Você está na página 1de 19

20 -Year

Performance

I
of Bridge
Maintenance
Systems
By J. Peter Ault, P.E., Elzly Technology Corporation, and Christopher L. Farschon, P.E., Corrpro Companies Inc.
n the years 1986 and 1987, the New Jersey DOT applied 47 dif-
ferent coating systems to various individual spans of the Mathis
Bridge. The eastbound Mathis Bridge carries Route 37 over the
Barnegat Bay from Toms River to Seaside Heights, NJ. (The west-
bound span is a separate, newer, parallel structure, which was
not coated at this time.) Each experimental system was applied
to a complete span, with each span comprising approximately
4,000 square feet of steel. Experimental coating systems includ-
ed metallizing, various zinc-based systems, various levels of sur-
face preparation, and several overcoating strategies (e.g., an alkyd coating applied over a
hand-tool-cleaned surface).
This article will present the results of an inspection conducted in 2007, nominally 20
years after the initial coating application. The inspection showed varied service lives asso-
Editor’s note: This article is based on a ciated with the different coating systems. Some of the systems were in excellent condi-
paper the authors presented at the SSPC- tion after 20 years, while others had completely broken down. In addition to the present
PDCA joint conference, PACE 2008, in condition of the test spans, the article will review the historical performance of the vari-
Los Angeles, CA, January 27–30, 2008. ous coating systems as well as the applied cost. Finally, several important implications for

16 JPCL January 2009 www.paintsquare.com


Photos courtesy of the authors.

maintenance planners will be presented. for the evaluation of different mainte- ufacturers had a representative on site to
These will include cost-benefit calcula- nance painting methods. approve surface preparation, give mixing
tions and risk-reduction strategies. Subsequent to a laboratory evaluation instructions, and provide guidance
of available maintenance coatings, regarding any potential problems. State
History and Maintenance of the Mathis Bridge NJDOT awarded contract 85-2, Painting inspectors worked closely with the paint
New Jersey DOT’s ongoing evaluation of of the Mathis Bridge. The bid documents contractor and manufacturers’ represen-
various bridge coatings on the Thomas contained specifications for each experi- tatives to assure compliance with the
Mathis Bridge involves evaluating 66 mental paint system. Full containment of manufacturers’ and NJDOT’s minimum
spans plus a lift span. Each span is the blast abrasive and debris (using specification requirements. Painting
approximately 73 feet long and contains 1986-1987 technology) was required to began on October 11, 1986. Seven sys-
five rolled I-beam stringers of A-36 steel comply with environmental regulations. tems requiring spot cleaning were
spaced 8 feet apart. Each span contains applied before mid-November, when
approximately 4,000 square feet of Coating Systems weather conditions were no longer suit-
painted surface area. The bridge is situat- Eighteen manufacturers donated coat- able for any of the systems. (Some of the
ed over the salt water of Barnegat Bay, ings to be used on 47 of the 66 spans. systems were designed for application as
with vertical clearances from 5 feet at The experimental systems consisted of low as 40 F.) Painting resumed in April,
the abutments to 33 feet at the lift span. inorganic and organic zinc coatings, 1987, and was completed in October,
Upon construction in 1950, the struc- epoxies, aluminum epoxy urethanes, 1987.
ture was painted with three coats of an vinyls, urethanes, oil-alkyds, zinc metal-
oil-based paint containing red lead pig- lizing, aluminum metallizing, rust con- Inspections
ment. The bridge was painted three verters, and others. These systems repre- In addition to the data presented in the
times at various intervals over the next sented the most feasible options for original NJDOT report, the data present-
28 years. The painting work preceding maintenance overcoating or coating ed in this article is also the result of visu-
the 1986–87 experimental evaluation replacement on a bridge. Table 1 (p. 22) al inspections conducted by the authors
was performed in 1978. At that time, a provides a list of the coating systems in 1995 and 2007.
basic lead-silico chromate, oil alkyd sys- tested along with surface preparation, The NJDOT report included one-year
tem was used with a pigmented fascia application date, and span number. The performance evaluations conducted from
coating and “black graphite” on the inte- remaining spans were coated with the a snooper tuck.1,2 Visual ratings were
rior steel. standard NJDOT Zone 3B system, which given to each span based on the percent
In 1984, an inspection of the bridge consisted of a phenoxy organic zinc rusting of the bottom flange. This was
noted that rust and corrosion were primer and vinyl intermediate and finish deemed to be the harshest exposure and
extremely heavy on the bearing assem- coats. thus the best basis for ranking the sys-
blies, some stringer webs, and bottom The surface preparations ranged from tems after a short exposure period. The
flange of the stringers. Corrosion was SSPC-SP 2, Hand Tool Cleaning, to ratings were made in accordance with
especially concentrated on stringer ends SSPC-SP 5, White Metal Blast, depend- ASTM D610, Standard Method of
located at the bridge piers (i.e., steel in ing on the coating manufacturer’s recom- Evaluating Degree of Rusting on Painted
the path of run-off water form the bridge mendation. For systems requiring spot Steel Surfaces.
deck expansion joints). Rust scale on the cleaning, only loose rust and peeling As part of a FHWA project, three
steel was as thick as 1⁄ 2-inch. The existing paint were removed. Containment was inspectors performed a follow-up inspec-
paint was 15 to 25 mils (380 to 635 not erected during hand tool cleaning. tion of the structure in 1995.3 The
microns) in thickness. Concentrated salt Sand used for blasting was collected on inspections consisted of assigning a 1–10
deposits were visible on the steel direct- corrugated steel containment floors so rating to the entire span in accordance
ly beneath the deck joints. The severe that it could be removed for proper dis- with ASTM D610 based on visual
marine environment and road salt usage posal. assessment from a boat. The inspectors
create a severely corrosive environment Seventeen of the eighteen coating man- were 0 to 30 feet from the structure,

