Two-wire 4 … 20 mA/HART
Contents
1 About this document................................................................................................................ 4
1.1 Function............................................................................................................................ 4
1.2 Target group...................................................................................................................... 4
1.3 Symbols used................................................................................................................... 4
2 For your safety.......................................................................................................................... 5
2.1 Authorised personnel........................................................................................................ 5
2.2 Appropriate use................................................................................................................. 5
2.3 Warning about incorrect use.............................................................................................. 5
2.4 General safety instructions................................................................................................ 5
2.5 EU conformity.................................................................................................................... 6
2.6 NAMUR recommendations............................................................................................... 6
2.7 Radio licenses for Europe................................................................................................. 6
2.8 Radio approval for USA..................................................................................................... 7
2.9 Radio approval for Canada................................................................................................ 7
2.10 Installation and operation in the USA and Canada............................................................ 9
2.11 Security concept, Bluetooth operation............................................................................... 9
2.12 Environmental instructions................................................................................................ 9
3 Product description................................................................................................................ 10
3.1 Configuration................................................................................................................... 10
3.2 Principle of operation...................................................................................................... 12
3.3 Adjustment...................................................................................................................... 12
3.4 Packaging, transport and storage.................................................................................... 14
3.5 Accessories and replacement parts................................................................................ 14
4 Mounting.................................................................................................................................. 15
4.1 General instructions........................................................................................................ 15
4.2 Mounting versions........................................................................................................... 15
4.3 Mounting preparations, mounting strap........................................................................... 18
4.4 Mounting instructions...................................................................................................... 19
5 Connecting to power supply.................................................................................................. 26
5.1 Preparing the connection................................................................................................ 26
5.2 Wiring plan...................................................................................................................... 26
5.3 Switch-on phase............................................................................................................. 26
6 Setup with smartphone/tablet (Bluetooth)........................................................................... 28
6.1 Preparations.................................................................................................................... 28
6.2 Connecting...................................................................................................................... 28
6.3 Sensor parameter adjustment......................................................................................... 29
7 Setup with PC/notebook (Bluetooth).................................................................................... 30
7.1 Preparations.................................................................................................................... 30
7.2 Connecting...................................................................................................................... 30
7.3 Parameter adjustment..................................................................................................... 31
38061-EN-190404
used.
To avoid any danger, the safety approval markings and safety tips on
the device must also be observed and their meaning read in this oper-
ating instructions manual.
The low transmitting power of the radar sensor is far below the inter-
nationally approved limits. No health impairments are to be expected
with intended use. The band range of the transmission frequency can
be found in chapter "Technical data".
2.5 EU conformity
The device fulfils the legal requirements of the applicable EU direc-
tives. By affixing the CE marking, we confirm the conformity of the
instrument with these directives.
You can find the EU conformity declaration on our website under
www.vega.com/downloads.
This device has been approved for open air environments with the
following limitations:
• This device shall be installed and maintained to ensure a verti-
cally downward orientation of the transmit antenna's main beam.
Furthermore, the use of any mechanism that does not allow the
main beam of the transmitter to be mounted vertically downward is
prohibited.
• The installation of the LPR/TLPR device shall be done by trained
installers, in strict compliance with the manufacturer's instructions.
• This device shall be installed only at fixed locations. The LPR
device shall not operate while being moved or while inside a mov-
ing container.
• Hand-held applications are prohibited.
• Marketing to residential consumers is prohibited.
• The use of this device is on a "no-interference, no-protection"
basis. That is, the user shall accept operations of high-powered
radar in the same frequency band which may interfere with or
damage this device.
• However, devices found to interfere with primary licensing opera-
tions will be required to be removed at the user's expense.
Le présent appareil est conforme aux CNR d’Industrie Canada ap-
plicables aux appareils radio exempts de licence. L’exploitation est
autorisée aux conditions suivantes :
• L’appareil ne doit pas produire de brouillage; et
• L’utilisateur de l’appareil doit accepter tout brouillage radioélect-
rique subi, même si le brouillage est susceptible d’en compromet-
tre le fonctionnement.
Cet appareil est homologué pour une utilisation dans les environne-
ments ouverts avec les restrictions suivantes :
• L'appareil doit être installé et entretenu de manière à garantir une
orientation verticale vers le bas du faisceau principal de l’antenne
émettrice. De plus, l’utilisation de tout mécanisme ne permettant
pas l’orientation verticale vers le bas du faisceau principal de
l’émetteur est interdite
• L’installation d’un dispositif LPR ou TLPR doit être effectuée
par des installateurs qualifiés, en pleine conformité avec les
instructions du fabricant.
