Escolar Documentos
Profissional Documentos
Cultura Documentos
a r t i c l e i n f o a b s t r a c t
Article history: In this paper, the Fault Current Limiter (FCL) is used to restore the coordination between the protection
Received 4 September 2014 devices in distribution systems with high-level of DG penetration. The FCL allocation may be described as
Received in revised form 4 October 2015 an optimization problem involving multiple objective functions which are contradictory and of different
Accepted 10 November 2015
dimensions. So, it is formulated as a multi-objective constrained nonlinear programming problem. The
interaction among different objectives gives rise to a set of compromised solutions, largely known as
the Pareto-optimal solutions. The objectives are to simultaneously minimize: the increase in fault current
Keywords:
levels due to the penetration of DG, voltage sag, and the total cost (size) of required limiters. The opti-
Protection coordination
Fault current limiter
mization problem is solved using Particle Swarm Optimization (PSO). The method is applied to two dis-
Voltage sag tribution test systems. Effects of different operating factors are assessed. Comparative analysis of results
DG is provided.
Ó 2015 Elsevier Ltd. All rights reserved.
Introduction between the recloser and fuses on a feeder. But this method limits
the size of DG connected to a system blocking other operational
Distributed generation (DG) is small generation units, inte- benefits of DG. In [7], Brahma and Girgis discussed a
grated to low or medium voltage distribution systems. DG can pro- microprocessor-based reclosing scheme to keep recloser-fuse coor-
vide emergency energy source, mitigate voltage violations, dination on a feeder with a high penetration level of DG. A method
improve service continuity, reduce power losses, and lessen unde- to modify recloser characteristics to achieve coordination is also
sired gas emissions [1–4]. Distribution protection system incorpo- described. The method assumes that DG will be disconnected
rates relays, reclosers and fuses. Reclosers are usually installed on before the recloser operates at the first time, which means that
main feeders with fuses on laterals. Reclosers lower service inter- the DG status must be continuously monitored. Also, disconnecting
ruptions because about 80% of faults that occur in distribution sys- the DG at every fault occurrence may degrade service reliability
tems are temporary. A recloser can clear a temporary fault before and quality because the faults on distribution feeders may be fre-
allowing a fuse to blow. Operation coordination of fuses, reclosers quent and temporary.
and relays is a crucial issue [5]. Fault Current Limiter (FCL) has emerged as an active and effec-
DG integration to a distribution network causes changes in fault tive way to limit fault currents [16,17]. It provides a sudden extra
current. So, the coordination between the protection devices is not impedance in the way of the fault current. Examples of FCL devices
assured. Many factors, such as size of DG, location of DG, and type are explosive limiters, solid state FCL, and superconducting FCL
of DG (static or rotating machine), would influence the share of DG [16]. In general, a FCL provides a small impedance under normal
in total fault current [2]. The impact of DG on overcurrent protec- system operating conditions and a large impedance during fault
tion devices in radial distribution systems is investigated in [6–15]. conditions. FCLs may lower system reliability, increase cost, and
Many problems occur because of DG integration. They include fuse increase operational complexity [18]. Application of FCLs for keep-
fatigue, nuisance fuse blowing, and recloser-fuse mis-operation. ing protection coordination is analyzed in [17–19]. The merits of
Several methods have been proposed to keep coordination of FCLs greatly depend on their sizes and locations [20]. In [15], a
protection devices in presence of DG [6–9]. Ref. [6] determines genetic algorithm is used to find the optimal FCLs to minimize fault
the maximum capacity of DG that would assure coordination current under DG integration. The same is done in [21] using
Particle Swarm Optimization (PSO). The method is applied to a
small-scale simple test system.
⇑ Corresponding author. Tel.: +20 502300779; fax: +20 507734015.
E-mail address: kelmitwally@yahoo.co.uk (A. Elmitwally).
http://dx.doi.org/10.1016/j.ijepes.2015.11.021
0142-0615/Ó 2015 Elsevier Ltd. All rights reserved.