www.paintsquare.com JPCL January 2009 17


Before Termarust Before Termarust

After Termarust After Termarust

Termarust coated crevice corroded structure after 2 years. Termarust coated bearing after 7 years

Focus
Structure critical crevice corroded, pack rusted gusset plates, connections and corrosion frozen bearings

Opportunity
Save our deteriorating structural steel infrastructure with proactive coatings maintenance programs -
to chemically stop corrosion
The Solution
Termarust's High Ratio Co-Polymerized Calcium Sulfonate chemically active TR2200LV Penetrant/Sealer and
TR2100 Primer/Topcoat. This same formula has a 15 year field proven history of chemically stopping crevice
corrosion and pack rust.

Visit our website for the whole story


www.termarust.com • toll free 1-888-279-5497

Click our Reader e-Card at paintsquare.com/ric


depending on the span. Extensive pho- inherent variability in any coating sys- • Good condition–ASTM D610 rating
tographs were taken during the inspec- tem, the overall performance of a coat- better than “7” (less than 0.3% rusting)
tions. The ASTM D 610 ratings provid- ing system is not reliably quantified • Maintenance candidate–D610 rating
ed by three individual inspectors were with a single life expectancy. of “4” to “7” (from 0.3% to 10% rusting)
averaged to provide a composite rating. Quantifying a coating system life is bet- • Remove/recoat candidate–D610 rat-
In most cases, the inspectors’ ratings ter suited to a probabilistic or risk-based ing of “4” or below (more than 10% rust-
were within one unit of each other. For analysis. To make generalized conclu- ing)
the purposes of this paper, the authors sions, we grouped the 47 experimental Figure 2 shows the likelihood of
again rated the structures in 2007 using systems into eight generic categories as reaching each of the above defined con-
similar procedures to the 1995 inspec- shown in Table 1. ditions after 20 years for each coating
tion. Table 2 (p. 24) shows the number of system group. Notice how this figure
systems in each group meeting one of ranks the groups of coating systems by
Understanding the Results three classifications at two inspection performance, with the better performing
The results of the NJDOT test program times: Continued on p. 21
after one year of exposure indicated
mixed performance of overcoating sys- 10
tems.4 Those systems applied over an 9

8
2007 Rating (10 + perfect)

SSPC-SP 2 (hand-tool cleaned) surface


7
included alkyds, epoxies, and urethanes.
6
The epoxy mastic systems exhibited a

5
wide range of performance. Several dif-

4
ferent manufacturers’ versions of this

3
popular maintenance painting system

2
were applied over SP 2 surfaces. Some
of these systems had already failed at
the one-year inspection, while others 1

0
$0.00 $1.00 $2.00 $3.00 $4.00 $5.00 $6.00
were among the best performers over
“surface tolerant” conditions. Other sys-
tems performing well over SP 2 surfaces 1986 Cost
were a calcium borosilicate-pigmented
alkyd system and an oil-alkyd system. Fig. 1: Correlation between cost and condition after 20 years of service.