• Cet appareil ne doit être installé qu'à des emplacements fixes.
L’appareil LPR ne doit pas être utilisé pendant qu’il est en train
d’être déplacé ou se trouve dans un conteneur en mouvement.
• Les applications portables sont interdites.
• La vente à des particuliers est interdite
• Ce dispositif ne peut être exploité qu'en régime de non-brouillage
et de non-protection, c'est-à-dire que l'utilisateur doit accepter que
des radars de haute puissance de la même bande de fréquences
puissent brouiller ce dispositif ou même l'endommager.
38061-EN-190404
Authentication
When starting Bluetooth communication, an authentication is carried
out between sensor and adjustment device by means of the sensor
PIN. The sensor PIN is part of the respective sensor and must be
entered in the adjustment device (smartphone/tablet). To increase
adjustment convenience, this PIN is stored in the adjustment device.
This process is secured via an algorithm acc. to standard SHA 256.
3 Product description
3.1 Configuration
Scope of delivery The scope of delivery encompasses:
• Radar sensor
• Optionally integrated Bluetooth module
• Optional mounting accessory
• Documentation
–– Quick setup guide VEGAPULS WL 61
–– Supplement with sensor PIN
–– Instructions for optional instrument features
–– Ex-specific "Safety instructions" (with Ex versions)
–– If necessary, further certificates
Information:
Optional instrument features are also described in this operating
instructions manual. The respective scope of delivery results from the
order specification.
Scope of this operating This operating instructions manual applies to the following instrument
instructions versions:
• Hardware version from 1.0.0
• Software version from 4.5.3
Type label You can find the type label on the sensor housing as well as on the
type label support on the connection cable.
It contains the most important data for identification and use of the
instrument.
38061-EN-190404
1 16
2
3 15
4
14
5
6
13
7
8 12
9
10 11
Serial number - Instru- The type label contains the serial number of the instrument. With it
ment search you can find the following instrument data on our homepage:
• Product code (HTML)
• Delivery date (HTML)
• Order-specific instrument features (HTML)
• Operating instructions and quick setup guide at the time of ship-
ment (PDF)
• Order-specific sensor data for an electronics exchange (XML)
• Test certificate (PDF) - optional
Move to "www.vega.com" and enter in the search field the serial
number of your instrument.
Alternatively, you can access the data via your smartphone:
• Download the VEGA Tools app from the "Apple App Store" or the
"Google Play Store"
• Scan the Data Matrix code on the type label of the instrument or
• Enter the serial number manually in the app
38061-EN-190404
Sensor PIN The 4-digit PIN is necessary for the Bluetooth connection to the sen-
sor. The PIN is unique and is only valid of this sensor.
You can find the PIN:
XXXX
Functional principle The antenna of the radar sensor emits short radar pulses with a
duration of approx. 1 ns. These pulses are reflected by the product
and received by the antenna as echoes. The transit time of the radar
pulses from emission to reception is proportional to the distance and
hence to the level. The determined level is converted into an appropri-
ate output signal and outputted as measured value.
3.3 Adjustment
Adjustment via the signal The VEGAPULS WL 61 can be operated by default:
cable
• External display and adjustment unit VEGADIS 82
• PC/notebook with adjustment software PACTware
38061-EN-190404
• DD adjustment programs
• Field Communicator 375, 475
4
3
1
Fig. 4: Connection of the VEGADIS 82 to the sensor, adjustment via the display
and adjustment module
1 Voltage supply/Signal output sensor
2 VEGADIS 82
3 Display and adjustment module
4 4 … 20 mA/HART signal cable
5 Sensor
1
4
3
38061-EN-190404
Transport Transport must be carried out in due consideration of the notes on the
transport packaging. Nonobservance of these instructions can cause
damage to the device.
Transport inspection The delivery must be checked for completeness and possible transit
damage immediately at receipt. Ascertained transit damage or con-
cealed defects must be appropriately dealt with.
Storage Up to the time of installation, the packages must be left closed and
stored according to the orientation and storage markings on the
outside.
Unless otherwise indicated, the packages must be stored only under
the following conditions:
• Not in the open
• Dry and dust free
• Not exposed to corrosive media
• Protected against solar radiation
• Avoiding mechanical shock and vibration
Storage and transport • Storage and transport temperature see chapter "Supplement -
temperature Technical data - Ambient conditions"
• Relative humidity 20 … 85 %
Lifting and carrying With instrument weights of more than 18 kg (39.68 lbs) suitable and
approved equipment must be used for lifting and carrying.
4 Mounting
4.1 General instructions
Process conditions Note:
For safety reasons, the instrument must only be operated within the
permissible process conditions. You can find detailed information on
the process conditions in chapter "Technical data" as well as on the
type label.
