485 400203485 1
38 Connecting Cable 400205401 400205401 0
39 Connecting Cable / 4002053603 0
40 Remote Controller 30510474 30510474 1
Part Code
Description
No. GWH18QD-K3NNB6B/I GWH18QD-K3NNC6B/I Qty
Product Code CA435N01200 CA443N01200
1 Decorative Strip / / /
2 Front Panel 20000300040 20000300103 1
3 Display Board 30565278 30565260 1
4 Filter Sub-Assy 11122089 11122089 2
5 Decorative Board (Left) 20192662 20192662 1
6 Front Case 2002248401 2002248401 1
7 Guide Louver 1051276501 1051276501 1
8 Axile Bush 10542036 10542036 2
9 Air Louver 10512732 10512732 3
10 Helicoid Tongue 26112512 26112512 1
11 Left Axile Bush 10512037 10512037 1
12 Rear Case assy 22202571 22202571 1
13 Rubber Plug (Water Tray) 76712012 76712012 1
14 O-Gasket sub-assy of Bearing 7651205102 7651205102 1
15 Ring of Bearing 26152025 26152025 1
16 Evaporator Support 24212177 24212177 1
17 Evaporator Assy 01002686 01002686 1
18 Cross Flow Fan 10352060 10352060 1
19 Fan Motor 1501214502 1501214502 1
20 Motor Press Plate 26112511 26112511 1
21 Wall Mounting Frame 01362026 01252033 1
22 Connecting pipe clamp 2611218801 2611218801 1
23 Crank 73012005 73012005 1
24 Stepping Motor 1521240212 1521240212 1
25 Drainage Hose 05230014 05230014 1
26 Electric Box Assy 10000202519 10000203937 1
27 Lower Shield of Electric Box 01592139 01592139 1
28 Electric Box 20112211 20112211 1
29 Jumper 4202300103 4202300103 1
30 Main Board 30135991 30135991 1
31 Shield Cover of Electric Box 01592140 01592139 1
32 Electric Box Cover 20112209 20112209 1
33 Terminal Board 42010268 42010268 1
34 Decorative Board (Right) 20192662 20192662 1
35 Screw Cover 2425201726 2425201726 3
36 Electric Box Cover2 20112210 20112210 1
37 Power Cord 400203485 400203485 1
38 Connecting Cable 4002053603 4002053603 0
39 Connecting Cable 400205401 400205401 0
40 Remote Controller 30510474 30510474 1
24K
14 15
42
37 38 39 40 41
13
12
11 16
10
9
17
7 8
5 6 18
4 19
2 3
1
20
21
23 22
24
25
26
B4
pan
el 27
A1
/B6
/C2
28
pan
el
A6
pan
el
29 36
35
30 34
33
31 32
The component picture is only for reference; please refer to the actual product.
Part Code
Description
No. GWC24QE-K3NNA1B/I GWH24QE-K3NNA1B/I Qty
Product Code CA419N05600 CA419N05500
1 Front Panel Assy 20022491 20022491 1
2 Filter Sub-Assy 11012007 11012007 1
3 Screw Cover 24252453 24252453 1
4 Front Case Assy 20022487 20022487 2
5 Swing Lever 10512743 10512743 1
6 Air Louver 1 10512741 10512741 1
7 Helicoid Tongue 26112513 26112513 1
8 Left Axile Bush 10512037 10512037 2
9 Rear Case assy 22202558 22202558 3
10 Rubber Plug (Water Tray) 76712012 76712012 1
11 Ring of Bearing 26152025 26152025 1
12 O-Gasket sub-assy of Bearing 76512051 76512051 1
13 Cross Flow Fan 10352057 10352057 1
14 Evaporator Support 24212178 24212178 1
15 Evaporator Assy 01002687 01002687 1
16 Wall Mounting Frame 01252229 01252229 1
17 Motor Press Plate 26112515 26112515 1
18 Fan Motor 15012145 15012145 1
19 Connecting pipe clamp 26112514 26112514 1
20 Drainage Hose 0523001405 0523001405 1
21 Stepping Motor 1521240212 1521240212 1
22 Crank 73012005 73012005 1
23 Air Louver 1 10512742 10512742 1
24 Air Louver 10512744 10512744 1
25 Guide Louver 10512738 10512738 1
26 Axile Bush 10542036 10542036 1
27 Electric Box 20112211 20112211 1
28 Terminal Board 42011233 4201026201 1
29 Electric Box Cover2 20112210 20112210 1
30 Main Board 30135996 30145001 1
31 Display Board 30565233 30565233 1
32 Shield cover of Electric Box 01592140 01592140 1
33 Electric Box Cover 20112209 20112209 1
34 Jumper 4202300106 4202300106 3
35 Lower Shield of Electric Box 01592139 01592139 1
36 Electric Box Assy 20102000374 20102000373 1
37 Power Cord 400203463 400203463 1
38 Connecting Cable 400205382 400205382 0