10 A. Elmitwally et al. / Electrical Power and Energy Systems 77 (2016) 9–18
Usually, locations of FCL are assumed. Then, a simplified single- Recloser has two modes, fast mode that trips the circuit for tempo-
objective optimization problem is solved to get the size of FCL. The rary fault before the fuse operates, and slow mode that serves as
cost of FCLs is generally high as it typically involves power elec- backup protection when a fuse fails to blow up. The breaker is used
tronics or superconducting devices [16]. The FCL cost depends on as the entire backup protection when both the recloser and lateral
the resistive and inductive elements sizes (values). The total size fuses fail to isolate a fault on the feeder. A fuse has two character-
of determined FCLs might be prohibitively large that limit the eco- istics: ‘‘Minimum Melting (MM) and Total Clearing (TC)”. Breakers
nomic feasibility of applying FCL. So, special care should be given and reclosers are normally equipped with reverse-time overcur-
to FCLs size when FCL installing is studied to reduce stress on rent relays having the characteristics given in (1) [13].
power network equipment or to maintain protection coordination.
A
Hence, if the planner main objective is to achieve protection tðIÞ ¼ TD P
þB ð1Þ
devices coordination by FCLs, another crucial objective must be M 1
minimizing the size of the required FCLs. Besides, voltage sag where A, B and p are constants for particular curve characteristics; t
accompanies the occurrence of faults. It can cause tripping of crit- is operating time of device; M is ratio of I I (Ipickup is the relay cur-
pickup
ical loads leading to serious consequences. Voltage sag is mitigated
rent set point) and TD is time dial setting. The characteristic of fuses
by proper setting and coordination of overcurrent protection
is similar to reverse-time overcurrent relay characteristic. General
devices [8]. So, if overcurrent protection devices coordination is
equation of fuses follows (2) [13].
concerned on one side, the voltage sag level must be considered
on the other side. Allocation of FCLs can be done in such a way that logðtÞ ¼ a logðIÞ þ b ð2Þ
it optimizes average voltage sag in the network. Nonetheless, opti-
where t and I are the associated operating time and current, and the
mizing FCL cost and voltage sag level are not tackled in the
coefficients a and b are calculated from curve fitting.
reported studies.
In this paper, FCL is used to restore the recloser-fuse coordina-
tion without disconnecting DG. The FCL allocation problem Breaker–breaker mis-coordination
involves multiple objectives which are contradictory and of differ-
ent dimensions. Fig. 2 shows a distribution system with two radial feeders.
The novel aspects in the paper are: When a fault occurs at the upper feeder, the circuit breaker at this
feeder must operate. But the circuit breaker at the lower feeder
The FCL allocation problem is formulated as a multi-objective may operate because the DG feeds a fault current and it may lead
constrained nonlinear programming problem. The objectives to unnecessary electricity interruption on this healthy feeder. The
are to simultaneously minimize: the increase in fault current solution for the false tripping on healthy feeders is using a direc-
levels due to the penetrating of DG, average voltage sag level, tional overcurrent relay for the circuit breaker. Another solution
and the total cost (size) of the required FCLs. for this problem is using same or similar circuit breakers for both
Both the FCLs locations and sizes are searched. The FCLs loca- feeders [13].
tions are not assumed in advance like other studies. This results
in much reduced total size of FCLs. recloser-fuse mis-coordination
Effects of DG size, location, type, network configuration and FCL
type are investigated. Fig. 3 presents the time-current characteristics of the recloser
The proposed method is applied to both small-scale and large- and the fuse, as well as the short-circuit current across the fuse
scale test distribution networks. Comparative analysis of results before and after connecting DG. The penetration of DG will cause
is presented. mis-coordination between fuse and recloser. When a fault occurs
at the lateral feeder (see Fig. 1), the recloser at fast mode operates
The interaction among different objectives gives rise to a set of (opens) first to isolate the presumed temporary fault. If the fault
compromised solutions, known as Pareto-optimal solutions [22]. still remains when the recloser closes again after a specific time,
The optimization problem is solved using Particle Swarm Opti- the fuse at the lateral feeder should blow up to isolate the fault that
mization (PSO). is actually a permanent fault. If the fuse fails to operate, the reclo-
ser at slow-mode will operate as a backup protection. To obtain
this sequential operation, the fault current must rest between the
Protection coordination minimum and maximum currents shown in Fig. 3.