The one-year results for systems applied


over abrasive blasting were consistently
good, showing little differences between
systems.
Figure 1 presents the 2007 inspection
data on the Y-axis (ASTM D610–10 =
best, 0 = worst) versus the cost of the
coating system ($/ft2 in 1986/87 dol-
lars) on the X-axis. The data suggests a
trend toward increased performance
with increasing cost, but the relationship
has considerable scatter. Cost alone
would not be a good basis to assess the
overall value of a coating system simply
because there are so many other criteria
that play into the success of a coating
system.
Each of the tested coating systems
was a unique combination of coating and
surface preparation. Because of the Fig. 2: Coating systems by category, showing the likelihood of their overall condition at 20 years.

18 JPCL January 2009 www.paintsquare.com


Click our Reader e-Card at paintsquare.com/ric
Stretch your Maintenance Budget
ARMOR-SHIELD CSA Series
Calcium Sulfonate Alkyd

• Provides an impermeable barrier, adding years to service life


• 1 or 2 coat applications
• No abrasive blasting required, can be applied over blasted metals
• Surface tolerant over rust and existing coatings
• Apply as low as 0ºF - extend painting season 3 months
• Dries quickly to a firm film

Click our Reader e-Card at paintsquare.com/ric


epoxy systems show a low probability
of success and are most likely to be in
poor condition after eight years. The fol-
lowing paragraphs will explore some of
the coating groups in more detail. In par-
ticular, the performance of the individ-
ual systems with time is shown graphi-
cally. Note that the inspection basis at
one year was only the bottom flange.
This explains the apparent improvement
of some systems from year one to year
eight.

Metallizing Systems
The two metallizing systems are per-
forming extremely well, even after 20

10
Fig. 3: Risk assessment evaluation for each group
of coating systems

9
8
SP-6/WBIOZ/Si
7 SP-10/WBIOZ/Acry
SP-10/IOZ/VY
6 SP-10/IOZ/VY
Rating (10=new)

SP-6/IOZ/EP/Ure
5 SP-10/IOZ/EP/Ure
SP-6/OZ/Ure
4 SP-10/IOZ/VY

3
2
1
Photo 1: Close-up of bearings on
metallized systems.

0
0 5 10 15 20
groups to the left and the poorer groups
to the right.
Age, Years
A reasonable definition of a successful
coating system might be one that is “good” Fig. 4: 20-year performance of inorganic zinc systems.
at 8 years and only a “maintenance candi- 10
9
date” at 20 years. A reasonable definition

8
of “failure” might be a system that
SP-10/OZ/VY/VY
requires complete replacement after 8
7 SP-10/OZ/E/U
SP-10/OZ/U
years. Using these definitions, we can

6 SP-6/OZ/U
Rating (10=new)

determine a probability of success and a


SP-6/OZ/U
5
probability of failure for each generic
SP-6/OZ/E/U
SP-6/OZ/VY
maintenance strategy. Figure 3 shows the
4
probability of success, probability of fail-

3
ure, and the average applied cost for each
of the coating system groups.
Obviously, there are nuances in each of 2
1
the broad categories. Certainly the high

0
cost and high probability of success asso-

0 5 10 15 20
ciated with the metallizing are expected.
However, there is also a high probability
of success with the inorganic and organic Age, Years
zinc-based systems. The aluminum and Fig. 5: 20-year performance of organic zinc systems

