Você está na página 1de 42

63249-401-206/A3

June 2005
Instruction Bulletin LaVergne, TN, USA

POWERLINK® G3 Controller
With Metasys® N2 Communications Protocol

Retain for future use.


NOTICE Read these instructions carefully and look at the equipment to become familiar
with the device before trying to install, operate, service, or maintain it. The
following special messages may appear throughout this bulletin or on the
equipment to warn of potential hazards or to call attention to information that
clarifies or simplifies a procedure.
The addition of either symbol to a “Danger” or “Warning” safety label indicates
that an electrical hazard exists which will result in personal injury if the
instructions are not followed.
This is the safety alert symbol. It is used to alert you to potential personal injury
hazards. Obey all safety messages that follow this symbol to avoid possible injury
or death.

DANGER
DANGER indicates an imminently hazardous situation which, if not
avoided, will result in death or serious injury.

WARNING
WARNING indicates a potentially hazardous situation which, if not
avoided, can result in death or serious injury.

CAUTION
CAUTION indicates a potentially hazardous situation which, if not
avoided, can result in minor or moderate injury.

CAUTION
CAUTION, used without the safety alert symbol, indicates a potentially
hazardous situation which, if not avoided, can result in property damage.

NOTE: Provides additional information to clarify or simplify a procedure.

PLEASE NOTE Electrical equipment should be installed, operated, serviced, and maintained only
by qualified personnel. This document is not intended as an instruction manual
for untrained persons. No responsibility is assumed by Schneider Electric for any
consequences arising out of the use of this manual.

CLASS A FCC STATEMENT This equipment has been tested and found to comply with the limits for a Class A
digital device, pursuant to part 15 of the FCC Rules. These limits are designated
to provide reasonable protection against harmful interference when the
equipment is operated in a commercial environment. This equipment generates,
uses, and can radiate radio frequency energy and, if not installed and used in
accordance with the instruction manual, may cause harmful interference to radio
communications. Operation of this equipment in a residential area is likely to
cause harmful interference in which case the user will be required to correct the
interference at his own expense.

U.S. PATENT STATEMENT The products described herein are protected under one or more of the following
U.S. Patents: 4,901,219; 4,964,058; 5,028,853; 4,940,903; 4,623,859;
4,965,694; D317,906; 5,083,103; 5,180,051; 5,184,278; 5,231,565; 5,233,511;
5,249,115; 5,253,159; 5,315,499; 5,323,307; 5,455,760; 5,532,660; 5,892,449;
5,909,180; and 6,055,144. Additional patents pending.
Metasys® is a registered trademark of Johnson Controls.

© 2005 Schneider Electric All Rights Reserved


63249-401-206/A3 Table of Contents
June 2005

TABLE OF CONTENTS CHAPTER 1—INTRODUCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1


CONTENTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
INTRODUCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
STANDARD FEATURES. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
METASYS N2 FEATURES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
BEFORE YOU BEGIN . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
USING WITH PCS SOFTWARE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
TECHNICAL SUPPORT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3

CHAPTER 2—SAFETY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5

CHAPTER 3—INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
CONTENTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
INSTALLING THE CONTROLLER . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
N2 NETWORK WIRING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Grounding. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
NETWORK RECOMMENDATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8

CHAPTER 4—OPERATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
CONTENTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
OPERATION OVERVIEW . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
ZONE PRIORITY. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
TIME SYNCHRONIZATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
N2 MODE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
POINT TYPES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Physical and Logical Inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Control Bus Status . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Control Bus Address Identification . . . . . . . . . . . . . . . . . . . . . . 13
Zone Control. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Input Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Time Schedules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16

CHAPTER 5—CONFIGURATION OVERVIEW . . . . . . . . . . . . . . . . . . . 17


CONTENTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
INTRODUCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
BEFORE YOU BEGIN . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
POWERLINK CONFIGURATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
METASYS CONFIGURATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
NCM SCHEDULE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
POWERLINK G3 SCHEDULE. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20

APPENDIX A—NF1000G3N2 POINT MAP . . . . . . . . . . . . . . . . . . . . . . 21

© 2005 Schneider Electric All Rights Reserved i


Table of Contents 63249-401-206/A3
June 2005

ii © 2005 Schneider Electric All Rights Reserved


63249-401-206/A3 Chapter 1—Introduction
June 2005 Contents

CHAPTER 1—INTRODUCTION

CONTENTS CONTENTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
INTRODUCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
STANDARD FEATURES. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
METASYS N2 FEATURES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
BEFORE YOU BEGIN . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
USING WITH PCS SOFTWARE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
TECHNICAL SUPPORT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3

INTRODUCTION The POWERLINK G3 NF1000G3N2 controller provides a data interface to


Johnson Controls equipment using the Metasys® N2 Open Protocol. The
controller connects a POWERLINK G3-equipped panel to the N2 network,
eliminating the need for a Metasys Integrator for data conversion.
POWERLINK G3 remotely operable circuit breakers, grouped into lighting
zones, are commanded as a single binary output (BO) point. A low-voltage
wall switch, connected to the controller’s wiring compartment, can be used to
provide local control of the lighting zone. A maximum of 16 physical switches
may be connected locally. These 16 inputs are a subset of a larger set of 64
logical inputs that are provided for controlling up to 64 unique lighting control
zones.
The controller features a front panel LCD user interface for configuration. You
can use the front panel to assign remotely operable circuit breakers to
lighting zones. Advanced features of the controller, such as blink notice or
input timers, are also configured through the front panel. No software
configuration tools or cables are required for any application.
POWERLINK G3 represents the third-generation of Square D Company’s
remote power switching systems. POWERLINK G3 continues to advance the
technology of remotely operable circuit breakers by providing a unique
system architecture in which multiple circuit breaker panelboards can be
operated by one controller. A single N2 network connection is made at the
master panelboard containing the controller. Slave panelboards do not
require an N2 connection, saving wiring costs and allowing more devices to
exist on the N2 network segment.

© 2005 Schneider Electric All Rights Reserved 1


Chapter 1—Introduction 63249-401-206/A3
Standard Features June 2005

STANDARD FEATURES The NF1000G3N2 controller is part of the G3 series 1000 controller family
that provides both input and time of day control. All POWERLINK G3 series
1000 controllers have these standard features:
• Control up to 168 remotely operable circuit breakers in up to 8
panelboards from one controller
• Ability to assign any circuit breaker to any lighting zone, up to 64 lighting
zones
• Blink notice selectable for each individual circuit breaker
• Up to 16 individually configurable switch inputs with timers for local
override
• On-board time schedules
• Front panel keyboard/LCD for configuration and status monitoring
• Programmable communications time-out action for each lighting zone

METASYS N2 FEATURES In addition to the standard G3 series 1000 features, the NF1000G3N2
controller has the following features:
• Auto detecting communication ports that switch between N2 and Modbus
protocol formats. “Auto” or “*N2*” will display to indicate the current
communication mode.
NOTE: Addresses 58 and 62 are not selectable because they are
reserved for protocol auto detection.
• Modeling of Modbus coil and discrete input points as N2 BO and BI points.
Points are used for control, monitoring, override, alarming and trending.
• Access to time schedule configuration parameters through ADI points,
which are used to load back-up time schedules into the POWERLINK G3
controller.
• Baud rate (9600) and other communications parameters (no parity) are
locked on the LCD communication setup screen according to N2 network
requirements.

BEFORE YOU BEGIN This document focuses on the Metasys N2 aspect of the NF1000G3N2
controller. Knowledge of the POWERLINK G3 architecture and components,
POWERLINK G3 system configuration, and the specific project application
requirements are assumed. For more information about the standard
NF1000G3 controller, refer to instruction bulletin 63249-401-200. If you have
questions concerning system installation or configuration, see “Technical
Support” on page 3.

2 © 2005 Schneider Electric All Rights Reserved


63249-401-206/A3 Chapter 1—Introduction
June 2005 Using With PCS Software

USING WITH PCS SOFTWARE As a member of the POWERLINK G3 family, the NF1000G3N2 is compatible
with PCS101 configuration software. This software uses Modbus ASCII
communications to interact with the controller. If you are using PCS101 you
will want to consider the following:
• The front panel RS232 connection provided on every POWERLINK G3
controller connects to the RS485 network through an internal data
converter. If you are using the front panel port you must do one of the
following to avoid data collisions:
° Disconnect the controller from the N2 network or
° Temporarily stop N2 master communications
• You can configure and save all POWERLINK G3 controllers from any
controller’s front panel port provided you observe the restrictions noted
above. A front panel serial cable is included with PCS101
• To match the controller’s communication parameters, you will need to
communicate using 9600 baud, no parity.