To illustrate the problem, a connected DG is assumed at the
Fig. 1 depicts the protection scheme in a typical distribution downstream end of a main feeder. If a fault occurs at a lateral fee-
network. Fuse must isolate permanent faults of the lateral feeder. der downstream the recloser, the fault current seen by the recloser
Substation
Breaker Recloser
Main Feeder
IF,Sub
IF,DG
Breaker
Recloser
DG
To ensure that the recloser in fast mode will operate before fuse
FUSE MM FUSE TC in MM mode, the fault current from DG must be lower than Imargin,
100
that is:
Current
Configuration A: Grid with all DG disconnected.
1 Configuration B: Grid with all DG connected.
R l
Recloser Sl d
Slow mode Configuration A represents the base case for which the settings
of protective devices are designed. The short circuit currents of this
configuration will be used as the reference values for configuration
0.1 B. The optimization problem is formulated such that the changes in
Recloser Fast mode fault currents passing through main and backup protective devices
MARGIN are minimized by optimal allocation of FCLs. Meanwhile, the cost
of the required FCLs is to be minimized. Assuming the same cost
for the per unit inductive impedance and the per unit resistance,
0.01 the p.u cost of FCLs is the same as the p.u size. The increased fault
100 1000 10000
current level after DG integration causes higher voltage drop on
Current, A
feeder sections and increased voltage sag at most of nodes. This
Fig. 3. Sample coordination of breaker, recloser, and fuse. is a severe power quality problem that results in loss of productiv-
ity due to undesired load tripping. Hence, it is targeted herein to
minimize the average voltage sag of the system nodes.
will be lower than that seen by the fuse because of the fault current The three objective functions are expressed as:
fed from DG. Fig. 3 shows the fault currents flowing through the
recloser and the fuse for this case. With these different fault cur- X
N X X
N
Min F1 ¼ absðIfuseBi IfuseAi Þ þ absðIrpBm IrpAm Þ þ absðIrbBn IrbAn Þ
rents seen by the fuse and recloser, fuse blowing may occur before i¼1 m n¼1
the recloser acts that means loss of recloser-fuse coordination. To ð5Þ
restore coordination, utilities can replace the protective devices
with higher rating devices to fit the extra fault current from DG. X
L
This may not be a good solution because the cost of replacement Min F2 ¼ ðRk þ X k Þ ð6Þ
and setting are considerable compared to the economic benefits k¼1
backup operation current for faults downstream of the nth fuse 1. Set the time counter t = 0 and generate randomly n particles,
with and without the DG, respectively. Rk and Xk represent the resis- {Xj(0), j = 1, . . ., n}. Similarly, generate randomly initial veloc-
tance and inductive reactance of the kth FCL. V ij is the p.u voltage at ities of all particles, {Vj(0), j = 1, . . ., n}. Each particle includes
bus i for a three-phase fault at bus j. M is the number of buses. values for all control variables to be optimized, resistance
The above problem is solved subject to: and inductance for each possible FCL. Set the initial value
of the inertia weight.
Rmin 6 Rk 6 Rmax ð8Þ 2. Insert the FCLs estimated by a particle (possible set of FCLs).
Apply a solid symmetrical three-phase fault at each bus con-
X min 6 X k 6 X max ð9Þ necting all DGs.
3. Calculate the objectives F1, F2 and F3 values for each particle
Ih;B Ih;A < e ð10Þ using (5), (6), and (7).
