Você está na página 1de 2

The ABC’s of Fire Alarm Systems – Part III

By Anthony J. Shalna  2009Principal IMSA Representative to the Automatic Fire Alarm Association
President: Southeastern Signalmen of Massachusetts
Approvals Manager: Gamewell-FCI by Honeywell

Addressable Fire Alarm Systems The addressable system operates


Until now we have been concerned with conventional fire over a circuit known as a Signaling
alarm systems. These systems require specialized wiring Line Circuit (SLC). Depending on the
practices using “in and out” connections to devices in order manufacturer and design, the circuit can be wired in various
to maintain supervision of the devices. “T” tapping is an- methods in regard to fail-safe operation. These methods are
other practice also not permitted in conventional systems. presently referred to as “Styles”, but I understand that the
These will be covered in detail in a later installment. 2010 Edition of NFPA 72, National Fire Alarm Code, will
revert to an older “Class” designation. At any rate, I recom-
Addressable systems are a different matter. No specialized mend consulting the charts of the current edition of NFPA
methods of wiring are required. These systems are controlled 72 for further information.
by microprocessors and their operation relies on communi-
cation between the microprocessor in the central processing The SLC does not resemble conventional initiating circuits
(control) unit, and connect- since it is a data gathering
ed devices which have their circuit, while conventional
own microprocessors. Ad- devices, having normally
dressable systems feature open alarm contacts, place
an LCD or similar visual a short circuit across their
display that may give loca- initiating device circuit. A
tion and specific informa- short on an SLC will cause
tion about the connected a trouble condition instead
devices, depending on how of alarm.
it is programmed. Some
systems show detailed in- Connected to this SLC are
formation via an alpha-nu- addressable smoke or heat
meric display while other sensors, monitor modules,
smaller, economy type sys- output modules and/or
tems might display only a data gathering panels. Dif-
code number assigned to ferent manufacturers all
the device. These systems have been nicknamed “smart” or have their own various designations for these modules, but
“intelligent” systems. generically, they are usually referred to as transponders and
in common conversation as modules.
Addressable systems are obviously much more complex than
conventional systems, but they have an infinitely greater The sensors and modules all may be intermingled on the
flexibility. Oddly enough, even though they may be exceed- SLC regardless of their (input or control) function. (See
ingly complex, describing them is a relatively simple matter. illustration) As stated above, they have their own unique
The initiating devices and notification appliances are either address that is assigned when the system is programmed.
connected to or incorporate a transponder that has a specific This address is assigned to the transponder at installation
address assigned to it. These transponders are connected to a via a DIP or rotary switch.
circuit of the central processing unit which interrogates each Again, the variety of modules, sensors and data gathering
transponder in sequence. When interrogated, a device may panels is limited only by the manufacturer’s imagination and
respond that it is normal, or if an initiating device, that it is in technical expertise. Addressable smoke or heat detectors are
an alarm condition. If a device is inoperative, disconnected, usually referred to as “sensors” to distinguish them from
damaged, etc., it will not respond. The central processor then conventional detectors. These sensors may either contain an
creates a trouble condition and a “device missing” message integral address switch, or in older or economical systems,
will be displayed. they may simply be conventional detectors installed in an
addressable base. Conventional detectors installed in an ad-
Present standards require a maximum of five (5) seconds dressable base would constitute an “Addressable System”.
for a CPU to report an alarm from a device. The speed of Smoke sensors containing microprocessors now report their
interrogation has increased dramatically in recent years status to the CPU. While a conventional detector has only
with the development of better and faster microprocessors. two conditions: Alarm or Normal, the newest sensors can
Now there exists a signaling protocol for certain models of notify the CPU that they “smell smoke”, or are approaching
smoke sensors where the CPU interrogates a large cluster an alarm condition, or signal that they are dirty and require
of sensors instead of individually. This cluster will instantly cleaning, etc. Their sensitivity can be varied by the control
report an alarm condition when interrogated and then indi- panel and new features are being announced continually.
cate the address of the specific device in alarm. This saves a
significant amount of time that would be otherwise required Systems employing these sensors are known as “Analog
to interrogate each device individually.
Continued on page 30
Page 28 IMSA Journal
The ABC’s of Fire Alarm Systems – Part III . . . Continued from page 28
Addressable” since their condition is dis- ums where only a collective address is OPERATION SUMMARY
played in an analog fashion rather than a needed to guide fire-fighting forces to The microprocessor in the main control
digital “normal” or “alarm” condition. the source of the fire. interrogates or polls the transponders in
sequence, with only nanoseconds being
Many people erroneously use the term Data gathering panels have been used required for each device or cluster of
“Analog Addressable” to describe since the earliest days of addressable sensors. When a transponder is polled,