TECHNICAL SUPPORT For technical assistance, please contact your local sales representative, or
use one of the methods below:
Fax: (615) 287-3404
E-mail: PMOSuprt@SquareD.com
Web site: http://www.PowerLnk.com
NOTE: Include your name, company, address, phone number, type(s) of
POWERLINK products, and a detailed description of your problem.

Phone: (615) 287-3400 to speak with a technical support specialist


NOTE: If a support specialist is not available, leave a voice mail message.
For an urgent situation, speak to an operator who will process your request.

© 2005 Schneider Electric All Rights Reserved 3


Chapter 1—Introduction 63249-401-206/A3
Technical Support June 2005

4 © 2005 Schneider Electric All Rights Reserved


63249-401-206/A3 Section 2—Safety
June 2005

SECTION 2— SAFETY

This chapter contains important safety precautions that must be followed


before attempting to install, service, or maintain electrical equipment.
Carefully read and follow the safety precautions below.

DANGER
HAZARD OF ELECTRIC SHOCK, BURN, OR EXPLOSION
• This equipment must be installed and serviced only by qualified
personnel.
• Turn off all power supplying this equipment before working on or inside
equipment.
• Always use a properly rated voltage sensing device to confirm that
power is off.
• Replace all devices, doors, and covers before turning on power to this
equipment.
• Before energizing panelboard, all unused spaces must be filled with
blank fillers.

Failure to follow these instructions will result in death or serious


injury.

© 2005 Schneider Electric All Rights Reserved 5


Section 2—Safety 63249-401-206/A3
June 2005

6 © 2005 Schneider Electric All Rights Reserved


63249-401-206/A3 Chapter 3—Installation
June 2005 Contents

CHAPTER 3—INSTALLATION

CONTENTS CONTENTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
INSTALLING THE CONTROLLER . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
N2 NETWORK WIRING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Grounding. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
NETWORK RECOMMENDATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8

INSTALLING THE CONTROLLER A copy of the standard NF1000G3 instruction bulletin (63249-401-200) is
supplied with the NF1000G3N2 controller. Refer to that document for
information and safety instructions regarding the installation and wiring of the
POWERLINK G3 controller.

N2 NETWORK WIRING The network wiring terminals are located in the low-voltage wiring
compartment of the controller. The N2 communication wiring must be
connected to the 5-pin COM 1 connector found in this compartment. The
connector legend is found on the wiring compartment cover.
Note that the COM 1 connector has terminals for both RS232 and RS485
communications. Do not make any connection to the RS232 terminals when
connected to the N2 network. Although the RS232 and RS485 terminals use
different driver chips, they connect internally to the same communications
port. Attempting to use both sets of terminals simultaneously may result in
improper operation. Also note that the same precautions apply to the front
panel RS232 port, as it is internally connected to the RS232 terminals in the
wiring compartment.

Front Panel Communication


RS232 Port Wiring Terminals

RS485
+

COM 1
RS232
TX
RX

Figure 3–1: Controller Communication Wiring Terminals

© 2005 Schneider Electric All Rights Reserved 7


Chapter 3—Installation 63249-401-206/A3
Network Recommendations June 2005

Grounding The REF terminal of the controller’s RS485 communications circuit is


internally connected to digital common and is isolated from earth ground.
Connection of REF to earth ground is not recommended. If a shielded cable
is used, do not connect the shield to REF or any other terminal in the wiring
compartment.

REF
N2–
N2+

REF
N2–
N2+

Figure 3–2: COM 1 Terminal Wiring for N2 Communications

NETWORK RECOMMENDATIONS The controller RS485 circuitry is protected from voltage spikes by internal
transient suppressors and from excessive current by a PTC device. The N2+
and N2- lines are each internally biased using 10K resistors. It is
recommended that unterminated networks should be limited to 32 controllers
per repeater with up to 4,000 feet wire length between repeaters. This
distance may be increased to 5,000 feet when using 16 or less controllers
per segment.

8 © 2005 Schneider Electric All Rights Reserved


63249-401-206/A3 Chapter 4—Operation
June 2005 Contents

CHAPTER 4—OPERATION

CONTENTS CONTENTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
OPERATION OVERVIEW . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
ZONE PRIORITY. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
TIME SYNCHRONIZATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
POINT TYPES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Physical and Logical Inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Control Bus Status . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Control Bus Address Identification . . . . . . . . . . . . . . . . . . . . . . 13
Zone Control. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Input Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Time Schedules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16

OPERATION OVERVIEW The POWERLINK G3 controller is modeled around the concept of lighting
control zones. Zones are circuits that are combined into groups within the
POWERLINK G3 logic (see Figure 4–1). Overriding a zone or commanding
an input to a zone affects all of the circuits assigned to that zone. Zones 1–
16 are controlled by local switches, on-board schedules, or by
communication commands. Zones 17–64 are controlled only by
communications command.

Time Zone
Schedule Override
Object Control
1–16➀ (BO 1–64)

Input Zone
Input Control Output Circuit Breaker
Object Object
(BO 65–128) Object Commands
1–64 1–64

Input Control Bus


Status Status
(BI 1–64) (BI 65–80)

➀ The time schedule object is available when the N2 protocol is inactive.

Figure 4–1: POWERLINK NF1000G3N2 Controller Logic Model

A G3 controller has object-oriented logic designed around four functional


areas: Inputs, Zones, Outputs, and Time Schedules.
• Inputs—Combines contact closure activity with timers to create a logical
state to represent the input. This logical input state can also be
commanded via communications.
• Zones—Logically combines the schedule state with the input state to
create a single zone state, which is used to set or clear the desired states

© 2005 Schneider Electric All Rights Reserved 9


Chapter 4—Operation 63249-401-206/A3
Zone Priority June 2005

of any circuit breakers assigned to that zone. (See zone priority discussion
below.) The computed zone state may be overridden via communications.
• Outputs—Uses the desired state of a circuit breaker to control the circuit
breaker’s physical state. This function also manages blink notice and the
blink delay timer.
• Time Schedules—Compares the current time, day, and date with the
schedule configuration; and it computes a logical state.
NOTE: Time schedules are disconnected from the zone object when N2
communications are active.

ZONE PRIORITY Remotely operated circuit breakers must be assigned to a zone. Circuit
breakers are generally OFF when not commanded ON by any zone.
However, if circuit breakers are included in more than one zone they will
behave according to the zone’s priority configuration. The table below lists
the zone priority configurations from the lowest to highest priority and the
circuit breaker status.

Table 4–1: Zone Priority Configurations

Zone Priority Configuration Circuit Breaker Status (ON or OFF)


Circuit breaker is ON when zones are ON. Circuit
Normal ON
breaker is OFF when zones are OFF.
Circuit breaker is forced OFF regardless of the state
Priority OFF
of the other zones.
Circuit breaker is forced ON regardless of the state
Priority ON
of the other zones, including Priority OFF.

Most applications will use the Normal ON zone priority setting. An example
where the Priority OFF is appropriate is in a load-shed scenario. One-half of
all lighting circuits, regardless of zone, can be assigned to a load-shed zone.
These circuits are forced OFF when the point is commanded ON, based on
a control signal that indicates a demand target has been exceeded. An
example where Priority ON would be appropriate is an alarm scenario. All
lighting circuits, including those commanded OFF by Priority OFF, are forced
ON based on a security or fire alarm.
NOTE: The zone priority logic is computed after zone logic so that using the
zone override for normal control is not affected. See “Zone Control” on
page 14

TIME SYNCHRONIZATION POWERLINK G3 supports the N2 time update command, which is used by
the N2 master to synchronize the clock of the N2 slave device. It is assumed
that the N2 master time update message contains the local time. Therefore,
POWERLINK G3’s time zone attribute will not affect the time value. A time or
date set locally at the controller front panel will be overwritten by N2.
NOTE: The controller time clock is used for execution of on-board schedules.
If Metasys control is used in conjunction with POWERLINK G3 controller-
resident back-up schedules, it is essential that the N2 master be set to the
correct time.