39 Connecting Cable / 40020536 0
40 Temperature Sensor 3900031302 3900031302 1
41 Remote Controller 30510474 30510474 1
42 Cold Plasma Generator / / /
Part Code
Description GWC24QE-K3NNA1B/I
No. GWC24QE-K3NNA6B/I Qty
(Cold Plasma)
Product Code CA419N05601 CA427N06100
1 Front Panel Assy 20022491 2002248602 1
2 Filter Sub-Assy 11012007 11012007 1
3 Screw Cover 24252453 2425245301 1
4 Front Case Assy 20022487 00000200024 2
5 Swing Lever / / /
6 Air Louver 1 10512737 10512737 1
7 Helicoid Tongue 26112513 26112513 1
8 Left Axile Bush 10512037 10512037 2
9 Rear Case assy 22202570 22202570 3
10 Rubber Plug (Water Tray) 76712012 76712012 1
11 Ring of Bearing 26152025 26152025 1
12 O-Gasket sub-assy of Bearing 7651205102 7651205102 1
13 Cross Flow Fan 10352057 10352057 1
14 Evaporator Support 24212178 24212178 1
15 Evaporator Assy 01002988 01002988 1
16 Wall Mounting Frame 01252229 01252229 1
17 Motor Press Plate 26112515 26112515 1
18 Fan Motor 15012145 15012145 1
19 Connecting pipe clamp 26112514 26112514 1
20 Drainage Hose 0523001405 0523001405 1
21 Stepping Motor 1521240212 1521240212 1
22 Crank 73012005 73012005 1
23 Air Louver 1 10512737 10512737 1
24 Air Louver 10512738 10512738 1
25 Guide Louver 10512738 1051232001 1
26 Axile Bush 10542036 10542036 1
27 Electric Box 20112211 20112211 1
28 Terminal Board 42011233 42011233 1
29 Electric Box Cover2 20112210 20112210 1
30 Main Board 30135997 30135996 1
31 Display Board 30565233 30565264 1
32 Shield cover of Electric Box 01592140 01592140 1
33 Electric Box Cover 20112209 20112209 1
34 Jumper 4202300106 4202300127 3
35 Lower Shield of Electric Box 01592139 01592139 1
36 Electric Box Assy 10000202319 10000201340 1
37 Power Cord 400203463 400203463 1
38 Connecting Cable 400205382 400205382 0
39 Connecting Cable / / /
40 Temperature Sensor 3900031302 3900031302 1
41 Remote Controller 30510474 30510474 1
42 Cold Plasma Generator 1114001602 / 1
Part Code
Description
No. GWH24QE-K3NNA1E/I GWH24QE-K3NNB6B/I Qty
Product Code CA419N15400 CA435N01500
1 Front Panel Assy 20022491 20000300048S 1
2 Filter Sub-Assy 11012007 11012007 1
3 Screw Cover 24252453 2425245301 1
4 Front Case Assy 20022487 00000200043 2
5 Swing Lever / 10512743 1
6 Air Louver 1 10512737 10512737 1
7 Helicoid Tongue 26112513 26112513 1
8 Left Axile Bush 10512037 10512037 2
9 Rear Case assy 22202570 22202570 3
10 Rubber Plug (Water Tray) 76712012 76712012 1
11 Ring of Bearing 26152025 26152025 1
12 O-Gasket sub-assy of Bearing 7651205102 7651205102 1
13 Cross Flow Fan 10352057 10352057 1
14 Evaporator Support 24212178 24212178 1
15 Evaporator Assy 01100100052 01002988 1
16 Wall Mounting Frame 01252229 01252229 1
17 Motor Press Plate 26112515 26112515 1
18 Fan Motor 15012145 15012145 1
19 Connecting pipe clamp 26112514 26112514 1
20 Drainage Hose 0523001405 0523001405 1
21 Stepping Motor 1521240212 1521240212 1
22 Crank 73012005 73012005 1
23 Air Louver 1 / / /
24 Air Louver 10512737 10512737 3
25 Guide Louver 10512738 1051232001 1
26 Axile Bush 10542036 10542036 1
27 Electric Box 20112211 20112211 1
28 Terminal Board 4201026201 4201026201 1
29 Electric Box Cover2 20112210 20112210 1
30 Main Board 30145001 30145001 1
31 Display Board 30565233 30565278 1
32 Shield cover of Electric Box 01592140 01592140 1
33 Electric Box Cover 20112209 20112209 1
34 Jumper 4202300119 4202300128 3
35 Lower Shield of Electric Box 01592139 01592139 1
36 Electric Box Assy 10000202034 10000202527 1
37 Power Cord 400203485 400203463 1
38 Connecting Cable 40020538 40020538 0
39 Connecting Cable 40020536 40020536 0
40 Temperature Sensor 3900031302 3900031302 1
41 Remote Controller 30510474 30510474 1
42 Cold Plasma Generator / / /