4. Search for the nondominated solutions and form the non-
where, dominated global set S⁄⁄(0). The best member in S⁄⁄(0) is
Rmin, and Rmax are lower and upper limits of Ri. selected as the global best Xj⁄⁄(0). Set the external set equal
Xmin, and Xmax are lower and upper limits of Xi. to S⁄⁄(0).
Ih,B is current of hth feeder section after DG connection. 5. Update the time counter t to t + 1.
Ih,A is current of hth feeder section before DG connection. 6. Update the inertia weight.
e is tolerance error. 7. Update the particle velocity and position.
8. The updated position of the jth particle is added to the set
Solution algorithm Sj⁄(t). Truncate the dominated solutions in Sj⁄(t). If the size
of Sj⁄(t) exceeds a maximum permissible limit, reduce it to
Single-objective PSO (SOPSO) and multi-objective PSO (MOPSO) the limit by the hierarchical clustering algorithm [24].
are used to solve many power system optimization problems 9. Perform the union of all nondominated local sets to produce
[22,23]. The decision of each individual in PSO depends on own the nondominated global set S⁄⁄(t). If the size of S⁄⁄(t)
experience together with other individuals’ experiences. The indi- exceeds a maximum limit, reduce its size by hierarchical
vidual particles are drawn randomly toward the position at present clustering algorithm.
velocity of each individual, their own previous best performance, 10. Copy the members of S⁄⁄(t) to the external Pareto set. If the
and the best previous performance of their neighbors [22,23]. number of the Pareto set members exceeds a maximum
The multiple-objective optimization problem has a set of differ- limit, reduce the set by means of clustering.
ent solutions (the so-called Pareto optimal set). Solving a multi- 11. Measure the individual distances between members in Sj⁄(t),
objective problem requires maximizing the number of elements and members in S⁄⁄(t) in the objective space. The members
of the Pareto optimal set and maximizing the spread of solutions of Sj⁄(t) and S⁄⁄(t) that give the minimum distance are
to make distribution of vectors as smooth as possible [22]. On selected as the local best and the global best, respectively.
extending PSO to MOPSO, one must decide how to select particles 12. If the termination criterion is met, then stop. Else go to step
to give preference to non-dominated solutions, and how to main- 2.
tain diversity in the swarm to avoid convergence to a single solu-
tion [22]. The flowchart of the proposed planning of the FCLs using
Each FCL is allowed to have a resistive component and an induc- MOPSO is shown in Fig. 5.
tive component. These components are series-connected and
inserted into a network branch. Thus, for the system in Fig. 4, a
maximum of 11 FCLs can be connected. This implies that 22 vari- Application
ables should be optimized.
The MOPSO-based solution algorithm is implemented as given The proposed MOPSO-based FCL planning algorithm is devel-
below. oped in MATLAB environment. It is applied to two test system.
12.47 kV 6 7 8 9
R2 500m 450m 550m 500m
F5 F6 F7 F8
T1
2MVA 2MVA 2MVA 2MVA
T3
DG2
2 3 4 5
R1 400m 500m
500m 425m
1 F1 F2 F3 F4
T2 2MVA
2MVA 2MVA 2MVA
DG1
Table 2
Evaluate the objective functions F1 , F2 and F3 Protection device fault currents using MOPSO, p.u.
Yes
Size of EPS ≤ limit
No
Reduce EPS size by clustering
Yes
n ≤ nmax
Fig. 6. Components R, X of the determined FCLs.
No
Yes
t ≤ tmax
in series to: each DG unit, utility source, and each feeder section.
No
Each FCL is composed of a resistive component and an inductive
Display component connected in series.
solution
Table 3
Protection devices fault currents in p.u and PSO results.
