Você está na página 1de 1

Design Wind Force on Panel Antenna

Shape of Panel Flat
Length of panel 2580 mm
Width of Panel 262 mm
Depth of Panel 116 mm
Antenna Mount Height Zh 17.13 m
Number of Panels 2
Azimuth Panel 1 0 °
Azimuth panel 2 60 °
Azimuth Panel 3 300 °
2.6.5.2 Velocity Pressure Coefficient Kz 0.84
Table 2‐5 Heigh Attenuation Factor f Not Applicable
2.6.6.4 Height Reductio Factor Kh Not Applicable
Table 2‐4 Terrain Constant Ke 0.9
Table 2‐5 Topographic Constant Kt Not Applicable
2.6.6.4 Topographic Factor Kzt 1.00
Table 2‐2 Wind direction probability factor Kd 0.95
Table 2‐3 Importance factor, I 1
2.6.9 Velocity Pressure qz 780.87 N/m2
Table 2‐8 Velocity Coefficient C 9.59
Table 2‐8 Force Coefficient for Flat Appurtenance Cf 1.49
2.6.9.2 Effective Projected area for Normal Face EPAN 1.01 m2
2.6.9.2 Effective Projected area for Side Face EPAT 0.45 m2
2.6.9.2 Shielding Factor for Appurtenances Ka 1
Design Wind force for 0° 1.37 kN
Design Wind force for 45° 1.46 kN
Design Wind force for 90° 1.13 kN
Design Wind force for 135° 1.04 kN
Design Wind force for 180° 1.37 kN
Design Wind force for 225° 1.46 kN
Design Wind force for 270° 1.13 kN
Design Wind force for 315° 1.04 kN

Design Wind Force on Mounts
Section of mounting pipe PIP 80x3
Type of Mount Dual Mount
Mount Shape Round
Length of mounting pipe 3 m
Diameter of mounting pipe 80 mm
2.6.9.2.1 Force Coefficient Ca Normal 1
Table 2‐8 Velocity Coefficient C 2.93
Table 2‐8. Force Coefficient Ca Side  1.2
2.6.9.2 Effective Projected area for Normal Face EPAN 0.07 m2
2.6.9.2 Effective Projected area for Side Face EPAT 0.48 m2
2.6.9.2 Shielding Factor for Appurtenances Ka 1
Orientation Mount 1 0 °
Orientation Mount 2 60 °
Orientation Mount 3 300 °
Design Wind force for 0° 0.38 kN
Design Wind force for 45° 0.32 kN
Design Wind force for 90° 0.56 kN
Design Wind force for 135° 0.62 kN
Design Wind force for 180° 0.38 kN
Design Wind force for 225° 0.32 kN
Design Wind force for 270° 0.56 kN
Design Wind force for 315° 0.62 kN

Você também pode gostar