Part Code
Description
No. GWC24QE-K3NNB4B/I GWC24QE-K3NNC2B/I Qty
Product Code CA434N07000 CA439N02500
1 Front Panel Assy 20000300029T 20000300071S 1
2 Filter Sub-Assy 11012007 11012007 1
3 Screw Cover 2425245301 2425245301 1
4 Front Case Assy 00000200043 00000200043 2
5 Swing Lever / / /
6 Air Louver 1 10512737 10512737 1
7 Helicoid Tongue 26112513 26112513 1
8 Left Axile Bush 10512037 10512037 2
9 Rear Case assy 22202570 22202570 3
10 Rubber Plug (Water Tray) 76712012 76712012 1
11 Ring of Bearing 26152025 26152025 1
12 O-Gasket sub-assy of Bearing 7651205102 7651205102 1
13 Cross Flow Fan 10352057 10352057 1
14 Evaporator Support 24212178 24212178 1
15 Evaporator Assy 01002988 01002988 1
16 Wall Mounting Frame 01252229 01252229 1
17 Motor Press Plate 26112515 26112515 1
18 Fan Motor 15012145 15012145 1
19 Connecting pipe clamp 26112514 26112514 1
20 Drainage Hose 0523001405 0523001405 1
21 Stepping Motor 1521240212 1521240212 1
22 Crank 73012005 73012005 1
23 Air Louver 1 10512737 10512737 1
24 Air Louver 60311226 60311226 1
25 Guide Louver 1051232001 1051232001 1
26 Axile Bush 10542036 10542036 1
27 Electric Box 20112211 20112211 1
28 Terminal Board 42011233 42011233 1
29 Electric Box Cover2 20112210 20112210 1
30 Main Board 30135997 30135996 1
31 Display Board 30565260 30565278 1
32 Shield cover of Electric Box 01592140 01592140 1
33 Electric Box Cover 20112209 20112209 1
34 Jumper 4202300127 4202300127 3
35 Lower Shield of Electric Box 01592139 01592139 1
36 Electric Box Assy 10000203313 10000203236 1
37 Power Cord 400203463 400203463 1
38 Connecting Cable 400205382 400205382 0
39 Connecting Cable / / /
40 Temperature Sensor 3900031302 3900031302 1
41 Remote Controller 30510474 30510474 1
42 Cold Plasma Generator 1114001602 / 1
Part Code
Description
No. GWC24QE-K3NNA1E/I GWH24QE-K3NNC6C/I Qty
Product Code CA419N15600 CA443N01100
1 Front Panel Assy 20022491 20000300104 1
2 Filter Sub-Assy 11012007 11012007 1
3 Screw Cover 24252453 2425245301 1
4 Front Case Assy 20022487 00000200043 2
5 Swing Lever / / 1
6 Air Louver 1 10512738 10512737 1
7 Helicoid Tongue 26112513 26112513 1
8 Left Axile Bush 10512037 10512037 2
9 Rear Case assy 22202570 22202570 3
10 Rubber Plug (Water Tray) 76712012 76712012 1
11 Ring of Bearing 26152025 26152025 1
12 O-Gasket sub-assy of Bearing 7651205102 7651205102 1
13 Cross Flow Fan 10352057 10352057 1
14 Evaporator Support 24212178 24212178 1
15 Evaporator Assy 01100100052 01002988 1
16 Wall Mounting Frame 01252229 01252229 1
17 Motor Press Plate 26112515 26112515 1
18 Fan Motor 15012145 15012145 1
19 Connecting pipe clamp 26112514 26112514 1
20 Drainage Hose 0523001405 0523001405 1
21 Stepping Motor 1521240212 1521240212 1
22 Crank 73012005 73012005 1
23 Air Louver 1 10512738 10512737 1
24 Air Louver 60311226 60311226 1
25 Guide Louver 10512738 1051232001 1
26 Axile Bush 10542036 10542036 1
27 Electric Box 20112211 20112211 1
28 Terminal Board 42011233 4201026201 1
29 Electric Box Cover2 20112210 20112210 1
30 Main Board 30135996 30145001 1
31 Display Board 30565233 30565260 1
32 Shield cover of Electric Box 01592140 01592139 1
33 Electric Box Cover 20112209 20112209 1
34 Jumper 4202300106 4202300128 3
35 Lower Shield of Electric Box 01592139 01592139 1
36 Electric Box Assy 10000202878 10000204679 1
37 Power Cord 400203485 400203463 1
38 Connecting Cable / 400205382 0
39 Connecting Cable 40020538 40020536 0
40 Temperature Sensor 3900031302 3900031302 1
41 Remote Controller 30510516 30510474 1
42 Cold Plasma Generator / / /
21 20 19 18
22
17
23
16
24
15
25
14
13
12
1 2 3 4 5 6 26 7 8 9 10 11
The component picture is only for reference; please refer to the actual product.