10 © 2005 Schneider Electric All Rights Reserved


63249-401-206/A3 Chapter 4—Operation
June 2005 N2 Mode

N2 MODE The main LCD screen indicates whether the controller is in AUTO or N2
communications mode.
• AUTO Mode—If N2 communications is not detected, the controller
responds to any active on-board schedules.
• N2 Mode—If N2 communications is detected, on-board schedules are
forced inactive. If N2 communications is not detected for a duration equal
to the Comms Loss Action time-out period, the controller returns to AUTO
mode.

POINT TYPES POWERLINK G3 has an object-oriented architecture that lends itself to N2


operation. Binary output (BO) points are used for control of the input and
zone objects. Binary input (BI) points are used to monitor status of the inputs
and the control busses. Analog data integer points (ADI) are used to set time
schedules. Here is a summary of each of each point type:

Table 4–2: Point Types

Point Type Address Description Comment


Use to monitor the state of a physical (or
logical) input point. Overriding this point
Input Object
BI 1–64 forces the override state to the input and
Status
causes the local switch to be ignored until
the override is released.
Use to monitor a panel for non-responding
circuit breakers and control bus reliability.
BI 65–80 Bus Status
Alarms should be assigned to these
points.
Use to control a zone via zone override.
This method of control has priority over
Zone Object inputs or on-board time schedules. Local
BO 1–64
Control input switches are ignored until released.
Trouble indicates a circuit breaker
assigned to this zone is not responding.
Use to control a zone via input. Overriding
Input Object
BO 65–128 this point forces a state to the input, but still
Control
allows a local switch to control the zone.
Time Schedule Use to set time schedule periods and valid
ADI 1–192
Configuration days for a zone.

NOTE: Please refer to Appendix A for a complete point map.

© 2005 Schneider Electric All Rights Reserved 11


Chapter 4—Operation 63249-401-206/A3
Point Types June 2005

Physical and Logical Inputs Sixty-four BI points are provided, representing both the 16 physical switch
inputs and the 48 additional logical inputs. These points report the current
state of the input. These BI points support overrides, alarming, and change-
of-state reporting.

Override/Release

Alarm Enable Override Active


Local Switch and
Logical Inputs
Normal State Alarm State
(BI)
COS Enabled Current State

COS Reporting

Figure 4–2: Input Point Diagram

The N2 Binary Input override and release commands are used to temporarily
control the input point. The table below lists the N2 commands and explains
what they do:

Table 4–3: N2 Binary Input Override and Release Commands

Command Action
• “ON” state applied to the input so that the local input
ON switch activity is ignored
• Input timer will not cause the input state to change.
• “OFF” state applied to the input so that the local input
switch activity is ignored
OFF
• Input timer will not cause the input state to change.

• Restores operation to the locally connected switch.
Release Override • Leaves the logical state of the input at the last
commanded state.

If alarming is enabled, the alarm state is true when the normal state does not
match the current state. If change-of-state reporting is enabled and the
current state changes, the latest current state will be placed into the binary
change-of-state response list.

12 © 2005 Schneider Electric All Rights Reserved


63249-401-206/A3 Chapter 4—Operation
June 2005 Point Types

Control Bus Status Sixteen BI points are provided to represent the control busses operating and
monitoring the circuit breakers. While only eight control busses can be
connected to the controller at any time, 16 points are provided to represent
the 16 logical addresses where these eight busses can be installed.
A BI point represents the status of a control bus. These BI points support
alarming and change-of-state reporting. Override of this point is not
supported.

Alarm Enable
Bus Status
Normal State (BI) Alarm State

COS Enabled Current State

COS Reporting

Figure 4–3: Control Bus Status Point Diagram

Bus status monitoring is useful to determine if the control bus becomes


disconnected (unreliable), or if the bus contains a non-responding circuit
breaker. A non-responding circuit breaker is one that cannot reach its
commanded state because it is either: (A) tripped, (B) turned OFF by the
handle, or (C) is in manual mode. The default state of the BI point is 0 (OK).
A non-responding circuit breaker or missing bus sets the current state to 1
(FAULT). Do not enable alarms for control busses that are not present to
prevent false alarms. If change-of-state reporting is enabled and the current
state changes, the latest current state is placed into the binary change-of-
state response list.
NOTE: The system integrator should associate an alarm message
containing the panel name to the alarm condition, for example “Non-
responding circuit breaker in Panel LP4A – Room 5E727,” and enable the
alarm for this point.

Control Bus Address Identification POWERLINK G3 control busses use reference numbering that indicates the
bus location in a typical installation. The 16 control bus addresses are
identified in the point map by a number format “xy” (see Table 4–4).

Table 4–4: Control Bus Address Identifiers

Identifier Value
• Slave Address Selector switch setting or
x
• “0” for the panel containing the controller and power supply
• “L” for the left side of the panel or
y
• “R” for the right side of the panel

For example, the positions of the master panel are “0L” and “0R.” The
positions of the first slave panel are “1L” and “1R.” The bus with the Slave
Address Selector or power supply is always the “xL” bus, and the second bus
in the panel is always the “xR” bus.
NOTE: Actual installations may deviate from the typical installation practices.
You should verify that the alarm messages direct the maintenance personnel
to the correct panel.

© 2005 Schneider Electric All Rights Reserved 13


Chapter 4—Operation 63249-401-206/A3
Point Types June 2005

Zone Control Sixty-four BO points are provided, each representing one of the 64
POWERLINK G3 zones. The first 16 zones are internally connected to the 16
physical inputs and the 16 time schedules. Zones 17–64 are internally
connected to logical inputs 17–64 only. These BO points report the current
state of the zone and support overrides and change-of-state reporting.

Override/Release

Override Active
Zone
Trouble
(BO)
COS Enabled Current State

COS Reporting

Figure 4–4: Zone Control Point Diagram

The “Trouble” flag indicates that a circuit breaker assigned to this zone is non-
responding. This information may be useful when investigating a bus status
alarm condition. If change-of-state reporting is enabled and the current state
changes, the latest current state is placed into the binary change-of-state
response list.
Zone-based control is performed by applying ON, OFF and Release
commands to the zone’s BO point. Table 4–5 explains the zone-based
commands and their actions:

Table 4–5: Zone-based Control Override and Release Commands

Commands Action
• “ON” state applied to the zone as an override
ON
• Zones will not respond to input or schedule changes
• “OFF” state applied to the zone as an override
OFF
• Zones will not respond to input or schedule changes
• Restores normal zone operation
Release • Zone returns to the state set by the input or schedule
according to the zone logic type setting

Remotely operable circuit breakers must be assigned to a zone. Typically a


circuit breaker is commanded ON whenever its assigned zone is ON. If a
circuit breaker is assigned to more than one zone, such as in an egress area
application, it is ON if any of its assigned zones is ON. This rule may not be
valid if the zone priority configuration setting is changed. For more
information about zone priority, see “Zone Priority” on page 10.

14 © 2005 Schneider Electric All Rights Reserved


63249-401-206/A3 Chapter 4—Operation
June 2005 Point Types

Input Control Sixty-four BO points are provided to represent the 64 physical and logical
input points. Unlike the BI representation of the input point, Metasys can
control the BO version of the point automatically via a weekly schedule. This
method of control is useful where a sweep of local inputs is desired. An
override written to this point is equivalent to turning the zone ON or OFF from
a local switch, but unlike a zone override command, the input remains free to
respond to the local switch. The point representation is as follows:

Override/Release

Input
(BO) Current State

Figure 4–5: Input Control Point Diagram

Input-based control is performed by applying ON, OFF and Release


commands to the input’s BO point.