Make sure before mounting that all parts of the instrument exposed to
the process are suitable for the existing process conditions.
These are mainly:
• Active measuring component
• Process fitting
• Process seal
Process conditions in particular are:
• Process pressure
• Process temperature
• Chemical properties of the medium
• Abrasion and mechanical influences
You can find detailed information on the materials and process condi-
tions in chapter "Technical data" as well as on the type label.
> 200 mm
(7.87")
Mounting bracket For a rigid mounting, a mounting bracket with opening for thread
G1½, e.g. from the VEGA product range, is recommended. The
mounting of the sensor in the bracket is carried out via a G1½ counter
nut of plastic. Take note of chapter "Mounting instructions" for the
distance to the wall.
> 200 mm
(7.87")
Mounting strap The optional mounting strap enables sensor mounting on e.g. a ceil-
ing, wall or bracket. It is available in the following versions:
• Length 300 mm for ceiling mounting
• Length 170 mm for wall mounting
Mounting strap - Ceiling The instrument is normally mounted vertically with a bracket on the
mounting ceiling.
This ensures swivelling of the sensor up to 180° for optimum orienta-
tion.
Fig. 8: Ceiling mounting via the mounting strap with length 300 mm
Mounting strap - Wall As an alternative the strap mounting is carried out horizontally or
mounting obliquely.
> 200 mm
38061-EN-190404
(7.87")
Fig. 10: Wall mounting via the mounting strap with length 170 mm
Fig. 11: Wall mounting with inclined wall via the mounting strap with length
300 mm
Fig. 12: Mounting by means of an adapter flange, for example, on a manhole lid.
1 2
Fig. 13: Mounting strap for screwing to the sensor
1 For angle of inclination in steps
2 For angle of inclination, infinitely variable
Tight installation of the For tight installation of the version with plastic horn antenna with com-
plastic horn antenna pression or adapter flange, the following conditions must be fulfilled:
1. Use suitable flat seal, e.g. of EPDM with Shore hardness 25 or 50
Polarisation The emitted radar impulses of the radar sensor are electromagnetic
waves. The polarisation is the direction of the electrical wave compo-
nent. By turning the instrument in the connection flange or mounting
strap, the polarisation can be used to reduce the effects of false
echoes.
The position of the polarisation is marked by marking bars on the
instrument.
Fig. 16: Position of the polarisation, marked by marking bars on the instrument.
1 Marking bar
Installation position When mounting the sensor, keep a distance of at least 200 mm
(7.874 in) to the vessel wall. If the sensor is installed in the center of
dished or round vessel tops, multiple echoes can arise. These can,
however, be suppressed by an appropriate adjustment (see chapter
"Setup").
If you cannot maintain this distance, you should carry out a false
signal suppression during setup. This applies particularly if buildup on
the vessel wall is expected. In such cases, we recommend repeating
the false signal suppression at a later date with existing buildup.
38061-EN-190404
> 200 mm
(7.87")
Fig. 18: Mounting of the radar sensor on vessels with conical bottom
Inflowing medium Do not mount the instrument in or above the filling stream. Make sure
that you detect the product surface, not the inflowing product.
38061-EN-190404
Mounting socket Approximate values of the socket heights are shown in the following
illustration. The socket end should be smooth and burr-free, if possi-
ble also rounded. After mounting, you have to carry out a false signal
suppression during the parameter adjustment.
h
The below charts specify the max. pipe socket length h depending on
the diameter d.
Socket diameter d Socket length h
80 mm ≤ 300 mm
100 mm ≤ 400 mm
150 mm ≤ 500 mm
3" ≤ 11.8 in
4" ≤ 15.8 in
6" ≤ 19.7 in
Sensor orientation Direct the sensor as perpendicular as possible to the product surface
to achieve optimum measurement results.
Vessel installations The mounting location of the radar sensor should be a place where no
other equipment or fixtures cross the path of the radar signals.
Vessel installations, such as e.g. ladders, limit switches, heating spi-
rals, struts, etc., can cause false echoes and impair the useful echo.
Make sure when planning your measuring point that the radar sensor
has a "clear view" to the measured product.
In case of existing vessel installations, a false signal suppression
should be carried out during setup.
If large vessel installations such as struts or supports cause false
echoes, these can be attenuated through supplementary measures.
Small, inclined sheet metal baffles above the installations scatter the
radar signals and prevent direct interfering reflections.
Foam generation Through the action of filling, stirring and other processes in the vessel,
compact foam can form on the product surface, damping the emitted
signals considerably.