www.paintsquare.com JPCL January 2009 21


Table 1. Summary of Test Coating Systems

Span Coating System Surface Preparation Application Date 1986 Cost ($/ft2)
Alkyd Systems (6)
7E Alkyd Oil Base/Si Alkyd SP-2 Nov. 86 $0.71
11E Alkyd/Epoxy/Urethane SP-2 Oct. 86 $1.04
21W Alkyd/Epoxy/Urethane SP-6 Aug. 87 $1.56
43W Oil - Alkyd SP-6 Oct. 87 $1.11
13W Oil Alkyd - 3 Cts SP-2 June 87 $0.73
31W Oil-Alkyd SP-6 Oct. 87 $1.37
Aluminum Systems (8)
41W Alum. Urethane/Acryl. SP-6 Sept. 87 $1.58
12E Alum. Epoxy/Urethane SP-7 Oct. 86 $1.00
9E Alum. Epoxy/Urethane SP-2/3 Nov. 86 $0.63
8E Alum. Epoxy/Urethane SP-2 Nov. 86 $1.07
6E Alum. Epoxy/Urethane SP-2 April 87 $0.60
5W Alum. Epoxy/Urethane SP-2 May 87 $0.70
45W Alum. Epoxy/Urethane SP-6 Oct. 87 $0.82
24W Alum. Ureth/Urethane SP-6 Sept. 87 $1.28
Epoxy Systems (6)
9W Epoxy Mastic/Epoxy Mast. SP-6 June 87 $1.00
17W Epoxy Mastic/Urethane SP-6 July 87 $1.25
18W Epoxy/Urethane SP-6 July 87 $1.29
32W Epoxy/Urethane SP-6 Oct. 87 $1.12
27W One Coat Epoxy SP-6 Sept. 87 $0.69
29W One Coat Epoxy SP-6 Oct. 87 $0.99
Inorganic Zinc Systems (8)
34W H20 Inorg. Prime/Silicone SP-6 Oct. 87 $1.67
30W H20 Inorg. Zinc/Acryl SP-10 Oct. 87 $1.99
42W Inorg. Zinc/Vinyl SP-10 Oct. 87 $1.56
46W Inorg. Zinc/Vinyl SP-10 Oct. 87 $1.26
14W Inorg. Zinc/Epoxy/Ur. SP-6 June 87 $1.85
35W Inorg. Zinc/Epoxy/Ure. SP-10 Oct. 87 $1.94
39W Inorg. Zinc/Urethane SP-6 Oct. 87 $1.07
12W Inorg. Zinc/Vinyl SP-10 June 87 $1.75
Metallizing Systems (2)
37W 100% Metallizing Zinc SP-5 Sept. 87 $4.72
38W 85% ZN - 15% Al Metallize SP-5 Sept. 87 $4.85
Miscellaneous Systems (5)
4E Calcium Boro-Silicate - 3Cts SP-2 May 87 $0.90
16W Calcium Boro-Silicate - 3Cts SP-6 July 87 $1.42
10W Latex - 3 Cts SP-10 June 87 $1.85
26W Thermoplastic Rubber SP-10 Sept. 87 $2.45
40W Vinyl/Acrylic SP-6 Oct. 87 $1.20
Organic Zinc Systems (7)
7W Org. Zinc/Epoxy/Uret. SP-10 May 87 $1.75
28W Org. Zinc/Urethan SP-6 Oct. 87 $1.33
20W Org. Zinc/Epoxy/Urethane SP-6 Aug. 87 $1.50
23W Org. Zinc/Urethane SP-6 Sept. 87 $1.48
25W Org. Zinc/Urethane SP-10 Sept. 87 $2.09
11W Org. Zinc/Vinyl SP-6 June 87 $1.75
15W Org. Zinc/Vinyl/Vinyl SP-10 July 87 $1.50
Urethane Systems (5)
33W Urethane 3-Coat SP-6 Oct. 87 $1.71
44W Urethane/Epoxy SP-6 Oct. 87 $1.19
10E Urethane/Epoxy/Urethane SP-2 Nov. 86 $1.01
5E Urethane/Epoxy/Urethane SP-2 Nov. 86 $1.55
19W Urethane/Epoxy/Urethane SP-6 Aug. 87 $1.55

22 JPCL January 2009 www.paintsquare.com


All our colors are Green.™

CrownShield ® SL CrownSpatter™ CrownPro™SparkShield CrownCove™& CrownHybrid™


JPCL 01-09

TURN GREEN INTO GOLD


Crown Products Are Good As Gold. Crown has become the industry leader In addition, Crown's Polymer College
Successful contractors and installers by offering innovative products, expert provides a level of marketing & sales
understand that Crown Polymers "Green" technical back-up and the finest customer support and hands-on technical training
products can help improve their bottom line. service in the business. As a result, an that is unmatched in the industry. If you
Long before the need was widely increasing number of architects, contractors are interested in learning more about how
recognized, Crown’s polymer scientists and installers are turning to Crown for the to maximize your profitability, talk to the
foresaw the demand for environmentally industry's most expansive line of decorative experts at Crown Polymers today.
sensitive building materials and began and industrial floor overlays.
producing zero VOC/HAP products. Today, Crown’s polymer scientists are
In today's competitive marketplace, creating new and improved standards that
savvy installers know that by using Crown are sure to have an industry-wide impact.
Polymers products they can reduce time
spent on the job site, lower labor costs and
Learn how to sell and install these unique
substantially increasing overall profitability systems at our Polymer College. Call Today!
on every project.
See CrownCove™ In Action!
View demonstrations of our vastly
WE’RE SETTING NEW INDUSTRY STANDARDS! improved precast cove system at
COME SEE WHAT WE’RE UP TO AT THE WORLD OF CONCRETE! The World of Concrete, booth S14327
VISIT BOOTHS: S14327 & SG22625

