Você está na página 1de 7

PT. SKEMANUSA CONSULTAMA TEKNIK JOB No. DOC. No. REV.

LAPORAN PERENCANAAN INSTALASI LAK P – 1026 TPIB – LAK – 01 0


ADMIRALTY APARTMENT TAHAP III
JAKARTA SHEET 1 OF 7

4.0.4. LAMPIRAN PENENTUAN RESISTANSI DAN REAKTANSI PADA SETIAP BAGIAN

RESISTANSI REAKTANSI
BAGIAN DARI INSTALASI
(m Ohm) (m Ohm)

R1 = Z1 COS φ X1 = Z1 sin φ
JARINGAN SISI ATAS COS φ = 0,15 sin φ = 0.96
(SISI TEGANGAN MENENGAH)
U02
Z1 = ---------------------
P
P = Daya hubungan pendek pada
jaringan sisi atas dalam MVA

R2 = Wc x U02 x 10 -3 X2 = √ Z22 - R22

S2
TRANSFORMATOR S = Daya terpasang Z2 = USC U02
Transformator ( KVA ) ------- x -------
100 S
Wc = Rugi – rugi tembaga USC = Tegangan Hubung
Pendek Transformator (%)

L
(2)
R3 = ρ ------
S X3 = 0.08 L (Kabel Tiga Phase)
(1)
KABEL
(3)
L = Panjang kabel dalam m X3 = 0.12 L (Kabel Satu
ρ = 22.5 (CU) atau 36 (AI) Phase)
S = Luas Penampang Kabel ( mm2)

L
REL R3 = ρ ------ X3 = 0.15 L
S
L dalam (M)
L = Panjang Rel (M)
ρ = 22.5 (CU) atau 36 (AI)
S = Luas Penampang Kabel (mm2)

4.0.5. CONTOH PERHITUNGAN ARUS HUBUNG SINGKAT


PT. SKEMANUSA CONSULTAMA TEKNIK JOB No. DOC. No. REV.

LAPORAN PERENCANAAN INSTALASI LAK P – 1026 TPIB – LAK – 01 0


ADMIRALTY APARTMENT TAHAP III
JAKARTA SHEET 2 OF 7

a. Untuk rangkaian TM – Trafo.PO (800 kVA) – PDTR.PO

DIAGRAM RESISTANSI REAKTANSI


BAGIAN DARI INSTALASI
(m Ohm) (m Ohm)
20.0002 20.0002
JARINGAN SISI ATAS
M0 R1 = --------- x 0,15 X 10-6 X1 = --------- x 0,98 X 10-6
(SISI TEGANGAN MENENGAH)
500 500
Psc = 500 MVA
R1 = 0,12 Ohm X1 = 0,784 Ohm

TRANSFORMATOR 10.850 x 400² x 10 -3 X2 =


S = 800 KVA
Usc = 4,5%
U = 400 V
Wc = 10.850 W
R2 = ---------------------------------

R2 = 2,71
800²
 
4,5 400 2 2
×
100 800
 −2,71
2

X2 = 8,58

KONEKSI KABEL DARI 22,5 x 5


TRANSFORMATOR KE R3 = -------------------- X3 = 0,08 x 5
PEMUTUS DAYA 3 x 240
NYY 3 X 1C X 240 mm 2
L = 5m = 0,16 X3 = 0,40

X
M1 PEMUTUS DAYA CEPAT R4 = 0 X4 = 0

Panel
Utama KONEKSI REL PEMUTUS 22,5 x 6
BATANG-BATANG (Cu) R5 = -------------- X5 = 0,15 x 6
4 X 50 X 10 mm2 500
L = 6m = 0,90
R5 = 0,27

X
M2 PEMUTUS DAYA CEPAT R6 = 0 X6 = 0

Perhitungan Arus Hubung Singkat (kA)


PT. SKEMANUSA CONSULTAMA TEKNIK JOB No. DOC. No. REV.

LAPORAN PERENCANAAN INSTALASI LAK P – 1026 TPIB – LAK – 01 0


ADMIRALTY APARTMENT TAHAP III
JAKARTA SHEET 3 OF 7

RESISTANSI REAKTANSI Isc


( m Ohm ) ( m Ohm ) ( kA )

20.000
Pada M0 RT0 = R1 XT0 = X1 √ 3 √( 0,12 2
+ 0,7842)
RT0 = 0,12 Ohm XT0 = 0,784 Ohm
= 14,56 kA

400
Pada M1 RT1 = R2 + R3 XT1 = X2 + X3 √ 3 √( 2,87 2
+ 8,9822)
RT1 = 2,87 XT1 = 8,982
= 24,49 kA

400
Pada M2 RT2 = RT1 + R4 + R5 XT2 = XT1 + X4 + X5 √ 3 √( 3,14 2
+ 9,8822)
RT2 = 3,14 XT2 = 9,882
= 22,27 kA

b. Untuk rangkaian TM – Trafo.A / B (1000 kVA) – PDTR.A / PDTR.B


PT. SKEMANUSA CONSULTAMA TEKNIK JOB No. DOC. No. REV.