If foams are causing measurement errors, the biggest possible radar
antennas, the electronics with increased sensitivity or low frequency
radar sensors (C band) should be used.
As an alternative, sensors with guided microwave can be used. These
are unaffected by foam generation and are best suited for such ap-
plications.
Flow measurement with The short examples give you introductory information on flow
38061-EN-190404
3 ... 4 hmax 1
90°
90°
hmax
≥ 2 x hmax
2 3 4
Fig. 23: Flow measurement with rectangular overfall: dmin. = min. distance of
the sensor (see chapter "Technical data"); hmax. = max. filling of the rectangular
spillway
1 Overflow orifice (side view)
2 Headwater
3 Tailwater
4 Overfall orifice (view from tailwater)
3 ... 4 x hmax
90°
hmax
1 B
38061-EN-190404
Fig. 24: Flow measurement with Khafagi-Venturi flume: hmax. = max. filling of the
flume; B = tightest constriction in the flume
1 Position sensor
2 Venturi flume
Warning:
Only connect or clamp in a de-energized state.
Voltage supply Power supply and current signal are carried on the same two-wire
cable. The operating voltage can differ depending on the instrument
version.
The data for power supply are specified in chapter "Technical data".
Provide a reliable separation between the supply circuit and the
mains circuits according to DIN EN 61140 VDE 0140-1.
Power the instrument via an energy-limited circuit acc. to IEC 61010-
1, e.g. via Class 2 power supply unit.
Keep in mind the following additional factors that influence the operat-
ing voltage:
• Lower output voltage of the power supply unit under nominal load
(e.g. with a sensor current of 20.5 mA or 22 mA in case of fault)
• Influence of additional instruments in the circuit (see load values in
chapter "Technical data")
Connection cable The instrument is connected with standard two-wire cable. If electro-
magnetic interference is expected which is above the test values of
EN 61326-1 for industrial areas, screened cable should be used.
Screened cable generally necessary in HART multidrop mode.
2
Fig. 25: Wire assignment in permanently connected connection cable
1 Brown (+) and blue (-) to power supply or to the processing system
2 Shielding
38061-EN-190404
6.2 Connecting
Connecting … Start the "VEGA Tools" app and select the function "Setup". The
smartphone/tablet searches automatically for Bluetooth-capable
instruments in the area.
The message "Searching …" is displayed.
The found instruments will be listed on the left side of the adjustment
window. The search is continued automatically.
Select the requested instrument in the device list.
The message "Connecting …" is displayed.
Authenticate For the first connection, the operating device and the sensor must
authenticate each other. After successful authentication, the next con-
nection functions without authentication.
iOS
During the pairing process, the following message is displayed: "Pair-
ing request (Bluetooth), e.g. 12345678 wants to pair with your iPad".
Press "Pair".
Android
The coupling passes through automatically.
Enter PIN For authentication, enter in the next menu window the 4-digit PIN.
You can find the PIN:
• Next to the type label on the connection cable
• On the supplement to the documentation
Note:
38061-EN-190404
Change sensor PIN It is recommended to change the default setting of the sensor PIN to
your own sensor PIN. To do this, go to the menu item "Lock adjust-
ment".
After the sensor PIN has been changed, sensor adjustment can be
enabled again. For access (authentication) with Bluetooth, the PIN is
still effective.
Enter the requested parameters and confirm via the keyboard or the
editing field. The settings are then active in the sensor.
Close the app to terminate connection.
38061-EN-190404
Activate Bluetooth con- Activate the Bluetooth connection via the VEGA project assistant.
nection
Note:
Older systems do not always have an integrated Bluetooth LE. In
these cases, a Bluetooth USB adapter is required.
Activate the Bluetooth USB adapter via the VEGA project assistant
(see supplementary instructions "Bluetooth USB adapter").
After activating the integrated Bluetooth or the Bluetooth USB adapt-
er, devices with Bluetooth are found and created in the project tree.
7.2 Connecting
Connecting … Select the requested device for the online parameter adjustment in
the project tree.
Enter PIN For authentication, enter in the next menu window the 4-digit PIN.
You can find the PIN:
• Next to the type label on the connection cable
• On the supplement to the documentation
38061-EN-190404
Note:
If an incorrect sensor PIN is entered, the PIN can only be entered
again after a delay time. This time gets longer after each incorrect
entry.
Change sensor PIN It is recommended to change the default setting of the sensor PIN to
your own sensor PIN. To do this, go to the menu "Additional adjust-
ments", menu item "PIN".