all devices connected to an SLC, but systems. These panels resemble a small it responds that it is either in a normal
technically this term does not apply to conventional fire alarm control panel state or in alarm. In Analog Address-
devices such as manual pull stations and contain a number of conventional able Systems, a transponder installed
or electronic addressable heat detec- initiating circuits, battery standby, in a smoke sensor will also indicate the
tors that have been employed in these etc. These panels in effect provide a condition of the sensor, such as “dirty”,
systems until now. Even though heat subsystem with its own address, but approaching alarm condition, etc. If the
sensors may be addressable and signal I wouldn’t be surprised if some of the transponder is disconnected for any
an alarm via the SLC, they can only latest ones provide multiple addresses, reason (malfunction or break in the wir-
report the two states, alarm or normal. one for each initiating circuit. ing) the panel will show a system trouble
Now appearing on the horizon are heat and show a “device missing” message
sensors that can indicate their chang- Output or control modules may also (or code) on the display, which will give
ing condition in the same manner as be installed anywhere on the SLC. a specific location of the device. Other
a smoke sensor, such as reporting an These modules likewise have their fault messages can be for an SLC break,
increase in ambient heat, so nothing is own unique address and may be pro- circuit shorted, etc. Some systems may
etched in concrete regarding the ability grammed to perform a function in the indicate a circuit break by displaying a
and features of these sensors. event of an alarm or trouble on any list of missing addresses located beyond
individual or combination of monitor the break or short.
Monitor modules have their own as- modules or sensors. These control
signed addresses and commonly fea- modules may contain dry contacts that One disadvantage of the addressable
ture a conventional initiating circuit transfer on command, but again, new system is that polling or interrogation
complete with an end of line resistor. configurations are arriving on the mar- consumes a fraction of a second per
Conventional dry contact initiating ket on a daily basis. Some will accept device polled. If a substantial number
devices are connected to this circuit. an audio input and provide supervised of devices are installed in an individual
These may be electromechanical heat loudspeaker appliance circuits, while signaling line circuit, a considerable
detectors, manual pull stations, water- others will supervise and operate notifi- amount of time could elapse until an
flow switches, etc. When any of these cation appliance circuits. Still others can alarm is processed. Present control
devices go into alarm, the monitor mod- be used to energize releasing solenoids panel standards require a maximum
ule provides a collective address for the or provide smoke damper operation in of 5 seconds for a panel to process an
devices on its circuit. Newer modules smoke control systems. alarm after it is received from an initiat-
are now available featuring multiple ing device. The development of sensors
initiating circuits and provide different System programming also varies with that will operate in a cluster mode has
addresses for each of these circuits. the manufacturer. In the earlier days made this an easier matter. However,
some small system manufacturers it is common to use a larger number of
SLCs with fewer devices installed on
Some modules are small enough to fit used burn-in chips, or PROMS for
them rather than have one huge SLC
inside a device housing or backbox. the programming. Larger systems are
with numerous devices.
These modules are usually intended programmed via software. In these sys-
for connection to a single initiating tems, the programming is often done in
The addressable system is also pro-
device. An example of this would be a the office on a computer and then down-
grammed to make specific responses
module installed inside a pull station, loaded to the control panel in the field depending on the device activated.
providing an address for the station. via lap-top computer. Some software Thus the system can process an alarm
Some manufacturers preassemble the programs are user friendly while others from a sensor with complete alarm re-
monitor modules into pull stations, etc. are not, and usually require specialized sponse including notification of the fire
while others prefer to sell the module training. The easiest ones to use contain department and operation of elevator
only, and allow the installer to connect drop-down menus and the programmer capture devices, operation of smoke
the modules in the field. need only to literally “fill in the blanks” dampers, etc. It may also process a su-
in order to complete the program. pervisory signal from a tamper switch
Other monitor modules have an initiat- with sounding of dedicated appliances
ing 2-wire circuit that may be extended When the system is programmed, a only, or indicate that a control module
considerably, and can accommodate a description of the device can also be has been activated and has performed
specified number of conventional 2- included (in systems with alphanu- its required function.
wire compatible conventional smoke meric display) such as “ionization
detectors in addition to a number of sensor, main lobby, right wing”. Thus, Now that we have described the basic
dry contact initiating devices. This when the device goes into alarm, this operation of both conventional and ad-
module provides one address for each message will display on the readout, dressable fire alarm controls, our next
circuit, and is useful in large areas, such giving firefighters explicit information installment will concern itself with
as auditoriums, atriums or gymnasi- as to the location of the fire. smoke detection.

Page 30 IMSA Journal

Você também pode gostar