Table 4–6: Input Control Commands for BO Points

Command Action
• “ON” state applied to the input
ON
• Local input switch is still operational
• “OFF” state applied to the input
OFF
• Local input switch is still operational
• Input remains in the last commanded state
Release Override
• Local input switch is still operational

© 2005 Schneider Electric All Rights Reserved 15


Chapter 4—Operation 63249-401-206/A3
Point Types June 2005

Time Schedules Typically the daily time schedule of a zone is under the control of the Metasys
schedule function. POWERLINK G3 schedules can be used as an optional
back-up in situations where the building owner desires distributed control as
a precaution against a non-functioning system. Although schedules may be
configured via the front panel user interface, schedules can also be
administered through ADI points.
The POWERLINK G3 controller contains 16 on-board schedules
corresponding to zones 1–16. Each lighting zone must be assigned its own
weekly schedule. The first four periods of each schedule are available
through ADI points. Additional time/day periods may be programmed directly
into the controller, but these periods are not available through N2.
NOTE: It is recommended that applications using ADI points stay within this
four period limitation instead of using a combination of ADI points and front
panel schedule configuration.

A group of three ADI points are used to define each period. The first point
defines the start time, the second point defines the end time, and the third
point defines the active days of the week for the occupancy period. Time
values are scaled as minutes past midnight. Valid days are set by using a
weighted composite value where Sunday = 64, Monday = 32, Tuesday = 16,
Wednesday = 8, Thursday = 4, Friday = 2, and Saturday = 1. See
Table A–4 in Appendix A—NF1000G3N2 Point Map on page 21.
For example, to set the schedule for zone 3 to be ON Monday through Friday
from 10:00 AM to 9:00 PM and Saturday from 10:00 AM to 6:00 PM, use two
periods:

Table 4–7: ADI Time Schedule Example

Schedule† Period Description ADI Network Point Address Time Period ADI Value
3 1 Start Time 25 10:00 600 min*
3 1 End Time 26 21:00 1260 min*
3 1 Active Days 27 MTWTF 62**
3 2 Start Time 28 10:00 600 min*
3 2 End Time 29 18:00 1080 min*
3 2 Active Days 30 S 1**
* Start and End time units scaled as minutes past midnight using the following formula:
Time x 60 minutes = minutes past midnight (i.e 10:00 x 60 = 600)
** Active Days units are a weighted composite value, with each active day representing a particular value:
Sun. = 64, Mon. = 32, Tues. = 16, Wed. = 8, Thurs. = 4, Fri. = 2, Sat. = 1
Examples: All 7 days (64 + 32 + 16 + 8 + 4 + 2 + 1 = 127); Weekdays only (32 + 16 + 8 + 4 + 2 = 62);
Weekends (64 + 1 = 65); etc.
† Schedule number is the same as zone number.

16 © 2005 Schneider Electric All Rights Reserved


63249-401-206/A3 Chapter 5—Configuration Overview
June 2005 Contents

CHAPTER 5—CONFIGURATION OVERVIEW

CONTENTS INTRODUCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
BEFORE YOU BEGIN . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
POWERLINK CONFIGURATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
METASYS CONFIGURATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
NCM SCHEDULE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
POWERLINK G3 SCHEDULE. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20

INTRODUCTION The POWERLINK G3 controller requires initial configuration before


integration with Metasys. This section provides an overview of the
configuration and integration process, which is dependent on the facility
wiring and the desired control strategy.

BEFORE YOU BEGIN Before programming the controller, you will need to collect facility-specific
information. It is assumed that light fixtures are wired to branch circuits, and
local override switches are installed. The required information is summarized
below:
• Zone Information – Determine which circuits are associated with
particular light fixtures and which of these circuits are to be grouped
together into lighting control zones. If this information is not provided, you
can manually operate the circuit breakers and observe which lights turn
ON or OFF.
• Local Switch Information – Determine whether a switch is provided for
a zone. If provided, identify the switch’s input terminal number, which
determines the zone number. Also, determine whether the switch type is
maintained or momentary. Momentary switches are recommended for
most applications.

POWERLINK CONFIGURATION Below is a list of configuration parameters for the NF1000G3N2 controller
using the front panel LCD. See the NF1000G3 instruction bulletin,
63249-401-200, for more information about using the front panel LCD.
NOTE: Be sure to fill out the system configuration sheets as you program the
controller. These sheets are located in Appendix C—System
Configuration Sheets of the NF1000G3 instruction bulletin.

1. Set Controller N2 Communications Address


a. From the Main menu, select Controller > Communications.
b. Set the N2 Network Address for each controller.
NOTE: Addresses 58 and 62 are not selectable because they are
reserved for protocol auto-detection.

© 2005 Schneider Electric All Rights Reserved 17


Chapter 5—Configuration Overview 63249-401-206/A3
POWERLINK Configuration June 2005

2. Set Breaker Numbering for Each Control Bus


a. From the Main menu, select Controller > Control Busses.
b. Review the circuit breaker numbering sequence for each panelboard.
If the numbering sequence does not match the numbering shown on
the panelboard trim and/or your system configuration documentation,
change the breaker numbering sequence to match. This is
recommended to prevent possible confusion when grouping the
circuits into zones.
NOTE: Numbering starts at the vertical bus connection end of the
control bus.
3. Set Blink Notice for Each Circuit Breaker
a. From the Controller menu, select Breakers > Blink Type.
b. Select the appropriate blink type for the connected load. A blink notice
is used to warn occupants when the lights are about to turn OFF. The
blink notice occurs when the zone controlling the circuit breakers
transitions from ON to OFF. The blink types are as follows:
• NONE (default) – The circuit breaker turns OFF immediately
without a blink notice. This blink type is typically used with
High-Intensity Discharge (HID) lighting or with non-lighting loads.
• SINGLE – The circuit blinks once to notify that the circuit breaker
will turn OFF in a specified amount of time unless it is
commanded back ON. This blink type is typically used with
incandescent, florescent, or halogen lighting.
• DOUBLE – The circuit blinks twice to notify that the circuit breaker
is about to turn OFF. A second blink occurs one minute before
turning the circuit breaker OFF. This blink type is typically used
with incandescent, florescent, or halogen lighting.
• DELAY ONLY – The circuit will turn OFF in the specified amount
of time, but will not blink. This blink type is typically used when HID
light circuits are included in the same zone as other circuits
configured for single or double blink.

4. Group Circuit Breakers into Zones


a. From the Main menu, select Zone > Breakers.
b. Using either the View/Edit method, or the Learn method, assign
circuit breakers to the correct lighting zone.
Zones 1–16 may have a local control switch wired to the zone’s input
terminals. Be sure to assign the circuit breakers to the zone number
corresponding to the local control switch physically located in the
zone area. Circuit breakers may be assigned to more than one zone
if controlling lights located in egress paths or common areas.
5. Configure Zone Input
a. From the Main menu, select Zone > Input.
b. If a local control switch is used, you will need to configure the zone
input according to the desired control behavior for the lighting zone.
Choose from the following control strategies:
• No Local Control – ON/OFF control commands are provided by
the Johnson Controls system only. Recommended for areas with
a consistent schedule, such as parking lots. Configuration of the
input is not required.
• Local Override – The local switch allows the occupant to turn the
lights ON during unscheduled periods. Recommended for offices
or other areas where the occupants might work overtime and

18 © 2005 Schneider Electric All Rights Reserved


63249-401-206/A3 Chapter 5—Configuration Overview
June 2005 Metasys Configuration

require a local means to turn lights ON. Configure the input type
to match the switch type, and configure the timer for the desired
amount of override time. A timer is recommended for use with
local override switches to automatically turn the zone OFF during
unscheduled periods.
• Local Control – The local switch will allow the occupant to turn
the lights OFF as well as ON. Recommended for areas that need
to turn lights OFF during normal work hours, such as a meeting
room. Configure the input type to match the switch type.
Configure an input timer, if desired.

METASYS CONFIGURATION POWERLINK G3 provides a variety of N2 points that are useful for control
and status monitoring. Most applications use a weekly occupancy schedule
to automate lighting. This schedule resides in the Metasys Network Control
Module (NCM) and is modified from the operator workstation. A back-up
schedule also can reside in the POWERLINK G3 controller.