4
3
1
Fig. 28: Connection of the VEGADIS 82 to the sensor, adjustment via the dis-
play and adjustment module
1 Voltage supply/Signal output sensor
2 VEGADIS 82
3 Display and adjustment module
4 4 … 20 mA/HART signal cable
5 Sensor
38061-EN-190404
CK
LO
TWIST
USB
3
N
OPE
1
5
Fig. 30: Connecting the PC to the signal cable
1 Sensor
2 HART resistance 250 Ω (optional depending on evaluation)
3 Connection cable with 2 mm pins and terminals
4 Processing system/PLC/Voltage supply
5 Interface adapter VEGACONNECT
Note:
With power supply units with integrated HART resistance (internal
resistance approx. 250 Ω), an additional external resistance is not
necessary. This applies, e.g. to the VEGA instruments VEGATRENN
149A, VEGAMET 381, VEGAMET 391. Common Ex separators are
also usually equipped with a sufficient current limiting resistance. In
such cases, the interface converter can be connected parallel to the
4 … 20 mA cable (dashed line in the previous illustration).
38061-EN-190404
1
2
2 on
1
TWIST
VEGAMET 381
LO
EN
CK
OP
USB 4
Standard/Full version All device DTMs are available as a free-of-charge standard version
and as a full version that must be purchased. In the standard version,
all functions for complete setup are already included. An assistant for
simple project configuration simplifies the adjustment considerably.
Saving/printing the project as well as import/export functions are also
part of the standard version.
In the full version there is also an extended print function for complete
project documentation as well as a save function for measured value
and echo curves. In addition, there is a tank calculation program as
well as a multiviewer for display and analysis of the saved measured
value and echo curves.
The standard version is available as a download under
www.vega.com/downloads and "Software". The full version is avail-
able on CD from the agency serving you.
38061-EN-190404
Cleaning The cleaning helps that the type label and markings on the instrument
are visible.
Take note of the following:
• Use only cleaning agents which do not corrode the housings, type
label and seals
• Use only cleaning methods corresponding to the housing protec-
tion rating
Measured value memory Up to 100,000 measured values can be stored in the sensor in a ring
memory. Each entry contains date/time as well as the respective
measured value. Storable values are for example:
• Distance
• Filling height
• Percentage value
• Lin. percent
• Scaled
• Current value
• Measurement reliability
• Electronics temperature
When the instrument is shipped, the measured value memory is
active and stores distance, measurement reliability and electronics
temperature every 3 minutes.
The requested values and recording conditions are set via a PC with
PACTware/DTM or the control system with EDD. Data are thus read
out and also reset.
Event memory Up to 500 events are automatically stored with a time stamp in the
sensor (non-deletable). Each entry contains date/time, event type,
event description and value. Event types are for example:
• Modification of a parameter
• Switch-on and switch-off times
• Status messages (according to NE 107)
• Error messages (according to NE 107)
38061-EN-190404
The data are read out via a PC with PACTware/DTM or the control
system with EDD.
Echo curve memory The echo curves are stored with date and time and the corresponding
echo data. The memory is divided into two sections:
Echo curve of the setup: This is used as reference echo curve for
the measurement conditions during setup. Changes in the measure-
ment conditions during operation or buildup on the sensor can thus
be recognized. The echo curve of the setup is stored via:
• PC with PACTware/DTM
• Control system with EDD
• Display and adjustment module
Further echo curves: Up to 10 echo curves can be stored in a ring
buffer in this memory section. Additional echo curves are stored via:
• PC with PACTware/DTM
• Control system with EDD
Status messages The status messages are divided into the following categories:
• Failure
• Function check
• Out of specification
• Maintenance requirement
and explained by pictographs:
1 2 3 4
Fig. 33: Pictographs of the status messages
1 Failure - red
2 Out of specification - yellow
3 Function check - orange
4 Maintenance - blue
F025 Index markers are not continu- Check linearisation table Bit 2 of Byte 0 … 5
Error in the lineari- ously rising, for example illogical Delete table/Create new
zation table value pairs
F036 Failed or interrupted software up- Repeat software update Bit 3 of Byte 0 … 5
No operable soft- date Check electronics version
ware Exchanging the electronics
Send instrument for repair
F040 Hardware defect Exchanging the electronics Bit 4 of Byte 0 … 5
Error in the elec- Send instrument for repair
tronics
F080 General software error Disconnect operating voltage Bit 5 of Byte 0 … 5
briefly
F105 The instrument is still in the start Wait for the end of the switch-on Bit 6 of Byte 0 … 5
Determine meas- phase, the measured value could phase
ured value not yet be determined Duration up to approx. 3 min.