FCLs can reduce fault current to be nearly the same as its values Comparative evaluation
before DG is integrated. This assures that no protection mis- Using a single objective function (only F1 given in (5)), three
coordination occurs. Fig. 7 depicts the node voltages for different FCLs are found sufficient. Their locations are at the utility source
symmetrical fault locations when the optimal FCLs are installed. and at each DG unit. Their optimal component values are provided
It also compares the results for the case without DG and without in bottom cell of fourth column in Table 3. The same results are
FCL under DG. The FCL presence much improves the node voltage almost obtained in [21]. On the other hand, when the proposed
under fault conditions. This improves voltage sag and lessens the multi-objective formulation is applied considering only the two
probability of critical loads tripping under fault conditions. objectives F1, F2 (without voltage sag), only one inductive FCL with
voltage,pu
0.04 0.15
voltage,pu
0.1 0.5
0.02
0.05
0 0 0
0 2 4 6 8 10 0 2 4 6 8 10 0 2 4 6 8 10
bus number bus number bus number
voltage,pu
voltage,pu
0.15
0.05
0 0 0
0 2 4 6 8 10 0 2 4 6 8 10 0 2 4 6 8 10
bus number bus number bus number
voltage,pu
voltage,pu
0 0 0
0 2 4 6 8 10 0 2 4 6 8 10 0 2 4 6 8 10
bus number bus number bus number
without DG with DG and without FCL with DG and with FCL
Table 4
Protection devices fault currents for various FCL placement strategies using MOPSO, p.u.
With source FCL Only With DG FCL only With DG and source FCL
IF1 1.7190 1.5940 1.5278
IF2 1.5782 1.4476 1.4108
IF3 1.4709 1.3416 1.3217
IF4 1.3593 1.2355 1.2289
IF5 1.7074 1.57 1.5111
IF6 1.5808 1.44 1.4064
IF7 1.5423 1.3786 1.3712
IF8 1.4181 1.2655 1.2700
IR1(P) 1.2329 1.4756 1.3435
IR2(P) 1.2302 1.4841 1.3468
IR1(BF1) 1.1742 1.4466 1.2746
IR1(BF2) 1.0813 1.3177 1.1805
IR1(BF3) 1.0098 1.2237 1.1082
IR1(BF4) 0.9341 1.1280 1.0314
IR2(BF5) 1.1630 1.4289 1.2607
IR2(BF6) 1.0799 1.3146 1.1768
IR2(BF7) 1.0558 1.2611 1.1497
IR2(BF8) 0.9718 1.1587 1.0659
FCL location (series to) FCL size, p.u
With source FCL Only With DG FCL only With DG and source FCL
DG1 4.2805 0.045 + j2.0839
DG2 4.48 + j0.0019 0.0312 + j2.1263
Utility source j0.7401 0.0086 + j0.2163
Value of objective F1 0.7315 1.93 0.4087
impedance 0 + j0.7401 p.u is found sufficient at the utility source. location as before. For the resistive FCL type, the value of the FCL
Table 3 presents the fault currents passing through the various resistance is 0.735 p.u with a value of 0.922 p.u for the objective
protective devices without DG, with DG but with no FCL, and with function F1. For the inductive FCL, the value of the inductive reac-
both DG and the FCLs for SOPSO (F1) and MOPSO (F1 and F2) cases. tance is J0.729 p.u with a value of 0.803 p.u for the objective func-
Strategic locations, usually next to power sources, can be selected tion F1. It is noted that the impedance magnitude of the FCL is
for placing FCLs and the problem is solved to get the FCLs sizes. nearly equal for both types with a bit better current damping capa-
Table 4 shows the fault currents passing through the various pro- bility for the inductive type FCL. Both types maintain protection
tective devices for different FCLs locations under DG. The FCLs devices coordination. So, the cost of FCL can be a decisive factor
components sizes are determined using MOPSO with two objec- in choosing the FCL type.
tives F1 and F2 and provided in the bottom of Table 4.
