TEST REPORT OF GENERATOR PROTECTION

RELAY (87G_G60) D18T PANEL

FIELD TEST REPORT FOR GENERATOR PROTECTION RELAY

Relay Details
Make GE Feeder CONTROL RELAY FEEDER
Model No G60 Function GENERATOR PROTECTION
Generator Details
Rating 126.77 MW CT Ratio Phase 8000/1 A
HV Volts 14.51 kV CT Ratio Neutral 8000/1 A
LV Volts 221 kV Date of testing 26/05/2019

Testing Equipment Details

Equipment Name Make & Model Serial Number Date


Relay Test kit OMICRON/CMC 256 PLUS LD095F 16/08/2018

PHASE DISTANCE:
PT INJ: X VT 9,10,11,12 NCT used: X CT 9,10,11,12 Tripping Feedback (186,187 refer pg 52 scheme)
(Keeping I CONST (1A) - V CALC by Z=V/I)
ZONE-1 SETTINGS:
DIR: FWD Z = 11.48 Ω RCA = 90° TIME DELAY= 0.5 Sec

Ref Applied Voltage(V) Injected Current (A) Set time (sec) Operated time(m sec)
R 11.40 1 90
Y 11.4-120 1  330 0.3 363.2
B 11.4120 1 210

Tested by Witnessed by Witnessed/Reviewed by


VEPL RIL-Maintenance RIL- Operations
Sign & Date: Sign & Date: Sign & Date:
Name: ASHWATH K Name: Name:
Designation: Protection Engr. Designation: Designation:
Page: 1 of 5
TEST REPORT OF GENERATOR PROTECTION
RELAY (87G_G60) D18T PANEL

ZONE-2 SETTINGS:
DIR: FWD Z = 29.84 Ω RCA = 90° TIME DELAY= 1 Sec

Ref Applied Voltage(V) Injected Current (A) Set time (sec) Operated time( sec)
R 28.90 1 90
Y 28.9-120 1  330 1 1.041
B 28.9120 1 210

ZONE-3 SETTINGS:
DIR: REV Z = 13.65 Ω RCA = 90° TIME DELAY= 0.3 Sec

Tested by Witnessed by Witnessed/Reviewed by


VEPL RIL-Maintenance RIL- Operations
Sign & Date: Sign & Date: Sign & Date:
Name: ASHWATH K Name: Name:
Designation: Protection Engr. Designation: Designation:
Page: 2 of 5
TEST REPORT OF GENERATOR PROTECTION
RELAY (87G_G60) D18T PANEL

Ref Applied Voltage(V) Injected Current (A) Set time (sec) Operated time( sec)
R 13.60 1 90
Y 13.6 -120 1  330 0.3 335.3
B 13.6 120 1 210

Corresponding LED and 86N-1 Tripping Checked OK & Snapshot of RELAY Events attached

OVER VOLTAGE TEST: Tripping Feedback (196,197refer pg 52 scheme)


1st STAGE: Alarm only Set – 1.1 pu Time – 10 sec

Phase Set Voltage(PU) Applied Voltage (V) Set Time Operating Time
(sec) (sec)
R-Y 1.1 70 AFTER 10 Sec
AFTER 10 Sec ALARM
Y-B 1.1 70 ALARM CHECKED
ONLY
B-R 1.1 70 OK

Tested by Witnessed by Witnessed/Reviewed by


VEPL RIL-Maintenance RIL- Operations
Sign & Date: Sign & Date: Sign & Date:
Name: ASHWATH K Name: Name:
Designation: Protection Engr. Designation: Designation:
Page: 3 of 5
TEST REPORT OF GENERATOR PROTECTION
RELAY (87G_G60) D18T PANEL

2nd STAGE: Trip Stage set – 1.2 pu Time- 3 sec

Phase Set Voltage(PU) Applied Voltage(V) Set Time(sec) Operating Time (sec)

R-Y 1.2 76.3


Y-B 1.2 76.3 3.0 3.067
B-R 1.2 76.3

Tested by Witnessed by Witnessed/Reviewed by


VEPL RIL-Maintenance RIL- Operations
Sign & Date: Sign & Date: Sign & Date:
Name: ASHWATH K Name: Name:
Designation: Protection Engr. Designation: Designation:
Page: 4 of 5
TEST REPORT OF GENERATOR PROTECTION
RELAY (87G_G60) D18T PANEL

Corresponding LED and 86L-1 Tripping Checked OK & Snapshot of RELAY Events attached

RELAY FOUND HEALTHY.

Tested by Witnessed by Witnessed/Reviewed by


VEPL RIL-Maintenance RIL- Operations
Sign & Date: Sign & Date: Sign & Date:
Name: ASHWATH K Name: Name:
Designation: Protection Engr. Designation: Designation:
Page: 5 of 5