Corporate Headquarters: 888.732.1270 | www.crownpolymers.com | info@crownpolymers.com | Call For Manufacturer Representative Opportunities
Click our Reader e-Card at paintsquare.com/ric
Table 2: Distribution of Condition Ratings for Coating within Each Category performed unacceptably as defined by
the authors. This system was a water-
D610 Rating at 8 Years D610 Rating at 20 Years
borne inorganic zinc with a silicone
>7 7-4 <4 >7 7-4 <4 topcoat applied over an SP 6
Metallizing Systems (2) 2 0 0 2 0 0 (Commercial Blast) surface. The per-
Inorganic Zinc Systems (8) 7 0 1 2 5 1 formance of the inorganic zinc sys-
OZ Systems (7) 5 2 0 2 4 1 tems is quite interesting because of
the variety of systems evaluated.
Miscellaneous Systems (5) 3 2 0 1 3 1
Figure 4 (p. 21) shows the ratings over
Alkyd Systems (6) 4 2 0 1 3 2
time for each of the individual sys-
Urethane Systems (5) 2 3 0 1 2 2 tems. The dark blue lines correspond
Aluminum Systems (8) 1 4 3 0 4 4 to systems applied over an SP 10 sur-
Epoxy Systems (6) 0 4 2 0 0 6 face and the pink lines correspond to
systems applied over an SP 6 surface.
10
Comparable coating systems have sim-

9
ilar symbols. It is interesting to note

8
that the waterborne inorganic zinc
performed poorly over the SP 6 sur-

7
face, while the solvent-borne systems

6
Rating (10=new)

performed as well or better over the


SP 6 versus the SP 10 surfaces. This
5 performance is in contrast to the stan-

4
dard industry requirement that an

3
inorganic zinc coating should be
SP-2/Calcium Boro-Silicate
SP-6/Calcium Boro-Silicate
applied over an SP 10 surface to opti-
2 SP-10/3 ct Latex
mize coating performance.
SP-10/Rubber
1
SP-6/Vy/Acry
0
Organic Zinc Systems

0 5 10 15 20
The organic zinc systems performed
quite well as a class. Of the seven sys-
Age, Years tems tested, the only system that did
Fig. 6: 20-year performance of miscellaneous (not categorized) systems.
not perform well was one of the
organic zinc systems with a urethane
topcoat over an SP 6
years. At the 20-year inspection, the prepared surface. Figure
first signs of rusting were noted on 5 (p. 21) shows the per-
both the zinc and 85 Zn-15 Al metal- formance versus time of
lized spans. For both systems, the rust- the individual organic
ing was at the crevice between the zinc systems. Again, the
bearings and the stringer flange, and dark blue lines represent
on isolated lower flange spots (Photo systems over an SP 10
1) likely to be containment hanger surface, while the pink
locations. It appeared that the steel lines represent systems
was not rusting at any place where over an SP 6 surface.
the surface preparation and metalliz- Except for the organic
ing thickness were attainable. zinc/urethane system,
the data suggest that
Inorganic Zinc Systems equivalent performance
The inorganic zinc systems performed can be achieved over an
quite well as a class. Of the eight inor- Photo 2: WBIOZ system with good condition of web, SP 6 and SP 10 surface.
but poorer condition of bottom flanges
ganic zincs tested, only one system Continued on p. 26

24 JPCL January 2009 www.paintsquare.com


silicone pioneers

proven performers

materials protection experts

regulatory allies

knowledgeable advisors

proactive collaborators

environmental stewards

technology leaders

sustainability partners

problem solvers

road-block eliminators

innovative thinkers

solution providers

Dow Corning LV D UHJLVWHUHG WUDGHPDUN RI 'RZ &RUQLQJ &RUSRUDWLRQ ‹ 'RZ &RUQLQJ &RUSRUDWLRQ $OO ULJKWV UHVHUYHG $9 $9 $9

Lending a hand to sustainable construction.


YRX QHHG WR FRPSO\ ZLWK FKDQJLQJ HQYLURQPHQWDO UHJXODWLRQV EXW FDQQRW VDFUL¿FH SHUIRUPDQFH 'RZ &RUQLQJ VKDUHV
\RXU FRPPLWPHQW WR VXVWDLQDEOH FRQVWUXFWLRQ DQG ZRUNV ZLWK NH\ UHJXODWRU\ DJHQFLHV RQ \RXU EHKDOI :H OLVWHQ
XQGHUVWDQG DQG DFW WR SURWHFW WHFKQRORJLHV WKDW EHQH¿W \RXU EXVLQHVV DQG WKH HQYLURQPHQW :H DOVR EULQJ \RX
HIIHFWLYH new solutions. Learn more at www.dowcorning.com/construction.