For both the single objective and multi-objective formulations, Effect of DG location on FCL planning
the FCLs keep the fault current levels close to the original values The two DG units basically located at bus 2 and bus 6 as
(without DG). The small increase in branch fault current is always depicted in Fig. 4 are moved to other locations. The required FCLs
less than the margin allowed to maintain coordination as discussed are determined using the proposed mlti-objective (F1 and F2) FCL
in Section ‘Protection coordination’. Assuming the device inverse planning algorithm under the rest of conditions as the same as Sec-
characteristics as given in Fig. 3, the protection coordination is tion ‘Canadian benchmark system’. A. For all examined DG loca-
assured even with the two DG units connected due to the inclusion tions, the results indicate that only one composite-impedance
of FCLs in optimal locations and sizes. FCL is required at the utility source. Its size depends on the new
It is worthy noting that the proposed multi-objective formula- DG locations as given in Table 5. It is observed that the location
tion results in less number and sizes of FCLs required to maintain of DG units in a radial distribution network, like the one shown
protection coordination under DG in comparison to the single- in Fig. 4, has a minor effect on the FCL placement and sizing.
objective formulation. This provides technical simplicity and eco-
nomic savings to the distribution network operators. To reduce Effect of DG size
the solution time, by reducing the search space, one can assume The size of the two DG units located at bus 2 and bus 6 as
the FCLs locations and searches only the FCLs components sizes. depicted in Fig. 4 are changed. The required FCLs are determined
Three candidate sets of FCL locations are evaluated as given in using the proposed multi-objective (F1 and F2) FCL planning algo-
Table 4. The first is to locate a FCL after the utility source. The sec- rithm under the rest of conditions as the same as Section ‘Canadian
ond is to locate a FCL in series to each DG unit. The third is to locate benchmark system’. Up to a certain penetration level of DG, the
a FCL in series to each power source (the utility and DG). results indicate that only one composite-impedance FCL is
Table 6
Effect of DG size on FCL.
DG size, MVA DG data Utility source FCL size, p.u DG FCL size, p.u Value of objective functions
DG1 DG2 F1, p.u F2, p.u
1.5 1.5 [25] 0.002 + J0.0684 0 0.0046 0.0704
3.75 3.75 [25] 0.01 + J0.1313 0 0.0238 0.1413
8 8 [20] J0.7401 0 0.7315 0.7401
0 30.4 [26] 0.0103 + J0.3604 0.0509 + J0.6664 0.1245 1.088
a radial distribution network, like the one shown in Fig. 4, has a sig-
Table 7
nificant effect on the FCL placement and sizing.
Effect of system configuration on FCL.
DG2
F27 F28 F29 F30 F31 F32 F33 F34
R4
40 41 55 56 57 58
F1 F2 F3 F4 F5 F6 F7 F8 F9 F10 F11 F12 F13 F14 F15 F16 F17 F18 F19 F20 F21 F22 F23 F24 F25 F26
Utility
source
R1
R2 R3
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27
F35 F36 F37 F38
F41 F42 F43 F44 F45 F46 F47 F48 F49 F50 F51 F52 F53
DG1
R5
R6
36 37 38 39
42 43 44 45 46 47 48 49 50 51 52 53 54
F58 F59 F60 F61 F62 F63 F64 F65 F66 F67 F68
R7 DG3
59 60 61 62 63 64 65 66 67 68 69
DG4
0.1
R,X, p.u
0.05 (a)
0
L1-2 L2-3 L3-4 L4-5 L5-6 L6-7 L7-8 L8-9 L9-10 L10-11 L11-12 L12-13 L13-14 L14-15 L15-16 L16-17 L17-18 L18-19
FCL Location
0.1
R,X, p.u
0.05 (b)
0
L19-20 L20-21 L21-22 L22-23 L23-24 L24-25 L25-26 L26-27 L3-28 L28-29 L29-30 L30-31 L31-32 L32-33 L33-34 L34-35 L4-36 L36-37
FCL Location
0.1
R,X, p.u
0.05 (c)
0
L37-38 L38-39 L8-40 L40-41 L9-42 L42-43 L43-44 L44-45 L45-46 L46-47 L47-48 L48-49 L49-50 L50-51 L51-52 L52-53 L53-54 L11-55
FCL Location
0.1
R,X, p.u
0.05 (d)
0
L55-56 L56-57 L12-58 L58-59 L3-60 L60-61 L61-62 L62-63 L63-64 L64-65 L65-66 L66-67 L67-68 L68-69SOURCE DG1 DG2 DG3 DG4