Part Code
Description
No. GWC09QB-K3NNA1B/O GWC09QB-K3NNA1J/O Qty
Product Code CA419W06000 CA419W15100
1 Front Grill 22263002 22263002 1
2 Front Panel 01533255P 01533255P 1
3 Chassis Sub-assy 0280312301P 01700000121P 1
4 Clapboard Sub-Assy 01233179 01233384 1
5 Compressor and Fittings 00103841 00103337 1
6 Inhalation Tube Sub-assy 03833392 03001000316 1
7 Capillary Sub-assy 03163534 / 1
8 Valve Support 01713041 01713041 1
9 Valve 07100003 07100003 1
10 Valve 07100005 07100005 1
11 Big Handle 26233042 2623304202 1
12 Right Side Plate Assy 01303243 01303243 1
13 Electric Box Assy 02613682 01403000201 1
14 Terminal Board 42011154 42011154 1
15 Capacitor Clamp 02143014 02143401 1
16 Capacitor CBB61 33010020 3301074701 1
17 Capacitor CBB65 33000081 33000081 1
18 Discharge Tube 03543414 03500800666 1
19 Rear Grill 11123204 11123204 1
20 Top Cover Sub-Assy 01253045P 01253045P 1
21 Condenser Assy 01103000236 01100200429 1
22 Motor Support 01703204 01703204 1
23 Fan Motor 1501315604 1501315604 1
24 Axial Flow Fan 10333002 10333002 1
25 Small Handle 26233100 26233100 1
26 Throttle Valve Sub-assy / 03005500014 1
The component picture is only for reference; please refer to the actual product.
Part Code
Description
No. GWH09QB-K3NNA1B/O GWH09QB-K3NNA1J/O Qty
Product Code CA419W06100 CA419W15000
1 Front grill 22413433 22413008 1
2 Front Panel 01533034P 01533034P 1
3 Chassis Sub-assy 0120374801P 01700000048P 1
4 Drainage Connecter 06123401 06123401 1
5 Compressor and fittings 00103804 00103978 1
6 Magnet Coil 4300040047 4300040047 1
7 4-way Valve Assy 03073300 03073384 1
8 4-way Valve 430004022 430004022 1
9 Strainer A 07210022 / 1
10 Capillary Sub-Assy 03163527 / 1
11 Valve 07100003 07100003 1
12 Valve 07100005 07100005 1
13 Big Handle 26233433 262334332 1
14 Valve Support 0170308901P 0170308901P 1
15 Right Side Plate Sub-Assy 01303183 01303183 1
16 Electric Box Assy 01403000150 10000202088 1
17 Terminal Board 42010265 42010265 1
18 Terminal Board 42011147 42011147 1
19 Capacitor CBB65 33000081 33000081 1
20 Capacitor CBB61 33010026 3301074710 1
21 Rear grill 1112320501 1112320501 1
22 Condenser Assy 01103000226 01100200419 1
23 Top Cover Sub-Assy 01253087 01253087 1
24 Clapboard Sub-Assy 01233066 01233059 1
25 Motor Support 01703103 01703103 1
26 Fan Motor 150130676 150130676 1
27 Small Handle 26233100 26233100 1
28 Axial Flow Fan 10333427 10333427 1
29 Throttle Valve Sub-assy / 03005500013 1
Part Code
Description
No. GWH12QC-K3NNA1B/O GWH12QC-K3NNA1D/O Qty
Product Code CA419W06500 CA419W15200
1 Front grill 22413008 22413008 1
2 Front Panel 01533034P 01533034P 1
3 Chassis Sub-assy 0280325701P 01700000116P 1
4 Drainage Connecter 06123401 06123401 1
5 Compressor and fittings 00103937 00103344 1
6 Magnet Coil 4300040022 4300040022 1
7 4-way Valve Assy 03073310 03073389 1
8 4-way Valve 430004022 430004022 1
9 Strainer A 07210022 07210022 1
10 Capillary Sub-Assy 03163541 03163541 1
11 Valve 07100003 07100003 1
12 Valve 07100006 07100006 1
13 Big Handle 26233433 262334332 1
14 Valve Support 0170308901P 0170308901P 1
15 Right Side Plate Sub-Assy 01303183 01303183 1
16 Electric Box Assy 02613706 10000201973 1
17 Terminal Board 42010265 42010265 1
18 Terminal Board 42011147 42011147 1
19 Capacitor CBB65 3300008102 3300008101 1
20 Capacitor CBB61 33010026 3301074710 1
21 Rear grill 1112320501 1112320501 1
22 Condenser Assy 01103000244 00010000002 1
23 Top Cover Sub-Assy 01253087 0125308701 1
24 Clapboard Sub-Assy 01233066 01233066 1
25 Motor Support 01703104 01703104 1
26 Fan Motor 150130676 150130676 1
27 Small Handle 26233100 26233100 1
28 Axial Flow Fan 10333427 10333427 1
29 Throttle Valve Sub-assy / 03005500015 1
GWC12QC-K3NNA1B/O GWC12QC-K3NNA1G/O
The component picture is only for reference; please refer to the actual product.