NCM SCHEDULE In typical applications the occupancy schedule is controlled by Metasys,


which issues commands to turn lights ON and OFF. The schedule controls
either the Zone BO point or the Input BO point, depending on the desired
operation. Choose the appropriate BO control point and commands
according to the chosen control strategy:
• No Local Control – Program a weekly schedule to command the Zone
BO point using the ON command at the beginning and the OFF command
at the end of each occupancy period.
• Local Override – Program a weekly schedule to command the Zone BO
point using the ON command at the beginning and the RELEASE
command at the end of each occupancy period. Releasing the zone
override allows the local switch to control the zone during the unoccupied
periods. Pressing the local switch keeps the zone ON for the desired timer
period.
• Local Control – Program a weekly schedule to command the Input BO
point using the ON command at the beginning and the OFF command at
the end of each occupancy period. Commanding the input point allows
“last-event” operation between the schedule and the local switch. Be
aware that an input timer will automatically turn the zone OFF
independent of the programmed schedule. Alternately, you can leave the
input timer unconfigured, and program the Metasys schedule to include
periodic OFF commands during the unoccupied time periods.

© 2005 Schneider Electric All Rights Reserved 19


Chapter 5—Configuration Overview 63249-401-206/A3
POWERLINK G3 Schedule June 2005

POWERLINK G3 SCHEDULE The internal schedule capability of POWERLINK G3 allows complete


stand-alone lighting control, which is useful in situations where a back-up
schedule is desired as a precaution against unsuccessful communications.
Metasys can be used to administer schedules to POWERLINK via ADI
points.
NOTE: Use the NCM schedule as a guide to program ADI points with the
same schedule. This schedule will be active only when N2 communications
is inactive.

A time schedule must be converted into ADI values. For example, a typical
office application requires that a POWERLINK G3 schedule be programmed
into zone 1. Occupancy hours are from 8:00 AM to 5:00 PM, Monday through
Friday. See Table 5–1 for the ADI point values used in this example.

Table 5–1: ADI Time Schedule Example for an Office Application

Schedule† Period Description ADI Network Point Address Time Period ADI Value
1 1 Start Time 1 8:00 480 min*
1 1 End Time 2 17:00 1020 min*
1 1 Active Days 3 MTWTF 62**
* Start and End time units scaled as minutes past midnight using the following formula:
Time x 60 minutes = minutes past midnight (i.e 10:00 x 60 = 600)
** Active Days units are a weighted composite value, with each active day representing a particular value:
Sun = 64, Mon = 32, Tues = 16, Wed = 8, Thurs = 4, Fri = 2, Sat = 1
Examples: All 7 days (64 + 32 + 16 + 8 + 4 + 2 + 1 = 127); Weekdays only (32 + 16 + 8 + 4 + 2 = 62);
Weekends (64 + 1 = 65); etc.
† Schedule number is the same as zone number.

20 © 2005 Schneider Electric All Rights Reserved


63249-401-206/A3 Appendix A—
June 2005

APPENDIX A—NF1000G3N2 POINT MAP

Table A–1: Binary Input Points — Input Object Status and Control Bus Status

Network Point Type Network Point Address Value Description


0 = OFF
BI 1 Input 1
1 = ON
0 = OFF
BI 2 Input 2
1 = ON
0 = OFF
BI 3 Input 3
1 = ON
0 = OFF
BI 4 Input 4
1 = ON
0 = OFF
BI 5 Input 5
1 = ON
0 = OFF
BI 6 Input 6
1 = ON
0 = OFF
BI 7 Input 7
1 = ON
0 = OFF
BI 8 Input 8
1 = ON
0 = OFF
BI 9 Input 9
1 = ON
0 = OFF
BI 10 Input 10
1 = ON
0 = OFF
BI 11 Input 11
1 = ON
0 = OFF
BI 12 Input 12
1 = ON
0 = OFF
BI 13 Input 13
1 = ON
0 = OFF
BI 14 Input 14
1 = ON
0 = OFF
BI 15 Input 15
1 = ON
0 = OFF
BI 16 Input 16
1 = ON
0 = OFF
BI 17 Input 17
1 = ON
0 = OFF
BI 18 Input 18
1 = ON
0 = OFF
BI 19 Input 19
1 = ON
0 = OFF
BI 20 Input 20
1 = ON
0 = OFF
BI 21 Input 21
1 = ON
0 = OFF
BI 22 Input 22
1 = ON
0 = OFF
BI 23 Input 23
1 = ON
0 = OFF
BI 24 Input 24
1 = ON

© 2005 Schneider Electric All Rights Reserved 21


Appendix A— 63249-401-206/A3
June 2005

Table A–1: Binary Input Points — Input Object Status and Control Bus Status

Network Point Type Network Point Address Value Description


0 = OFF
BI 25 Input 25
1 = ON
0 = OFF
BI 26 Input 26
1 = ON
0 = OFF
BI 27 Input 27
1 = ON
0 = OFF
BI 28 Input 28
1 = ON
0 = OFF
BI 29 Input 29
1 = ON
0 = OFF
BI 30 Input 30
1 = ON
0 = OFF
BI 31 Input 31
1 = ON
0 = OFF
BI 32 Input 32
1 = ON
0 = OFF
BI 33 Input 33
1 = ON
0 = OFF
BI 34 Input 34
1 = ON
0 = OFF
BI 35 Input 35
1 = ON
0 = OFF
BI 36 Input 36
1 = ON
0 = OFF
BI 37 Input 37
1 = ON
0 = OFF
BI 38 Input 38
1 = ON
0 = OFF
BI 39 Input 39
1 = ON
0 = OFF
BI 40 Input 40
1 = ON
0 = OFF
BI 41 Input 41
1 = ON
0 = OFF
BI 42 Input 42
1 = ON
0 = OFF
BI 43 Input 43
1 = ON
0 = OFF
BI 44 Input 44
1 = ON
0 = OFF
BI 45 Input 45
1 = ON
0 = OFF
BI 46 Input 46
1 = ON
0 = OFF
BI 47 Input 47
1 = ON
0 = OFF
BI 48 Input 48
1 = ON
0 = OFF
BI 49 Input 49
1 = ON

22 © 2005 Schneider Electric All Rights Reserved


63249-401-206/A3 Appendix A—
June 2005

Table A–1: Binary Input Points — Input Object Status and Control Bus Status

Network Point Type Network Point Address Value Description


0 = OFF
BI 50 Input 50
1 = ON
0 = OFF
BI 51 Input 51
1 = ON
0 = OFF
BI 52 Input 52
1 = ON
0 = OFF
BI 53 Input 53
1 = ON
0 = OFF
BI 54 Input 54
1 = ON
0 = OFF
BI 55 Input 55
1 = ON
0 = OFF
BI 56 Input 56
1 = ON
0 = OFF
BI 57 Input 57
1 = ON
0 = OFF
BI 58 Input 58
1 = ON
0 = OFF
BI 59 Input 59
1 = ON
0 = OFF
BI 60 Input 60
1 = ON
0 = OFF
BI 61 Input 61
1 = ON
0 = OFF
BI 62 Input 62
1 = ON
0 = OFF
BI 63 Input 63
1 = ON
0 = OFF
BI 64 Input 64
1 = ON
0 = OK
BI 65 Control Bus 0L
1 = FAULT
0 = OK
BI 66 Control Bus 0R
1 = FAULT
0 = OK
BI 67 Control Bus 1L
1 = FAULT
0 = OK
BI 68 Control Bus 1R
1 = FAULT
0 = OK
BI 69 Control Bus 2L
1 = FAULT
0 = OK
BI 70 Control Bus 2R
1 = FAULT
0 = OK
BI 71 Control Bus 3L
1 = FAULT
0 = OK
BI 72 Control Bus 3R
1 = FAULT
0 = OK
BI 73 Control Bus 4L
1 = FAULT
0 = OK
BI 74 Control Bus 4R
1 = FAULT

© 2005 Schneider Electric All Rights Reserved 23


Appendix A— 63249-401-206/A3
June 2005

Table A–1: Binary Input Points — Input Object Status and Control Bus Status

Network Point Type Network Point Address Value Description


0 = OK
BI 75 Control Bus 5L
1 = FAULT
0 = OK
BI 76 Control Bus 5R
1 = FAULT
0 = OK
BI 77 Control Bus 6L
1 = FAULT
0 = OK
BI 78 Control Bus 6R
1 = FAULT
0 = OK
BI 79 Control Bus 7L
1 = FAULT
0 = OK
BI 80 Control Bus 7R
1 = FAULT