depending on the version and pa-
rameter settings
F113 EMC interference Remove EMC influences Bit 12 of Byte 0 … 5
Communication Transmission error during external Exchange 4-wire power supply
error communication with 4-wire power unit or electronics
supply unit
F125 Temperature of the electronics in Check ambient temperature Bit 7 of Byte 0 … 5
Impermissible elec- the non-specified range Insulate electronics
tronics temperature Use instrument with higher tem-
perature range
F260 Error in the calibration carried out Exchanging the electronics Bit 8 of Byte 0 … 5
Error in the cali- in the factory Send instrument for repair
38061-EN-190404
Tab. 3: Error codes and text messages, information on cause and rectification (some specifications are only valid
for four-wire instruments, the electronics of VEGAPULS WL 61 cannot be replaced by the user)
Function check
Code Cause Rectification DevSpec
Text message State in CMD 48
C700 A simulation is active Finish simulation "Simulation Active"
Simulation active Wait for the automatic end after in "Standardized
60 mins. Status 0"
Out of specification
Code Cause Rectification DevSpec
Text message State in CMD 48
S600 Temperature of the electronics in Check ambient temperature Bit 5 of
Impermissible elec- the non-specified range Insulate electronics Byte 14 … 24
tronics temperature Use instrument with higher tem-
perature range
S601 Danger of vessel overfilling Make sure that there is no fur- Bit 6 of
Overfilling ther filling Byte 14 … 24
Check level in the vessel
Tab. 5: Error codes and text messages, information on causes as well as corrective measures
Maintenance
Code Cause Rectification DevSpec
Text message State in CMD 48
M500 The data could not be restored Repeat reset Bit 0 of
Error during the re- during the reset to delivery status Load XML file with sensor data in- Byte 14 … 24
set "delivery status" to the sensor
M501 Hardware error EEPROM Exchanging the electronics Bit 1 of
Error in the non- Send instrument for repair Byte 14 … 24
active linearisation
table
38061-EN-190404
Tab. 6: Error codes and text messages, information on causes as well as corrective measures
Level
1
2
0 time
1 Real level
2 Level displayed by the sensor
Note:
If the output level is constant, the cause could also be the fault setting
of the current output to "Hold value".
If the level is too low, the reason could be a line resistance that is too
high
hence running time error (small measure- to vessel form, adapt if necessary (bypass,
ment error close to 100 %/large error close standpipe, diameter).
0 time
to 0 %)
2. Measured value Multiple echo (vessel top, product surface) Check parameter "Application", especially
jumps towards 0 % with amplitude higher than the level echo vessel top, type of medium, dished bottom,
high dielectric constant, and adapt if nec-
Level
essary.
0 time
3. Measured val- Due to the process, the amplitude of the lev- Carry out a false signal suppression
ue jumps towards el echo sinks
100 % A false signal suppression was not car-
ried out
Level
Amplitude or position of a false signal has Determine the reason for the changed false
changed (e.g. condensation, buildup); false signals, carry out false signal suppression,
signal suppression no longer matches ac- e.g. with condensation.
0 time
tual conditions
38061-EN-190404
0 time
6. Measured value Turbulence on the product surface, quick Check parameters, change if necessary,
remains momentar- filling e.g. in dosing vessel, reactor
ily unchanged during
filling and then jumps
to the correct level
Level
0 time
7. Measured value Amplitude of a multiple echo (vessel top Check parameter "Application", especially
jumps towards 0 % - product surface) is larger than the lev- vessel top, type of medium, dished bottom,
during filling el echo high dielectric constant, and adapt if nec-
essary.
Level
The level echo cannot be distinguished from In case of interferences due to installations
the false signal at a false signal position in the close range: Change polarisation di-
0 time (jumps to multiple echo) rection
Chose a more suitable installation position
8. Measured val- Due to strong turbulence and foam genera- Carry out a false signal suppression
ue jumps towards tion during filling, the amplitude of the level
100 % during filling echo sinks. Measured value jumps to false
signal
Level
0 time
9. Measured value Varying condensation or contamination on Carry out a false signal suppression or
jumps sporadically to the antenna increase false signal suppression with con-
100 % during filling densation/contamination in the close range
38061-EN-190404
by editing.
Level
0 time
0 time
13. Measured value Varying condensation or contamination on Carry out false signal suppression or in-
jumps sporadically the antenna crease false signal suppression in the close
towards 100 % dur- range by editing
ing emptying With bulk solids, use radar sensor with
purging air connection
Level
0 time
Reaction after fault recti- Depending on the reason for the fault and the measures taken, the
fication steps described in chapter "Setup" must be carried out again or must
be checked for plausibility and completeness.
24 hour service hotline Should these measures not be successful, please call in urgent cases
the VEGA service hotline under the phone no. +49 1805 858550.