Part Code
Description
No. GWC12QC-K3NNA1B/O GWC12QC-K3NNA1G/O Qty
Product Code CA419W06400 CA419W15300
1 Front Grill 22413008 22413008 1
2 Front Panel 01533034P 01533034P 1
3 Chassis Sub-assy 02803257P 0170000011601P 1
4 Compressor and Fittings 00103937 00103344 1
5 Inhalation Tube 03753872 03001000201 1
6 Discharge Tube 03543437 03500800671 1
7 Capillary Sub-assy 03163543 03163543 1
8 Valve 07100003 07100003 1
9 Valve 07100006 07100006 1
10 Big Handle 26233433 262334332 1
11 Valve Support 0170308901P 0170308901P 1
12 Right Side Plate Sub-Assy 01303183 01303183 1
13 Electric Box Assy 02613663 10000202033 1
14 Terminal Board 42011154 42011154 1
15 Capacitor CBB61 33010026 3301074710 1
16 Capacitor CBB65 3300008102 3300008101 1
17 Rear Grill 1112320501 1112320501 1
18 Condenser Assy 01103000248 00010000003 1
19 Top Cover Sub-Assy 0125308701 01253087 1
20 Clapboard Sub-Assy 01233066 01233066 1
21 Motor Support 01703103 01703103 1
22 Fan Motor 150130676 150130676 1
23 Small Handle 26233100 26233100 1
24 Axial Flow Fan 10333427 10333427 1
25 Throttle Valve Sub-assy / 03005500016 1
GWC18QD-K3NNA1B/O GWC18QD-K3NNA1F/O
24
The component picture is only for reference; please refer to the actual product.
Part Code
Description
No. GWC18QD-K3NNA1B/O GWC18QD-K3NNA1F/O Qty
Product Code CA419W06600 CA419W14000
1 Front Grill 22413433 22413433 1
2 Front Panel 0153303204P 0153303204P 1
3 Chassis Sub-assy 02803254P 01700000073P 1
4 Compressor and Fittings 00105054 00103989 1
5 Inhalation Tube Sub-assy 03833922 03001000334 1
6 Discharge Tube 03543438 03001300220 1
7 Capillary Sub-assy 03163544 03700200445 1
8 Valve 07100003 07100003 1
9 Valve 07100006 07100006 1
10 Big Handle 26233433 262334332 1
11 Valve Support 01713041 01713041 1
12 Right Side Plate Assy 0130200404 0130200404 1
13 Terminal Board 42011154 42011154 1
14 Capacitor CBB65 3300008104 3300008113 1
15 Capacitor CBB61 33010026 3301074710 1
16 Electric Box Assy 01403000167 10000201455 1
17 Rear Grill 11123205 11123205 1
18 Condenser Assy 01103000249 01100200417 1
19 Top Cover Plate 01253443 01253443 1
20 Clapboard Sub-Assy 01233417 012334172 1
21 Motor Support 0170310401 0170310302 1
22 Fan Motor 1501307103 1501307103 1
23 Axial Flow Fan 10333427 10333427 1
24 Throttle Valve Sub-assy / 03005500008 1
GWH18QD-K3NNA1B/O
5 6 7 8 9 10 11
2
12
1
13
14
15
16
17
18
23 22 21 20 19
The component picture is only for reference; please refer to the actual product.
Part Code
Description
No. GWH18QD-K3NNA1B/O Qty
Product Code CA419W06700
1 Rear Grill 014730371 1
2 Left Handle 26235401 1
3 Front Panel 01305015 1
4 Axial Flow Fan 10335261 1
5 Fan Motor 15015057 1
6 Motor Support Sub-Assy 01703098 1
7 Top Cover 01255001 1
8 Clapboard Sub-Assy 01233035 1
9 Electric Box Assy 02613633 1
10 Condenser Assy 01103000303 1
11 Rear Grill 014730371 1
12 Capacitor CBB61 33010026 1
13 Capacitor CBB65 33000046 1
14 Terminal Board 42010265 1
15 Right Side Plate 01305095P 1
16 Handle 26235254 1
17 Valve Support Sub-Assy 01713075 1
18 Cut off Valve Sub-Assy 07133491 1
19 Cut off Valve 07130213 1
20 Capillary Sub-assy 03163591 1
21 4-Way Valve Assy 03073327 1
22 Compressor and Fittings 00105054 1
23 Chassis Sub-assy 01203826P 1
GWC24QE-K3NNA1B/O
24 23 22 21 20 19 18
25 17
16
15
26
14
13
12
11
1 2 3 4 5 6 7 8 9 10
The component picture is only for reference; please refer to the actual product.