24 © 2005 Schneider Electric All Rights Reserved


63249-401-206/A3 Appendix A—
June 2005

Table A–2: Binary Output Points – Zone Object Control


Network Point Type Network Point Address Value Description
BO 1 0 = OFF Zone 1
1 = ON
BO 2 0 = OFF Zone 2
1 = ON
BO 3 0 = OFF Zone 3
1 = ON
BO 4 0 = OFF Zone 4
1 = ON
BO 5 0 = OFF Zone 5
1 = ON
BO 6 0 = OFF Zone 6
1 = ON
BO 7 0 = OFF Zone 7
1 = ON
BO 8 0 = OFF Zone 8
1 = ON
BO 9 0 = OFF Zone 9
1 = ON
BO 10 0 = OFF Zone 10
1 = ON
BO 11 0 = OFF Zone 11
1 = ON
BO 12 0 = OFF Zone 12
1 = ON
BO 13 0 = OFF Zone 13
1 = ON
BO 14 0 = OFF Zone 14
1 = ON
BO 15 0 = OFF Zone 15
1 = ON
BO 16 0 = OFF Zone 16
1 = ON
BO 17 0 = OFF Zone 17
1 = ON
BO 18 0 = OFF Zone 18
1 = ON
BO 19 0 = OFF Zone 19
1 = ON
BO 20 0 = OFF Zone 20
1 = ON
BO 21 0 = OFF Zone 21
1 = ON
BO 22 0 = OFF Zone 22
1 = ON
BO 23 0 = OFF Zone 23
1 = ON
BO 24 0 = OFF Zone 24
1 = ON

© 2005 Schneider Electric All Rights Reserved 25


Appendix A— 63249-401-206/A3
June 2005

Table A–2: Binary Output Points – Zone Object Control


Network Point Type Network Point Address Value Description
BO 25 0 = OFF Zone 25
1 = ON
BO 26 0 = OFF Zone 26
1 = ON
BO 27 0 = OFF Zone 27
1 = ON
BO 28 0 = OFF Zone 28
1 = ON
BO 29 0 = OFF Zone 29
1 = ON
BO 30 0 = OFF Zone 30
1 = ON
BO 31 0 = OFF Zone 31
1 = ON
BO 32 0 = OFF Zone 32
1 = ON
BO 33 0 = OFF Zone 33
1 = ON
BO 34 0 = OFF Zone 34
1 = ON
BO 35 0 = OFF Zone 35
1 = ON
BO 36 0 = OFF Zone 36
1 = ON
BO 37 0 = OFF Zone 37
1 = ON
BO 38 0 = OFF Zone 38
1 = ON
BO 39 0 = OFF Zone 39
1 = ON
BO 40 0 = OFF Zone 40
1 = ON
BO 41 0 = OFF Zone 41
1 = ON
BO 42 0 = OFF Zone 42
1 = ON
BO 43 0 = OFF Zone 43
1 = ON
BO 44 0 = OFF Zone 44
1 = ON
BO 45 0 = OFF Zone 45
1 = ON
BO 46 0 = OFF Zone 46
1 = ON
BO 47 0 = OFF Zone 47
1 = ON
BO 48 0 = OFF Zone 48
1 = ON

26 © 2005 Schneider Electric All Rights Reserved


63249-401-206/A3 Appendix A—
June 2005

Table A–2: Binary Output Points – Zone Object Control


Network Point Type Network Point Address Value Description
BO 49 0 = OFF Zone 49
1 = ON
BO 50 0 = OFF Zone 50
1 = ON
BO 51 0 = OFF Zone 51
1 = ON
BO 52 0 = OFF Zone 52
1 = ON
BO 53 0 = OFF Zone 53
1 = ON
BO 54 0 = OFF Zone 54
1 = ON
BO 55 0 = OFF Zone 55
1 = ON
BO 56 0 = OFF Zone 56
1 = ON
BO 57 0 = OFF Zone 57
1 = ON
BO 58 0 = OFF Zone 58
1 = ON
BO 59 0 = OFF Zone 59
1 = ON
BO 60 0 = OFF Zone 60
1 = ON
BO 61 0 = OFF Zone 61
1 = ON
BO 62 0 = OFF Zone 62
1 = ON
BO 63 0 = OFF Zone 63
1 = ON
BO 64 0 = OFF Zone 64
1 = ON

© 2005 Schneider Electric All Rights Reserved 27


Appendix A— 63249-401-206/A3
June 2005

Table A–3: Binary Output Points – Input Object Control

Network Point Type Network Point Address Value Description


0 = OFF
BO 65 Input 1
1 = ON
0 = OFF
BO 66 Input 2
1 = ON
0 = OFF
BO 67 Input 3
1 = ON
0 = OFF
BO 68 Input 4
1 = ON
0 = OFF
BO 69 Input 5
1 = ON
0 = OFF
BO 70 Input 6
1 = ON
0 = OFF
BO 71 Input 7
1 = ON
0 = OFF
BO 72 Input 8
1 = ON
0 = OFF
BO 73 Input 9
1 = ON
0 = OFF
BO 74 Input 10
1 = ON
0 = OFF
BO 75 Input 11
1 = ON
0 = OFF
BO 76 Input 12
1 = ON
0 = OFF
BO 77 Input 13
1 = ON
0 = OFF
BO 78 Input 14
1 = ON
0 = OFF
BO 79 Input 15
1 = ON
0 = OFF
BO 80 Input 16
1 = ON
0 = OFF
BO 81 Input 17
1 = ON
0 = OFF
BO 82 Input 18
1 = ON
0 = OFF
BO 83 Input 19
1 = ON
0 = OFF
BO 84 Input 20
1 = ON
0 = OFF
BO 85 Input 21
1 = ON
0 = OFF
BO 86 Input 22
1 = ON
0 = OFF
BO 87 Input 23
1 = ON
0 = OFF
BO 88 Input 24
1 = ON
0 = OFF
BO 89 Input 25
1 = ON

28 © 2005 Schneider Electric All Rights Reserved


63249-401-206/A3 Appendix A—
June 2005

Table A–3: Binary Output Points – Input Object Control

Network Point Type Network Point Address Value Description


0 = OFF
BO 90 Input 26
1 = ON
0 = OFF
BO 91 Input 27
1 = ON
0 = OFF
BO 92 Input 28
1 = ON
0 = OFF
BO 93 Input 29
1 = ON
0 = OFF
BO 94 Input 30
1 = ON
0 = OFF
BO 95 Input 31
1 = ON
0 = OFF
BO 96 Input 32
1 = ON
0 = OFF
BO 97 Input 33
1 = ON
0 = OFF
BO 98 Input 34
1 = ON
0 = OFF
BO 99 Input 35
1 = ON
0 = OFF
BO 100 Input 36
1 = ON
0 = OFF
BO 101 Input 37
1 = ON
0 = OFF
BO 102 Input 38
1 = ON

BO 103 0 = OFF Input 39


1 = ON
BO 104 0 = OFF Input 40
1 = ON
BO 105 0 = OFF Input 41
1 = ON
BO 106 0 = OFF Input 42
1 = ON
BO 107 0 = OFF Input 43
1 = ON
BO 108 0 = OFF Input 44
1 = ON
BO 109 0 = OFF Input 45
1 = ON
BO 110 0 = OFF Input 46
1 = ON
BO 111 0 = OFF Input 47
1 = ON
BO 112 0 = OFF Input 48
1 = ON
BO 113 0 = OFF Input 49
1 = ON

© 2005 Schneider Electric All Rights Reserved 29


Appendix A— 63249-401-206/A3
June 2005

Table A–3: Binary Output Points – Input Object Control

Network Point Type Network Point Address Value Description

BO 114 0 = OFF Input 50


1 = ON
BO 115 0 = OFF Input 51
1 = ON
BO 116 0 = OFF Input 52
1 = ON
BO 117 0 = OFF Input 53
1 = ON
BO 118 0 = OFF Input 54
1 = ON
BO 119 0 = OFF Input 55
1 = ON
BO 120 0 = OFF Input 56
1 = ON
BO 121 0 = OFF Input 57
1 = ON
BO 122 0 = OFF Input 58
1 = ON
BO 123 0 = OFF Input 59
1 = ON
BO 124 0 = OFF Input 60
1 = ON
BO 125 0 = OFF Input 61
1 = ON
BO 126 0 = OFF Input 62
1 = ON
BO 127 0 = OFF Input 63
1 = ON
BO 128 0 = OFF Input 64
1 = ON