The hotline is also available outside normal working hours, seven
days a week around the clock.
38061-EN-190404
12 Dismount
12.1 Dismounting steps
Warning:
Before dismounting, be aware of dangerous process conditions such
as e.g. pressure in the vessel or pipeline, high temperatures, cor-
rosive or toxic products etc.
Take note of chapters "Mounting" and "Connecting to voltage supply"
and carry out the listed steps in reverse order.
12.2 Disposal
The instrument consists of materials which can be recycled by spe-
cialised recycling companies. We use recyclable materials and have
designed the electronics to be easily separable.
WEEE directive
The instrument does not fall in the scope of the EU WEEE directive.
Article 2 of this Directive exempts electrical and electronic equipment
from this requirement if it is part of another instrument that does not
fall in the scope of the Directive. These include stationary industrial
plants.
Pass the instrument directly on to a specialised recycling company
and do not use the municipal collecting points.
If you have no way to dispose of the old instrument properly, please
contact us concerning return and disposal.
38061-EN-190404
13 Supplement
13.1 Technical data
Note for approved instruments
The technical data in the respective safety instructions are valid for approved instruments (e.g. with
Ex approval). These data can differ from the data listed herein, for example regarding the process
conditions or the voltage supply.
General data
Materials, wetted parts
ƲƲ Adapter flange PP-GF30 black
ƲƲ Seal, adapter flange FKM (COG VI500), EPDM (COG AP310)
ƲƲ Focussing lense PP
Materials, non-wetted parts
ƲƲ Antenna cone PBT-GF 30
ƲƲ Compression flange PP-GF30 black
ƲƲ Mounting strap 316L
ƲƲ Fixing screws, mounting strap 316L
ƲƲ Fixing screws, adapter flange 304
ƲƲ Housing Plastic PBT (Polyester)
ƲƲ Connection cable PUR
ƲƲ Type label support on cable PE hard
Instrument weight, depending on pro- 0.7 … 3.4 kg (1.543 … 7.496 lbs)
cess fitting
Weight, connection cable 0.1 kg/m (0.07 lbs/ft)
Torques
Max. torques
ƲƲ Mounting screws, mounting strap on 4 Nm (2.950 lbf ft)
sensor housing
ƲƲ Flange screws, compression flange 5 Nm (3.689 lbf ft)
DN 80
ƲƲ Terminal screws, adapter flange - 2.5 Nm (1.844 lbf ft)
antenna
ƲƲ Flange screws, adapter flange DN 100 7 Nm (5.163 lbf ft)
Input variable
Measured variable The measured quantity is the distance between the
end of the sensor antenna and the product surface. The
reference plane for the measurement is the lower side of
the flange.
38061-EN-190404
3
1
2
4
Output variable
Output signal 4 … 20 mA/HART
Range of the output signal 3.8 … 20.5 mA/HART (default setting)
Signal resolution 0.3 µA
Resolution, digital 1 mm (0.039 in)
Fault signal, current output (adjustable) mA-value unchanged 20.5 mA, 22 mA, < 3.6 mA
Max. output current 22 mA
Load See load resistance under Power supply
Starting current ≤ 3.6 mA; ≤ 10 mA for 5 ms after switching on
Damping (63 % of the input variable), 0 … 999 s
adjustable
HART output values according to HART 7.01)
ƲƲ PV (Primary Value) Distance
ƲƲ SV (Secondary Value) Percent
ƲƲ TV (Third Value) Lin. percent
ƲƲ QV (Fourth Value) Scaled
Fulfilled HART specification 7.0
Further information on Manufacturer ID, See website of HART Communication Foundation
Device ID, Device Revision
1)
Default values can be assigned individually.
10 mm (0.394 in)
2 mm (0.079 in)
0
- 2 mm (- 0.079 in)
1 2 3
Fig. 35: Deviation under reference conditions
1 Reference plane
2 Antenna edge
3 Recommended measuring range
2)
Already included in the meas. deviation
3)
Time span after a sudden distance change of max. 0.5 m until the output signal reaches for the first time 90% of
the final value (IEC 61298-2).
Ambient conditions
Ambient, storage and transport tempera- -40 … +80 °C (-40 … +176 °F)
ture
Process conditions
For the process conditions, please also note the specifications on the type label. The lower value
always applies.