Part Code
Description
No. GWC24QE-K3NNA1B/O Qty
Product Code CA419W05600
1 Front Grill 26235254 1
2 Front Panel 01305015 1
3 Axial Flow Fan 10335261 1
4 Chassis Sub-assy 0120382601P 1
5 Clapboard Sub-Assy 01233035 1
6 Compressor Gasket 76711043 3
7 Compressor and Fittings 00103872 1
8 Gas Valve Sub-Assy 07103030 1
9 Cut off Valve 07130239 1
10 Cut off Valve Sub-Assy 07133019 1
11 Discharge Tube 03543175 1
12 Handle 26235254 1
13 Right Side Plate 01305095P 1
14 Capillary Sub-assy 03163517 1
15 Inhalation Tube 03833933 1
16 Condenser Assy 01103000217 1
17 Motor Support Sub-Assy 0170309801 1
18 Rear Grill 014730371 1
19 Coping 01255002 1
20 Fan Motor 15015057 1
21 Electric Box Assy 01403000139 1
22 AC Contactor 44010245 1
23 Terminal Board 42011113 1
24 Capacitor CBB61 33010027 1
25 Capacitor CBB65 3300008105 1
26 Left Handle 26235401 1
GWH24QE-D1NTA1A/O
25 24 23 22 21 20 19
26
27 18
17
28 16
15
14
13
12
1 2 3 4 5 6 7 8 9 10 11
The component picture is only for reference; please refer to the actual product.
Part Code
Description
No. GWH24QE-D1NTA1A/O Qty
Product Code CA419W05500
1 Front Grill 22415001 1
2 Front Panel 01435001P 1
3 Axial Flow Fan 10335261 1
4 Drainage Plug 0681340101 3
5 Drainage Connecter 06123401 1
6 Chassis Sub-assy 02803202P 1
7 Clapboard Sub-Assy 01233035 1
8 Compressor and Fittings 00103872 1
9 Valve Support Sub-Assy 01715001 1
10 Cut off Valve Sub-Assy 07133798 1
11 Gas Valve Sub-Assy 07103030 1
12 Handle 26235254 1
13 Right Side Plate 01305095P 1
14 Magnet Coil 4300040047 1
15 4-Way Valve Assy 03073297 1
16 4-Way Valve 4300008201 1
17 Condenser Assy 01103000218 1
18 Motor Support Assy 01703222 1
19 Rear Grill 01473069 1
20 Coping 01255002 1
21 Fan Motor 15015057 1
22 Electric Box Assy 02613594 1
23 AC Contactor 44010245 1
24 Terminal Board 42010194 1
25 Capacitor CBB61 33010027 1
26 Capacitor Clamp 02141375 1
27 Capacitor CBB65 3300008105 1
28 Left Handle 26235401 1
GWH18QD-K3NNA1D/O
5 6 7 8 9 10 11
2
12
1
13
14
15
16
17
18
24
23 22 25 21 20 19
The component picture is only for reference; please refer to the actual product.
Part Code
Description
No. GWH18QD-K3NNA1D/O Qty
Product Code CA419W13900
1 Front grill 22415001 1
2 left handle 26235401 1
3 Cabinet 01305015 1
4 Axial Flow Fan 10335261 1
5 Fan Motor 15015057 1
6 Motor Support Sub-Assy 01703098 1
7 Top Cover 01255001 1
8 Clapboard Sub-Assy 01233035 1
9 Electric Box Assy 10000201882 1
10 Condenser Assy 01100200396 1
11 Rear grill 014730371 1
12 Capacitor CBB61 3301074704 1
13 Capacitor CBB65 3300008113 1
14 Terminal Board 42010265 1
15 Right Side Plate 01305095P 1
16 Handle 2623525404 1
17 Valve Support Sub-Assy 01713075 1
18 Cut-off valve Sub-Assy 07133491 1
19 Cut-off Valve 07130213 1
20 Capillary Sub-assy / /
21 4-Way Valve Assy 03073361 1
22 Compressor and Fittings 00103989 1
23 Chassis Sub-assy 01203826P 1
24 Valve Cover 22243003 1
25 Throttle Valve Sub-assy 03005500007 1
GWC24QE-K3NNA1E/O
24 23 22 21 20
26 25
27
28
29
19
30
18
17
16
15
14
1 2 3 4 5 6 7 8 9 10 11 12 13
The component picture is only for reference; please refer to the actual product.