Technical Information Centers:


Americas +1 989 496 6000
Europe +49 (0)611 237 778
Asia +86 21 3774 7110
E-mail: construction@dowcorning.com

Click our Reader e-Card at paintsquare.com/ric


Miscellaneous Systems performing of the low-cost (less than
Figure 6 presents the performance $1 per square foot) systems.
over time of the five miscellaneous sys-
tems. All of the systems were candi- Alkyd Systems
dates for maintenance after 20 years. Figure 7 shows the performance of the
Worth noting is the performance of the six alkyd systems over time. As a class,
calcium boro-silicate over the SP 2 sur- the alkyd systems generally performed
face. This system was the second-best well over the first eight years. One of
performing system over an SP 2 sur- the systems over SP 2 had an unac-
Photo 3: SP 2/Alkyd/epoxy/urethane face. At an applied cost of $0.90 per ceptable level of failure on the flange
coated span after 20 years. square foot in 1986, it was the best during NJDOT’s one-year inspection.
However, considering all of the alkyd
10 systems, there seems to be relatively

9
little benefit to an SP 6 surface prepa-

8
ration versus an SP 2 surface prepara-
tion. (See photo 3.)
7
SP-2/Alk Oil/ Si Alk
6 SP-2/Alk/Ep/Ure
Rating (10=new)

Urethane Systems
SP-6/Alk/Ep/Ure
5
As a group, the urethane systems per-
SP-6/oil-Alk
SP-6/oil-Alk
formed adequately during the first
4 SP-6/oil-Alk
eight years. Of particular note, the SP

3
2 surface preparation performed as
well as the SP 6 surface preparation.
2 Another observation is that the two-

1
coat system was one of the poorest

0
performers. Of the five systems tested,

0 5 10 15 20
the three better performing urethane
systems were all three coats with an
Age, Years epoxy intermediate coat. While consis-
Fig. 7: 20-year performance of alkyd systems. tent data on applied thickness was not
available for this study, the authors
have found through other overcoating
10 research that when surface prepara-

9
tion is minimal, more coating thickness

8
over the “bare” spots equated to better
performance.5
7
SP-6/3ct Ure
6 SP-6/Ure/EP
Rating (10=new)

Aluminum Systems
SP-2/Ure/EP/Ure
5
Figure 9 shows the performance of
SP-2/Ure/EP/Ure
SP-6/Ure/EP/Ure
the eight individual aluminum sys-

4
tems tested. As a class, these systems

3
did not perform well. Of note, the SP
7 surface preparation seemed to per-
2 form better than the SP 6 and SP 2.

1
Also notice that the abrasive blasting

0
surface preparations tended to per-

0 5 10 15 20
form better to the eight-year mark,
and then performance across all sur-
Age, Years face preparations tends to even out.
This observation emphasizes the
Fig. 8: 20-year performance of urethane systems.
Continued on p. 29

26 JPCL January 2009 www.paintsquare.com


Would you make a phone call
to save your company $5,000?

There’s a new way to lower tank coating costs. But there’s only one company to
call to realize the savings. So, if you are not talking to us about climate control,
you may be spending thousands more…on many projects…than you need to.

That’s because Munters’ new, patented HCU climate control system has been specifically designed
to hold the blast, while lowering energy costs. The HCU’s revolutionary design combines the world’s
most dependable desiccant dehumidifier with cooling. At the same time, the HCU recycles the
system’s waste heat to reactivate its desiccant wheel.

In addition, PowerPurge™ technology reduces the energy


required for re-activation while also reducing the discharge
temperature of the process air, resulting in lower energy
costs for post cooling.

On a recent cone roof tank in Louisanna, with 3,200,000


cubic feet of interior space, our HCU cut fuel consumption
cost by more than $10,000 for overall savings of nearly
$6,000 on the project. How much can your project save
using Munters new HCU technology? Make the call to
Munters HCU Dehumidifier
find out.

1-800-MUNTERS (686-8377) l mcsinfo@munters.com l www.munters.us


79 Monroe Street, PO Box 640, Amesbury, MA 01913-0640
Munters is an ISO 9000 Registered Company.

Click our Reader e-Card at paintsquare.com/ric


Click our Reader e-Card at paintsquare.com/ric
10 painting. Also notice that all of these

9
systems are only two coats.