30 © 2005 Schneider Electric All Rights Reserved


63249-401-206/A3 Appendix A—
June 2005

Table A–4: Analog Data Integer Points – Time Schedule Object


Network Point Type Network Point Address Range1,2 Schedule3 Period Description
ADI 1 0 - 1439 1 1 Start Time
ADI 2 0 - 1439 1 1 End Time
ADI 3 0 - 127 1 1 Active Days
ADI 4 0 - 1439 1 2 Start Time
ADI 5 0 - 1439 1 2 End Time
ADI 6 0 - 127 1 2 Active Days
ADI 7 0 - 1439 1 3 Start Time
ADI 8 0 - 1439 1 3 End Time
ADI 9 0 - 127 1 3 Active Days
ADI 10 0 - 1439 1 4 Start Time
ADI 11 0 - 1439 1 4 End Time
ADI 12 0 - 127 1 4 Active Days
ADI 13 0 - 1439 2 1 Start Time
ADI 14 0 - 1439 2 1 End Time
ADI 15 0 - 127 2 1 Active Days
ADI 16 0 - 1439 2 2 Start Time
ADI 17 0 - 1439 2 2 End Time
ADI 18 0 - 127 2 2 Active Days
ADI 19 0 - 1439 2 3 Start Time
ADI 20 0 - 1439 2 3 End Time
ADI 21 0 - 127 2 3 Active Days
ADI 22 0 - 1439 2 4 Start Time
ADI 23 0 - 1439 2 4 End Time
ADI 24 0 - 127 2 4 Active Days
ADI 25 0 - 1439 3 1 Start Time
ADI 26 0 - 1439 3 1 End Time
ADI 27 0 - 127 3 1 Active Days
ADI 28 0 - 1439 3 2 Start Time
ADI 29 0 - 1439 3 2 End Time
ADI 30 0 - 127 3 2 Active Days
ADI 31 0 - 1439 3 3 Start Time
ADI 32 0 - 1439 3 3 End Time
ADI 33 0 - 127 3 3 Active Days
ADI 34 0 - 1439 3 4 Start Time
ADI 35 0 - 1439 3 4 End Time
ADI 36 0 - 127 3 4 Active Days
1 Start Time and End Time time units scaled as minutes past midnight using the following formula:
Time x 60 minutes = minutes past midnight (i.e 10:00 x 60 = 600)
2 Active Days units are a weighted composite value, with each active day representing a particular
value:
Sun. = 64, Mon. = 32, Tues. = 16, Wed = 8, Thurs. = 4, Fri. = 2, Sat. = 1
Examples: All 7 Active Days (64 + 32 + 16 + 8 + 4 + 2 + 1 = 127); Week Active Days only (32 +
16 + 8 + 4 + 2 = 62);
WeekEnd Times (64 + 1 = 65); etc.
3 For all schedules, periods 5 – 24 are not supported as N2 points.

© 2005 Schneider Electric All Rights Reserved 31


Appendix A— 63249-401-206/A3
June 2005

Table A–4: Analog Data Integer Points – Time Schedule Object


Network Point Type Network Point Address Range1,2 Schedule3 Period Description
ADI 37 0 - 1439 4 1 Start Time
ADI 38 0 - 1439 4 1 End Time
ADI 39 0 - 127 4 1 Active Days
ADI 40 0 - 1439 4 2 Start Time
ADI 41 0 - 1439 4 2 End Time
ADI 42 0 - 127 4 2 Active Days
ADI 43 0 - 1439 4 3 Start Time
ADI 44 0 - 1439 4 3 End Time
ADI 45 0 - 127 4 3 Active Days
ADI 46 0 - 1439 4 4 Start Time
ADI 47 0 - 1439 4 4 End Time
ADI 48 0 - 127 4 4 Active Days
ADI 49 0 - 1439 5 1 Start Time
ADI 50 0 - 1439 5 1 End Time
ADI 51 0 - 127 5 1 Active Days
ADI 52 0 - 1439 5 2 Start Time
ADI 53 0 - 1439 5 2 End Time
ADI 54 0 - 127 5 2 Active Days
ADI 55 0 - 1439 5 3 Start Time
ADI 56 0 - 1439 5 3 End Time
ADI 57 0 - 127 5 3 Active Days
ADI 58 0 - 1439 5 4 Start Time
ADI 59 0 - 1439 5 4 End Time
ADI 60 0 - 127 5 4 Active Days
ADI 61 0 - 1439 6 1 Start Time
ADI 62 0 - 1439 6 1 End Time
ADI 63 0 - 127 6 1 Active Days
ADI 64 0 - 1439 6 2 Start Time
ADI 65 0 - 1439 6 2 End Time
ADI 66 0 - 127 6 2 Active Days
ADI 67 0 - 1439 6 3 Start Time
ADI 68 0 - 1439 6 3 End Time
ADI 69 0 - 127 6 3 Active Days
ADI 70 0 - 1439 6 4 Start Time
ADI 71 0 - 1439 6 4 End Time
ADI 72 0 - 127 6 4 Active Days
1 Start Time and End Time time units scaled as minutes past midnight using the following formula:
Time x 60 minutes = minutes past midnight (i.e 10:00 x 60 = 600)
2 Active Days units are a weighted composite value, with each active day representing a particular
value:
Sun. = 64, Mon. = 32, Tues. = 16, Wed = 8, Thurs. = 4, Fri. = 2, Sat. = 1
Examples: All 7 Active Days (64 + 32 + 16 + 8 + 4 + 2 + 1 = 127); Week Active Days only (32 +
16 + 8 + 4 + 2 = 62);
WeekEnd Times (64 + 1 = 65); etc.
3 For all schedules, periods 5 – 24 are not supported as N2 points.

32 © 2005 Schneider Electric All Rights Reserved


63249-401-206/A3 Appendix A—
June 2005

Table A–4: Analog Data Integer Points – Time Schedule Object


Network Point Type Network Point Address Range1,2 Schedule3 Period Description
ADI 73 0 - 1439 7 1 Start Time
ADI 74 0 - 1439 7 1 End Time
ADI 75 0 - 127 7 1 Active Days
ADI 76 0 - 1439 7 2 Start Time
ADI 77 0 - 1439 7 2 End Time
ADI 78 0 - 127 7 2 Active Days
ADI 79 0 - 1439 7 3 Start Time
ADI 80 0 - 1439 7 3 End Time
ADI 81 0 - 127 7 3 Active Days
ADI 82 0 - 1439 7 4 Start Time
ADI 83 0 - 1439 7 4 End Time
ADI 84 0 - 127 7 4 Active Days
ADI 85 0 - 1439 8 1 Start Time
ADI 86 0 - 1439 8 1 End Time
ADI 87 0 - 127 8 1 Active Days
ADI 88 0 - 1439 8 2 Start Time
ADI 89 0 - 1439 8 2 End Time
ADI 90 0 - 127 8 2 Active Days
ADI 91 0 - 1439 8 3 Start Time
ADI 92 0 - 1439 8 3 End Time
ADI 93 0 - 127 8 3 Active Days
ADI 94 0 - 1439 8 4 Start Time
ADI 95 0 - 1439 8 4 End Time
ADI 96 0 - 127 8 4 Active Days
ADI 97 0 - 1439 9 1 Start Time
ADI 98 0 - 1439 9 1 End Time
ADI 99 0 - 127 9 1 Active Days
ADI 100 0 - 1439 9 2 Start Time
ADI 101 0 - 1439 9 2 End Time
ADI 102 0 - 127 9 2 Active Days
ADI 103 0 - 1439 9 3 Start Time
ADI 104 0 - 1439 9 3 End Time
ADI 105 0 - 127 9 3 Active Days
ADI 106 0 - 1439 9 4 Start Time
ADI 107 0 - 1439 9 4 End Time
ADI 108 0 - 127 9 4 Active Days
1 Start Time and End Time time units scaled as minutes past midnight using the following formula:
Time x 60 minutes = minutes past midnight (i.e 10:00 x 60 = 600)
2 Active Days units are a weighted composite value, with each active day representing a particular
value:
Sun. = 64, Mon. = 32, Tues. = 16, Wed = 8, Thurs. = 4, Fri. = 2, Sat. = 1
Examples: All 7 Active Days (64 + 32 + 16 + 8 + 4 + 2 + 1 = 127); Week Active Days only (32 +
16 + 8 + 4 + 2 = 62);
WeekEnd Times (64 + 1 = 65); etc.
3 For all schedules, periods 5 – 24 are not supported as N2 points.