Part Code
Description
No. GWC24QE-K3NNA1E/O Qty
Product Code CA419W15600
1 Front grill 22415002 1
2 Front Panel 01535013P 1
3 Chassis Sub-assy 01700000144P 1
4 Compressor and fittings 00103872 1
5 Overload Protector 00180299 1
6 Compressor Gasket 76711065 1
7 Discharge tube 2 03500800665 1
8 Inhalation Tube 03500600609 1
9 Right Side Plate 0130509402P 1
10 Valve Support Sub-Assy 01713098P 1
11 Cut-off valve Sub-Assy 07133170 1
12 Cut-off Valve 07130239 1
13 Handle 26233053 1
14 Terminal Board 42011113 1
15 AC Contactor 44010245 1
16 Capacitor CBB61 3301074705 1
17 Capacitor CBB65 3300008105 1
18 Electric Box Assy 10000202030 1
19 Capillary Sub-Assy / /
20 Rear Grill 01473061 1
21 Condenser Assy 01100200542 1
22 Supporting board(condenser) 01173127 1
23 Top Cover 01255005P 1
24 Clapboard Sub-Assy 01235027 1
25 Motor Support Sub-Assy 01703154 1
26 left handle 26233053 1
27 Fan Motor 1501506102 1
28 Left Side Plate 01305093P 1
29 Axial Flow Fan 10335008 1
30 Throttle Valve Sub-assy 03005500009 1
GWH24QE-K3NNA1E/O
26 25 24 23
28 27
29
30
31 22
21
32 20
19
18
17
16
15
1 2 3 4 5 6 7 8 9 33 10 11 12 13 14
The component picture is only for reference; please refer to the actual product.
Part Code
Description
No. GWH24QE-K3NNA1E/O Qty
Product Code CA419W15400
1 Front grill 22415002 1
2 Front Panel 01535013P 1
3 Drainage Plug 06813401 3
4 Drainage Connecter 06123401 1
5 Chassis Sub-assy 01700000020P 1
6 Compressor and fittings 00103872 1
7 Overload Protector / /
8 Compressor Gasket 76711065 3
9 4-way Valve Assy 03073385 1
10 Right Side Plate 01305094P 1
11 Valve Support Sub-Assy 01713098P 1
12 Cut-off valve Sub-Assy 07133170 1
13 Cut-off Valve 07133157 1
14 Handle 26233053 1
15 Terminal Board 42010194 1
16 AC Contactor 44010245 1
17 Terminal Board 42010194 1
18 Capacitor CBB61 3301074705 1
19 Capacitor CBB65 3300008105 1
20 Electric Box Assy 10000202032 1
21 Magnet Coil 4300040047 1
22 Capillary tube 81020167 1
23 Rear Grill 01473061 1
24 Condenser Assy 01100200422 1
25 Top Cover 01255005P 1
26 Supporting board(condenser) 01795010 1
27 Clapboard Sub-Assy 01235027 1
28 Motor Support Sub-Assy 01705036 1
29 left handle 26233053 1
30 Fan Motor 1501506102 1
31 Left Side Plate 01305093P 1
32 Axial Flow Fan 10335008 1
33 Throttle Valve Sub-assy 03005500011 1
Step Procedure
Groove
Step Procedure
Note:
1.Open the screw caps before removing
the screws around the air outlet.
2.The quantity of screws fixing the front
Front case
case sub-assy is different for different
sub-assy Screw caps
models.
Screw
Clasp
Bottom
b Loosen the connection clasps between
front case sub-assy and bottom case. Lift Front case
up the front case sub-assy and take it out. sub-assy
Vertical
louver
Clasps Vertical
louver
Step Procedure
Electric box
Shield cover of electric
box sub-assy
Indoor tube
temperature
① Remove the cold plasma generator by Cold plasma Screw sensor Electric box assy
b
generator
screwing off one locking screw on the
generator.
② Take off the indoor tube temperature
sensor.
③ Screw off one grounding screw.
④ Remove the wiring terminals of motor and Wiring
stepping motor. terminal
⑤ Remove the electric box assy. of motor
Grounding
screw Wiring
terminal
of stepping
motor
Screw
Main board
c Twist off the screws that are locking lead Power cord
wire and rotate the electric box assy.
Screw
Twist off the screws that are locking wire
clip.
Loosen the power cord and remove its wiring
terminal. Lift up the main board and take it
off. Wire clip
Screw
Wiring terminal of
temperature sensor
Step Procedure
Groove
Bottom shell
c First remove the left side of evaporator from
the groove of bottom shell and then remove
the right side from the clasp on the bottom
shell. Clasp
Evaporator assy
Connection pipe
Step Procedure
Motor clamp
Cross flow
b Remove the screws at the connection Screw
place of cross flow blade and motor; lift Holder Motor
the motor and cross flow blade upwards sub-assy
to remove them.
Remove the bearing holder sub-assy.
Remove the screw fixing step motor and
then remove the step motor.
Screws
Step motor
18/24K
NOTE: Take A1 panel for example.