8 Barrier Coatings
7 SP-6/Al Ure/Acry
This study included 30 barrier type
SP-7/Al Ep/Ure
6
Rating (10=new)

SP-2-3/Al Ep/Ure
coatings and 17 coatings with some kind

SP-2/Al Ep/Ure
5
of zinc metal in the primer. Barrier coat-
SP-2/Al Ep/Ure
ings essentially protect the substrate by
4 SP-2/Al Ep/Ure
SP-6/Al Ep/Ure
separating the environment from the

3 SP-6/Al Ure/Ure
surface. Although some of the barrier
systems contained inhibitive pigments,
2 we grouped all barrier coatings together

1
for this analysis. The zinc-containing

0
coatings arguably impart some sacrifi-

0 5 10 15 20
cial protection to a steel substrate and
were not considered in this analysis.
Age, Years Figure 11 shows averaged data for
the number of coats in a barrier coating
Fig. 9: 20-year performance of aluminum-based systems
system versus 20-year performance.
The trend indicates that applying more
coats will tend to improve performance.
rather difficult-to-predict situation in Epoxy Systems (6) Although this trend seems obvious, it is
which the replacement coating sys- Figure 10 shows the performance over important to consider the nature of the
tem may not perform over the long- time for the various epoxy systems. troublesome areas on a bridge (i.e., those
term as well as a “maintained” origi- These systems were among the worst spots that routinely cause low perfor-
nal coating system may perform. performers at the 8-and 20-year inspec- mance ratings). These areas/spots,
While this observation is interesting, tions. Notice that all of these systems when maintenance painted, are typically
note also that all of these systems are were applied to an SP 6 surface prepa- rusted and have no prior coating, so
D610 of 5 or less, very close to the ration—where most of the existing they become “bare spots” after surface
D610 rating of 4, selected as the lead-based coating would have been preparation. If we look at this data with
“coating system replacement” level of removed and where visible amounts of coverage of “bare spots” in mind, it is
performance. corrosion should be removed before Continued on p. 31

Click our Reader e-Card at paintsquare.com/ric

www.paintsquare.com JPCL January 2009 29


A MASTERPIECE
20 YEARS IN
THE MAKING
UNVEILING GENERATION 2009:
THE MOST PRODUCTIVE RECYCLER EVER

copyright 2009
Coming to PACE in New Orleans?
Don’t miss our VIP Advance Showing!
Call today for your free pass.

Click our Reader e-Card at paintsquare.com/ric


10

“We invented
9
8
7 the triple axle
recycler in 1989...
SP-6/Ep/EP
6 SP-6/Ep/Ure
Rating (10=new)

SP-6/Ep/Ure
5 SP-6/Ep/Ure
SP-6/Epoxy 20 years later,
this is truly our
4 SP-6/Epoxy

3
2 masterpiece”
1
0
0 5 10 15 20
Get 5% or greater
Age, Years productivity with Advantage SPS.
Fig. 10: 20-year performance of epoxy-based systems. Our 2009 generation recyclers routinely

10
produce 3 minutes or more blast “ON” time

9
per nozzle per

8
hour over the
competition --
7 which can move
6
Rating (10=new)

tens to hundreds of
5 1-coat systems (3) thousands of
2-coat systems (15)
4 3-coat systems (12)
dollars to your

3
bottom line.

2 Our 2009 models feature a variety of


1 patented improvements to increase

0
productivity, reliability, and safety, based on
0 5 10 15 20 our 20 years of engineering leadership in the
Age, Years industry. Advantage SPS systems cost a
Fig. 11: Performance by number of coats (non-zinc, non-metal systems). fraction to run versus the competition, and
offer the greatest reliability and simplicity to
operate. Call for a demo today and give it a
clear that the number of coats applied ing technologies have changed over the
increased the longevity of the coating 20 years since the test coatings were try to see for yourself.
system. This data re-affirms the mainte- applied, inspections provide excellent
nance painting practice of applying spot data to form the basis for risk-based
Click our Reader e-Card at paintsquare.com/ric