FCL Location
X R
(a)
5 69-bus test system
0 The optimal FCL component values are determined for the 69-
0 10 20 30 40 50 60 70
bus test system depicted in Fig. 8. The system data is given in
fuse number
[27]. This network has 7 reclosers, 68 fuses and 4DG units. It is
desired to maintain the coordinated operation of these protection
10 without DG with DG and no FCL with DG and FCL devices by installing FCLs. Each FCL is composed of a resistive com-
Current, p.u
1
0.5 (b) currents are shown in Fig. 10a and the recloser currents are shown
0 in Fig. 10b. It is noted that application of optimal FCLs reduces fault
0 10 20 30 40 50 60 70
currents to nearly its values without DG. This maintains protection
bus number
coordination even when DG is connected. Fig. 11 depicts the nodes
Voltage, p.u
FCLs components’ sizes at possible locations are shown in Fig. 9. international conference on probabilistic methods applied to power systems,
Stockholm, Sweden, June 11–15; 2006. p. 1–8.
Zero values of both R and X at some locations indicate that no
[5] Sa’ed J, Favuzza S, Ippolito M, Massaro F. An investigation of protection devices
FCL is needed at this location. It is noted that the required FCLs coordination effects on distributed generators capacity in radial distribution
are mostly resistive. Values of X are generally very small. A big- systems. In: IEEE/PES transmission and distribution conference and
size FCL is located in series to the utility power source. No FCLs exposition: Latin America; 2010. p. 110–5.
[6] Chaitusaney S, Yokoyama A, Fazanehrafat A, Javadian S, Bathaee S, Haghifamt
are required in series to DG units. Fig. 10 presents the symmetrical M. Maintaining the recloser-fuse coordination in distribution systems in
fault currents passing through the various protective devices under presence of DG by determining DG’s size. In: Proc IET 9th international
three conditions: without DG, with DG but without FCL, and with conference on developments in power system protection; 2008. p. 132–7.
[7] Brahma S, Girgis A. Microprocessor-based reclosing to coordinate fuse and
both DG and FCLs. The fuse currents are shown in Fig. 10a and recloser in a system with high penetration of distributed generation. In: Proc
the recloser currents are shown in Fig. 10b. It is noted that applica- IEEE power engineering society winter meeting; 2002. p. 453–8.
tion of optimal FCLs reduces fault currents to nearly its values [8] Gomez J, Morcos M. Coordination of voltage sag and overcurrent protection in
DG system. IEEE Trans Power Delivery 2005;20(1):214–8.
without DG. This maintains protection coordination even when [9] Brahma S, Girgis A. Development of adaptive protection scheme for
DG is connected. Fig. 11 depicts the nodes voltages for different distribution systems with high penetration of distribution generation. IEEE
symmetrical-fault locations when the optimal FCLs are installed Trans Power Delivery 2004;19(1):56–63.
[10] Distribution Line Protection Practices Report; 2002. Available: <http://www.
with DG. It also compares the results for the base case (without pes-psrc.org/Apublications.html>.
DG) and the case of integrating DG without FCL. The FCL presence [11] Hamed B, Butler-Purry K. An approach to mitigate the impact of distributed
much improves the node voltage under fault conditions. This mit- generation on the overcurrent protection scheme for radial feeders. In: IEEE/
PES Power Systems Conference and Exposition, PSCE ’09; 2009. p. 1–11.
igates voltage sag and lessens the probability of critical loads trip-
[12] Martinez J, Martin-Arnedo J. Impact of distributed generation on distribution
ping under fault conditions. protection and power quality. In: IEEE Power & Energy Society general
meeting, PES ’09; 2009. p. 1–6.