Vessel pressure -1 … 2 bar (-100 … 200 kPa/-14.5 … 29.0 psig)
Process temperature (measured on the -40 … +80 °C (-40 … +176 °F)
process fitting)
Vibration resistance
ƲƲ With adapter flange 2 g at 5 … 200 Hz according to EN 60068-2-6 (vibration
with resonance)
ƲƲ with mounting strap 1 g at 5 … 200 Hz according to EN 60068-2-6 (vibration
with resonance)
Shock resistance 100 g, 6 ms according to EN 60068-2-27 (mechanical
shock)
4)
Outside the specified beam angle, the energy level of the radar signal is 50% (-3 dB) less.
5)
EIRP: Equivalent Isotropic Radiated Power
Integrated clock
Date format Day.Month.Year
Time format 12 h/24 h
Time zone, factory setting CET
Max. rate deviation 10.5 min/year
Bluetooth interface
Standard Bluetooth smart
Effective range6) 25 m (82.02 ft)
Voltage supply
Operating voltage
ƲƲ Non-Ex instrument 9.6 … 35 V DC
ƲƲ Non-Ex device - Bluetooth 11.6 … 35 V DC
ƲƲ Ex-ia instrument 9.6 … 30 V DC
ƲƲ Ex-ia device - Bluetooth 11.6 … 30 V DC
Reverse voltage protection Integrated
Permissible residual ripple - Non-Ex, Ex-ia instrument
ƲƲ for 9.6 V < UN < 14 V ≤ 0.7 Veff (16 … 400 Hz)
ƲƲ for 18 V < UN < 36 V ≤ 1 Veff (16 … 400 Hz)
Load resistor
ƲƲ Calculation (UB - Umin)/0.022 A
ƲƲ Example - Non-Ex instrument with (24 V - 9.6 V)/0.022 A = 655 Ω
UB= 24 V DC
6)
Depending on the local conditions
7)
Galvanic separation between electronics and metal housing parts
Approvals
Instruments with approvals can have different technical specifications depending on the version.
For that reason the associated approval documents of these instruments have to be carefully
noted. They are part of the delivery or can be downloaded by entering the serial number of your
instrument into the search field under www.vega.com as well as in the general download area.
13.3 Dimensions
The following dimensional drawings represent only an extract of all possible versions. Detailed
dimensional drawings can be downloaded at www.vega.com/downloads under "Drawings".
G1 1/2
42,5 mm
ø 8 mm
(1.67")
18,5 mm (0.32")
(0.73")
ø 72 mm
(2.84")
300 mm
(11.81")
19 mm
(0.75")
ø 75 mm
15 mm
(0.59")
(2.95")
ø 115 mm
(4.53")
125 mm
(4.92")
2,5 mm
(0.10")
300 mm
(11.81")
170 mm
98 mm
(3.86")
(6.69")
19 mm
(0.75")
8,5 mm
(0.34")
75 mm
15 mm
(0.59")
(2.95")
107 mm
9 mm (4.21")
12 mm
(0.47")
(0.35") 115 mm
(4.53")
85 mm
(3.35")
(0.35")
9 mm
12 mm
(0.47")
38061-EN-190404
Fig. 37: VEGAPULS WL 61, version with mounting strap in 170 or 300 mm length
126 mm
(4.96")
10,5 mm
(0.41")
ø 21 mm
(0.83")
19 mm
(0.75")
ø 156 mm
(6.14")
ø 200 mm
(7.87")
138 mm (5.43")
1
31 mm
(1.22")
15 mm
(0.59")
20 mm
(0.79")
(0.32")
ø 98 mm (3.86") 8 mm
Fig. 39: VEGAPULS WL 61, adapter flange DN 100, 4" (JIS 100), DN 150, 6" (JIS 150)
1 Adapter flange
2 Seal
38061-EN-190404
13.6 Trademark
All the brands as well as trade and company names used are property of their lawful proprietor/
originator.
38061-EN-190404
INDEX
A S
Application area 12 Sensor orientation 23
Sensor PIN 11
C Service hotline 46
Check output signal 43
Connection cable 26 V
Vessel installations 23
D
Deviation 44
E
EDD (Enhanced Device Description) 38
Error codes 42
Event memory 39
F
Fault
––Rectification 43
Fault rectification 43
Flow measurement
––Khafagi-Venturi flume 24
––Rectangular overfall 23
Foam generation 23
H
HART resistance 35
I
Inflowing medium 21
Installation position 20
M
Measured value memory 39
Mounting
––Angle 16
––Flange 18
––Straining clamp 15
––Strap 16
Mounting socket 22
N
NAMUR NE 107 40, 42
––Failure 41
P
38061-EN-190404
Polarisation 20
R
Repair 47
38061-EN-190404
38061-EN-190404
All statements concerning scope of delivery, application, practical use and operat-
ing conditions of the sensors and processing systems correspond to the information
available at the time of printing.
Subject to change without prior notice