primers to areas of a prepared bridge decisions regarding maintenance of


with missing coating. It even suggests bridge coatings. The following general
that more than one spot primer may be conclusions can be made.
We Keep It Simple
appropriate for a longer lasting mainte- • In many of the instances, surface
nance overcoating system. preparation had less impact on the coat-
ing system life than might be expected.
See Advantage SPS at PACE,
Booth 750
Conclusions Given that surface preparation is a pri-
The original project provides an excel- mary cost driver, the opportunity may
lent comparative study of various main- exist to reduce cost with acceptable (per-
tenance-painting strategies. While coat- Continued on p. 32 800-800-7761
www.surfaceprep.com
www.paintsquare.com JPCL January 2009 email info@surfaceprep.com
haps even negligible) changes in perfor- risk, and cost associated with bridge Kauffman, Structural Coating
mance. coatings dictates that cost-benefit analy- Evaluation in New Jersey, Research
• By far the best performing systems sis be performed when selecting a suit- News, JPCL, January 1989,
were the metallizing systems. These sys- able system. pp. 23–26.
tems are only just beginning to show 3. C.L. Farschon, R.A. Kogler, and J.P.
rusting after 20 years. Of course, these Acknowledgements Ault, Guidelines for Repair and
systems were considerably more expen- The authors would like to acknowledge Maintenance of Bridge Coatings:
sive to apply. Currently, the cost dispari- the excellent work and innovative pro- Overcoating, August 1997, FHWA-
ty between metallizing and liquid coat- ject conducted by NJDOT. The authors RD-97-092.
ings is less than it was in 1987, although would also like to acknowledge Fred 4. Ibid.
the metallizing systems still carry a cost Lovett of NJDOT and Bob Kogler of 5. “Field Testing Maintenance
premium. Rampart, LLC for their help during dif- Overcoating Systems for Bridges,”
• Of the liquid-applied coating systems, ferent phases of this project. C.L. Farschon and R.A. Kogler, JPCL,
those containing an inorganic zinc or January 1997, Volume 14,
organic zinc primer performed best. The Notes Number 1, pp. 56–67.
epoxy systems and aluminum-mastic 1. A. Chmiel, V. Mottloa, and J.
systems performed worst. Kauffman, “Research on Structural
• The coating systems that are consid- Coatings Performance by New Jersey J. Peter Ault, P.E., (Elzy Technology
ered traditional overcoating materials Department of Transportation,” Corporation) has been involved in various
(i.e., non-zinc barrier type coatings) had presented at the 6th International aspects of corrosion control and materials
better performance when multiple coats Bridge Conference and Exhibition, engineering for over 17 years. He has
were applied. Pittsburgh, PA, 1989. worked on projects for the U.S. Army, Navy,
• The range of expected performance, 2. A. Chmiel, V. Mottloa, and J. and Marine Corps, and has extensive experi-
ence in the highway, oil & gas, and
water/wastewater industries. Mr. Ault, who
has been in charge of research and develop-
ment programs, field investigations, and
construction projects, is an active member
of several technical societies including
NACE, SSPC, ASTM, and NSPE. He earned a
BS in mechanical engineering and an MBA
from Drexel University (Philadelphia, PA), is
a registered Professional Engineer in several
states, and holds coatings specialist certifi-
cations from both NACE and SSPC.

Christopher Farschon is a senior engineer


and district manager with Corrpro
Companies Inc. in Ocean City, NJ. He man-
ages the company’s corrosion testing labo-
Click our Reader e-Card at paintsquare.com/ric

ratory and coatings services division in the


northeastern U.S. These offices perform
corrosion consulting and research for vari-
ous Department of Defense agencies and
provide coatings inspection services for var-
ious clients. Mr. Farschon holds a BS in
mechanical engineering from Drexel
University. He is a licensed professional
engineer, an SSPC member and Protective
Coatings Specialist, and a NACE certificated
coatings inspector. JPCL
32 JPCL January 2009 www.paintsquare.com
Concrete cracks.
CIM fights back.

A BREACH in your containment area can


rapidly become a serious financial,
environmental and regulatory nightmare.
Battle back. Coat it with CIM.
CIM forms a tough, permanently bonded and
impermeable barrier that keeps chemicals and
liquids where they
belong. It is highly
resistant to chemicals
across the full pH
range. And unlike rigid
coatings, CIM is a true
elastomer, maintaining
the flexibility to bridge
cracks throughout the
life of your containment
Over time, concrete cracks.
system. When cured, CIM is tough enough to drive
So do most protective coatings.
a truck on, yet will never become brittle.
Not CIM. It stays flexible
enough to accommodate When it comes to ease of application,
substrate movement, yet is other coatings need not apply.
strong enough to drive a truck A cost-effective, liquid-applied lining system with
on. CIM protects the environ- over thirty years of proven performance, CIM
ment from chemical spills while cures quickly for rapid return to service. For a
it maintains the integrity of permanent barrier in challenging environments,
your containment system. CIM is the solution.

C.I.M.
Industries
Inc.
KEEPING LIQUIDS
WHERE THEY BELONG
www.cimindustries.com
Tel 603.924.9481 800.543.3458
Fax 603.924.9482

Click our Reader e-Card at paintsquare.com/ric

Você também pode gostar