© 2005 Schneider Electric All Rights Reserved 33


Appendix A— 63249-401-206/A3
June 2005

Table A–4: Analog Data Integer Points – Time Schedule Object


Network Point Type Network Point Address Range1,2 Schedule3 Period Description
ADI 109 0 - 1439 10 1 Start Time
ADI 110 0 - 1439 10 1 End Time
ADI 111 0 - 127 10 1 Active Days
ADI 112 0 - 1439 10 2 Start Time
ADI 113 0 - 1439 10 2 End Time
ADI 114 0 - 127 10 2 Active Days
ADI 115 0 - 1439 10 3 Start Time
ADI 116 0 - 1439 10 3 End Time
ADI 117 0 - 127 10 3 Active Days
ADI 118 0 - 1439 10 4 Start Time
ADI 119 0 - 1439 10 4 End Time
ADI 120 0 - 127 10 4 Active Days
ADI 121 0 - 1439 11 1 Start Time
ADI 122 0 - 1439 11 1 End Time
ADI 123 0 - 127 11 1 Active Days
ADI 124 0 - 1439 11 2 Start Time
ADI 125 0 - 1439 11 2 End Time
ADI 126 0 - 127 11 2 Active Days
ADI 127 0 - 1439 11 3 Start Time
ADI 128 0 - 1439 11 3 End Time
ADI 129 0 - 127 11 3 Active Days
ADI 130 0 - 1439 11 4 Start Time
ADI 131 0 - 1439 11 4 End Time
ADI 132 0 - 127 11 4 Active Days
ADI 133 0 - 1439 12 1 Start Time
ADI 134 0 - 1439 12 1 End Time
ADI 135 0 - 127 12 1 Active Days
ADI 136 0 - 1439 12 2 Start Time
ADI 137 0 - 1439 12 2 End Time
ADI 138 0 - 127 12 2 Active Days
ADI 139 0 - 1439 12 3 Start Time
ADI 140 0 - 1439 12 3 End Time
ADI 141 0 - 127 12 3 Active Days
ADI 142 0 - 1439 12 4 Start Time
ADI 143 0 - 1439 12 4 End Time
ADI 144 0 - 127 12 4 Active Days
1 Start Time and End Time time units scaled as minutes past midnight using the following formula:
Time x 60 minutes = minutes past midnight (i.e 10:00 x 60 = 600)
2 Active Days units are a weighted composite value, with each active day representing a particular
value:
Sun. = 64, Mon. = 32, Tues. = 16, Wed = 8, Thurs. = 4, Fri. = 2, Sat. = 1
Examples: All 7 Active Days (64 + 32 + 16 + 8 + 4 + 2 + 1 = 127); Week Active Days only (32 +
16 + 8 + 4 + 2 = 62);
WeekEnd Times (64 + 1 = 65); etc.
3 For all schedules, periods 5 – 24 are not supported as N2 points.

34 © 2005 Schneider Electric All Rights Reserved


63249-401-206/A3 Appendix A—
June 2005

Table A–4: Analog Data Integer Points – Time Schedule Object


Network Point Type Network Point Address Range1,2 Schedule3 Period Description
ADI 145 0 - 1439 13 1 Start Time
ADI 146 0 - 1439 13 1 End Time
ADI 147 0 - 127 13 1 Active Days
ADI 148 0 - 1439 13 2 Start Time
ADI 149 0 - 1439 13 2 End Time
ADI 150 0 - 127 13 2 Active Days
ADI 151 0 - 1439 13 3 Start Time
ADI 152 0 - 1439 13 3 End Time
ADI 153 0 - 127 13 3 Active Days
ADI 154 0 - 1439 13 4 Start Time
ADI 155 0 - 1439 13 4 End Time
ADI 156 0 - 127 13 4 Active Days
ADI 157 0 - 1439 14 1 Start Time
ADI 158 0 - 1439 14 1 End Time
ADI 159 0 - 127 14 1 Active Days
ADI 160 0 - 1439 14 2 Start Time
ADI 161 0 - 1439 14 2 End Time
ADI 162 0 - 127 14 2 Active Days
ADI 163 0 - 1439 14 3 Start Time
ADI 164 0 - 1439 14 3 End Time
ADI 165 0 - 127 14 3 Active Days
ADI 166 0 - 1439 14 4 Start Time
ADI 167 0 - 1439 14 4 End Time
ADI 168 0 - 127 14 4 Active Days
ADI 169 0 - 1439 15 1 Start Time
ADI 170 0 - 1439 15 1 End Time
ADI 171 0 - 127 15 1 Active Days
ADI 172 0 - 1439 15 2 Start Time
ADI 173 0 - 1439 15 2 End Time
ADI 174 0 - 127 15 2 Active Days
ADI 175 0 - 1439 15 3 Start Time
ADI 176 0 - 1439 15 3 End Time
ADI 177 0 - 127 15 3 Active Days
ADI 178 0 - 1439 15 4 Start Time
ADI 179 0 - 1439 15 4 End Time
ADI 180 0 - 127 15 4 Active Days
1 Start Time and End Time time units scaled as minutes past midnight using the following formula:
Time x 60 minutes = minutes past midnight (i.e 10:00 x 60 = 600)
2 Active Days units are a weighted composite value, with each active day representing a particular
value:
Sun. = 64, Mon. = 32, Tues. = 16, Wed = 8, Thurs. = 4, Fri. = 2, Sat. = 1
Examples: All 7 Active Days (64 + 32 + 16 + 8 + 4 + 2 + 1 = 127); Week Active Days only (32 +
16 + 8 + 4 + 2 = 62);
WeekEnd Times (64 + 1 = 65); etc.
3 For all schedules, periods 5 – 24 are not supported as N2 points.

© 2005 Schneider Electric All Rights Reserved 35


Appendix A— 63249-401-206/A3
June 2005

Table A–4: Analog Data Integer Points – Time Schedule Object


Network Point Type Network Point Address Range1,2 Schedule3 Period Description
ADI 181 0 - 1439 16 1 Start Time
ADI 182 0 - 1439 16 1 End Time
ADI 183 0 - 127 16 1 Active Days
ADI 184 0 - 1439 16 2 Start Time
ADI 185 0 - 1439 16 2 End Time
ADI 186 0 - 127 16 2 Active Days
ADI 187 0 - 1439 16 3 Start Time
ADI 188 0 - 1439 16 3 End Time
ADI 189 0 - 127 16 3 Active Days
ADI 190 0 - 1439 16 4 Start Time
ADI 191 0 - 1439 16 4 End Time
ADI 192 0 - 127 16 4 Active Days
1 Start Time and End Time time units scaled as minutes past midnight using the following formula:
Time x 60 minutes = minutes past midnight (i.e 10:00 x 60 = 600)
2 Active Days units are a weighted composite value, with each active day representing a particular
value:
Sun. = 64, Mon. = 32, Tues. = 16, Wed = 8, Thurs. = 4, Fri. = 2, Sat. = 1
Examples: All 7 Active Days (64 + 32 + 16 + 8 + 4 + 2 + 1 = 127); Week Active Days only (32 +
16 + 8 + 4 + 2 = 62);
WeekEnd Times (64 + 1 = 65); etc.
3 For all schedules, periods 5 – 24 are not supported as N2 points.

36 © 2005 Schneider Electric All Rights Reserved


Square D Company Electrical equipment should be installed, operated, serviced, and maintained only by qualified
295 Techpark Drive, Suite 100 personnel. No responsibility is assumed by Schneider Electric for any consequences arising out of
LaVergne, TN 37086, USA the use of this material.
888-SquareD
(1-888-778-2733)
63249-401-206/A3 © 2005 Schneider Electric All Rights Reserved
www.SquareD.com/Powerlink
Replaces 63249-401-206/A2 dated November 2003

Você também pode gostar