1. Remove filter as s y
Front panel
A1/B6 A6 Display
2 2
S wing motor
Screw off the screws that are locking the
swing motor and take the motor off.
Indoor tube
Cut off the wire binder and pull out the temperature s ensor
indoor tube temperature sensor.
Screw off one grounding screw.
Main
Remove the wiring terminals of motor and
stepping motor. board
Remove the electric box assy. G rounding
Screw off the screws that are locking each s c rew Wi ring
lead wire. terminal
of motor
Wire binder
Wiring
terminal
of stepping
S crew motor
Wire clip
G roove
R ear case ass y
a Before disassembly.
front grille
front panel
electric box
isolation sheet
Remove the 3 screws fixing the isolation sheet.
Remove the isolation sheet.
gas valve
12.Remove compressor
discharge pipe
suction pipe
capillary
compressor
1. Before disassembly
Remove the connection screw fixing the big handle big handle
and then remove the handle.
front grille
front panel
motor
electric box
isolation sheet
soundproof sponge
compressor
Steps Procedure
1. Before disassembly
handle
valve cover
top panel
Remove screws fixing the top panel and
the grille respectively, and then remove the
top panel and the grille.
grille
Step Procedure
screw
screw
nut
Step Procedure
soundproof sponge
Step Procedure
solenoid coil
screw
compressor
Unsolder the pipes (including the soldering
a joint among the 4-way valve,the compressor
the condenser,the gas valve and the liquid
valve)connected to the compressor at rirst.
(NOTE:Berore unsoldering the joints,
discharge the refrigerant completely)
gas valve
liquid valve
nut
Step Procedure
isolation sheet
screw
GWC24QE-K3NNA1E/O GWH24QE-K3NNA1E/O
NOTE: Take GWH24QE-K3NNA1E/O for example.
Steps Procedure
a Before disassembly.
top panel
b Remove the screws connecting the top panel with
the front panel and the right side plate, and then
remove the top panel.
grille
Steps Procedure
panel
Steps Procedure
a Remove the nut fixing the blade and then remove the
axial flow blade. axial flow blade
nut
motor support
motor
Steps Procedure
7.Remove compressor
compressor
isolation sheet
Steps Procedure
support
condenser sub-assy
chassis sub-assy
Appendix:
Appendix 1: Reference Sheet of Celsius and Fahrenheit
Conversion formula for Fahrenheit degree and Celsius degree: Tf=Tcx1.8+32
Set temperature
Fahrenheit Fahrenheit Fahrenheit
display Fahrenheit display Fahrenheit display Fahrenheit
Celsius(℃) Celsius(℃) Celsius(℃)
temperature (℉) temperature (℉) temperature (℉)
(℉) (℉) (℉)
61 60.8 16 69/70 69.8 21 78/79 78.8 26
62/63 62.6 17 71/72 71.6 22 80/81 80.6 27
64/65 64.4 18 73/74 73.4 23 82/83 82.4 28
66/67 66.2 19 75/76 75.2 24 84/85 84.2 29
68 68 20 77 77 25 86 86 30
Ambient temperature
Fahrenheit Fahrenheit Fahrenheit
display Fahrenheit display Fahrenheit display Fahrenheit
Celsius(℃) Celsius(℃) Celsius(℃)
temperature (℉) temperature (℉) temperature (℉)
(℉) (℉) (℉)
32/33 32 0 55/56 55.4 13 79/80 78.8 26
34/35 33.8 1 57/58 57.2 14 81 80.6 27
36 35.6 2 59/60 59 15 82/83 82.4 28
37/38 37.4 3 61/62 60.8 16 84/85 84.2 29
39/40 39.2 4 63 62.6 17 86/87 86 30
41/42 41 5 64/65 64.4 18 88/89 87.8 31
43/44 42.8 6 66/67 66.2 19 90 89.6 32
45 44.6 7 68/69 68 20 91/92 91.4 33
46/47 46.4 8 70/71 69.8 21 93/94 93.2 34
48/49 48.2 9 72 71.6 22 95/96 95 35
50/51 50 10 73/74 73.4 23 97/98 96.8 36
52/53 51.8 11 75/76 75.2 24 99 98.6 37
54 53.6 12 77/78 77 25
Improper pipe expanding is the main cause of refrigerant leakage.Please Pipe cutter
expand the pipe according to the following steps:
Leaning Uneven Burr
A:Cut the pip
● Confirm the pipe length according to the distance of indoor unit and outdoor unit.
● Cut the required pipe with pipe cutter.
● Remove the burrs with shaper and prevent the burrs from getting into the pipe. Shaper
Downwards
C:Put on suitable insulating pipe
Smooth surface
F:Inspection
● Check the quality of expanding port. If there is any blemish, expand the
Improper expanding
port again according to the steps above.
Resistance Table of Tube Temperature Sensors for Outdoor and Indoor (20K)