LAPORAN PERENCANAAN INSTALASI LAK P – 1026 TPIB – LAK – 01 0


ADMIRALTY APARTMENT TAHAP III
JAKARTA SHEET 4 OF 7

DIAGRAM RESISTANSI REAKTANSI


BAGIAN DARI INSTALASI
(m Ohm) (m Ohm)
20.0002 20.0002
JARINGAN SISI ATAS
M0 R1 = --------- x 0,15 X 10-6 X1 = --------- x 0,98 X 10-6
(SISI TEGANGAN MENENGAH)
500 500
Psc = 500 MVA
R1 = 0,12 Ohm X1 = 0,784 Ohm

TRANSFORMATOR 14.400 x 400² x 10 -3 X2 =


S = 1.000 KVA
Usc = 5%
U = 400 V
Wc = 14.400 W
R2 = ---------------------------------

R2 = 2,3
1.000²
 
5
×
400 2 2
100 1.000
 −2,3
2

X2 = 7,66

KONEKSI KABEL DARI 22,5 x 5


TRANSFORMATOR KE R3 = -------------------- X3 = 0,08 x 5
PEMUTUS DAYA 4 x 300
NYY 4 X 1C X 300 mm 2
L = 5m = 0,09 X3 = 0,4

X
M1 PEMUTUS DAYA CEPAT R4 = 0 X4 = 0

Panel
Utama KONEKSI REL PEMUTUS 22,5 x 5,6
BATANG-BATANG (Cu) R5 = -------------- X5 = 0,15 x 6
4 X 60 X 10 mm2 600
L = 6m = 0,90
R5 = 0,17

X
M2 PEMUTUS DAYA CEPAT R6 = 0 X6 = 0

Perhitungan Arus Hubung Singkat (kA)


PT. SKEMANUSA CONSULTAMA TEKNIK JOB No. DOC. No. REV.

LAPORAN PERENCANAAN INSTALASI LAK P – 1026 TPIB – LAK – 01 0


ADMIRALTY APARTMENT TAHAP III
JAKARTA SHEET 5 OF 7

RESISTANSI REAKTANSI Isc


( m Ohm ) ( m Ohm ) ( kA )

20.000
Pada M0 RT0 = R1 XT0 = X1 √ 3 √( 0,12 2
+ 0,7842)
RT0 = 0,12 Ohm XT0 = 0,784 Ohm
= 14,56 kA

400
Pada M1 RT1 = R2 + R3 XT1 = X2 + X3 √ 3 √( 2,40 2
+ 8,0612)
RT1 = 2,40 XT1 = 8,061
= 27,46 kA

400
Pada M2 RT2 = RT1 + R4 + R5 XT2 = XT1 + X4 + X5 √ 3 √( 2,62 2
+ 8,9612)
RT2 = 2,62 XT2 = 8,961
= 24,73 kA

c. Untuk rangkaian TM – Trafo.C / D (1250 kVA) – PDTR.C / PDTR.D


PT. SKEMANUSA CONSULTAMA TEKNIK JOB No. DOC. No. REV.

LAPORAN PERENCANAAN INSTALASI LAK P – 1026 TPIB – LAK – 01 0


ADMIRALTY APARTMENT TAHAP III
JAKARTA SHEET 6 OF 7

DIAGRAM RESISTANSI REAKTANSI


BAGIAN DARI INSTALASI
(m Ohm) (m Ohm)
20.0002 20.0002
JARINGAN SISI ATAS
M0 R1 = --------- x 0,15 X 10-6 X1 = --------- x 0,98 X 10-6
(SISI TEGANGAN MENENGAH)
500 500
Psc = 500 MVA
R1 = 0,12 Ohm X1 = 0,784 Ohm

TRANSFORMATOR 17.500 x 400² x 10 -3 X2 =


S = 1.250 KVA
Usc = 5,5%
U = 400 V
Wc = 17.500 W
R2 = ---------------------------------

R2 = 1,79
1.250²
 
5,5 400 2 2
×
100 1.250
 −1,79
2

X2 = 6,81

KONEKSI KABEL DARI 22,5 x 5


TRANSFORMATOR KE R3 = -------------------- X3 = 0,08 x 5
PEMUTUS DAYA 4 x 300
NYY 4 X 1C X 300 mm 2
L = 5m = 0,09 X3 = 0,4

X
M1 PEMUTUS DAYA CEPAT R4 = 0 X4 = 0

Panel
Utama KONEKSI REL PEMUTUS 22,5 x 6
BATANG-BATANG (Cu) R5 = -------------- X5 = 0,15 x 6
4 X 80 X 10 mm2 800
L = 6m = 0,90
R5 = 0,17

X
M2 PEMUTUS DAYA CEPAT R6 = 0 X6 = 0

Perhitungan Arus Hubung Singkat (kA)


PT. SKEMANUSA CONSULTAMA TEKNIK JOB No. DOC. No. REV.

LAPORAN PERENCANAAN INSTALASI LAK P – 1026 TPIB – LAK – 01 0


ADMIRALTY APARTMENT TAHAP III
JAKARTA SHEET 7 OF 7

RESISTANSI REAKTANSI Isc


( m Ohm ) ( m Ohm ) ( kA )

20.000
Pada M0 RT0 = R1 XT0 = X1 √ 3 √( 0,12 2
+ 0,7842)
RT0 = 0,12 Ohm XT0 = 0,784 Ohm
= 14,56 kA

400
Pada M1 RT1 = R2 + R3 XT1 = X2 + X3 √ 3 √( 1,89 2
+ 7,2082)
RT1 = 1,89 XT1 = 7,208
= 31 kA

400
Pada M2 RT2 = RT1 + R4 + R5 XT2 = XT1 + X4 + X5 √ 3 √(2,05 2
+ 8,1082)
RT2 = 2,05 XT2 = 8,108
= 27,61 kA

Você também pode gostar