[13] Chaitusaney S, Yokoyama A. Impact of protection coordination on sizes of
Conclusions several distributed generation sources. In: The 7th International Power
Engineering Conference, IPEC 2005, vol. 2; 2005. p. 669–74.
The fault current limiter is used to restore the recloser-fuse [14] Hongesombut K, Mitani Y, Tsuji K. Optimal location assignment and design of
superconducting fault current limiters applied to loop power systems. IEEE
coordination in distribution system with DGs. The FCL allocation Trans Appl Supercond 2003;13(2):1828–31.
problem involves more than one objective function which are con- [15] Teng Jen-Hao, Lu Chan-Nan. Optimum fault current limiter placement. In: ISAP
flicting. So, it is formulated as a multi-objective constrained non- 2007; 2007. p. 1–6.
[16] Elmitwally A. Proposed hybrid superconducting fault current limiter for
linear programming problem to simultaneously minimize: the
distribution systems. Int J Electr Power Energy Syst 2009;31(10):619–25.
increase in fault current levels due to DGs, node voltage sag, and [17] Lim Sung-Hun, Kim Jae-Chul. Analysis on protection coordination of protective
the total cost (size) of required limiters. The optimization problem devices with a SFCL due to the application location of a dispersed generation in
a power distribution system. IEEE Trans Appl Supercond 2012;22(3).
is solved using PSO. The results obtained by the proposed formula-
[18] Zhang Y, Dougal R. Novel dual-FCL connection for adding distributed
tion surpass those obtained by single-objective formulation. The generation to a power distribution utility. IEEE Trans Appl Supercond
former yields an adequate fault current damping at much reduced 2011;21(3).
FCLs cost and tangibly mitigated node voltage sag. Including volt- [19] Zhang Y, Dougal R. Specification of fault current limitation level for FCLs in
power systems. In: Proceedings of the IEEE southeast con; 2010. p. 246–9.
age sag requires small-size FCL to be installed in every section in [20] Cakal G, Bagriyanik F, Bagriyanik M. The effect of fault current limiters on
the distribution system. Otherwise, few FCLs are generally required distribution systems with wind turbine generators. Int J Renewable Energy Res
in series to power sources. DGs sizes, locations, types, and network 2013;3(1).
[21] Zeineldin H, Xiao W. Optimal fault current limiter sizing for distribution
topology evidently affects the FCLs allocation. systems with DG. In: IEEE power & energy society general meeting; 2011. p. 1–
5.
References [22] Reyes-sierra M, Coello C. Multi-objective particle swarm optimizers: a survey
of the state-of-the-art. Int J Comput Intell Res 2006;2(3):287–308.
[23] Park Jong-Bae, Lee Ki-Song, Shin Joong-Rin, Lee Kwang. A particle swarm
[1] Tang G, Iravani MR. Application of a fault current limiter to minimize
optimization for economic dispatch with non smooth cost functions. IEEE
distributed generation impact on coordinated relay protection. In: Presented
Trans Power Syst 2005;20(1).
at the International conference on Power Systems Transients IPST’05,
[24] Chen M, Zhang C, Luo C. Adaptive evolutionary multi-objective particle swarm
Montreal, Canada, June 19–23; 2005.
optimization algorithm. Control Decis 2009;24(12):1851–5.
[2] Khan U. Impact of distributed generation on electrical power network. <www.
[25] Distributed Generation Modeling Guidelines. Synchronous Machine Data EPRI
wppt.pwr.wroc.pl>.
TR1000418.
[3] Begović M, Pregelj A, Rohatgi A. Impact of renewable distributed generation on
[26] Talkha Gas Turbine Power plant. <www.moee.gov.eg>.
power systems. In: Proceedings of the 34th Hawaii international conference on
[27] Soudi Saeid. Distribution system planning with distributed generations
system sciences; 2001.
considering benefits and costs. Int J Modern Educ Comput Sci 2013;9:45–52.
[4] Chaitusaney S, Yokoyama A. Reliability analysis of distribution system with
distributed generation considering loss of protection coordination. In: 9th