Paper n° 697
CIRED2019 1/5
25thInternational Conference on Electricity Distribution Madrid, 3-6 June 2019
Paper n° 697
CIRED2019 2/5
25thInternational Conference on Electricity Distribution Madrid, 3-6 June 2019
Paper n° 697
End-to-end Slight deviations in all windings End-to-end Slight deviations in all windings
CIRED2019 3/5
25thInternational Conference on Electricity Distribution Madrid, 3-6 June 2019
Paper n° 697
CIRED2019 4/5
25thInternational Conference on Electricity Distribution Madrid, 3-6 June 2019
Paper n° 697
ARE SFRA RESPONSES OF DISTRIBUTION Additionally, it was demonstrated that SFRA variations
TRANSFORMERS DIFFERENT FROM have a similar behavior for distribution and power
LARGE POWER TRANSFORMERS ? transformers. In power transformers responses have
another magnitude considering that capacitance is greater
In order to answer this question, a comparison of IEEE than distribution transformers. That means that the existing
C57.149 [4] with the results measured in the analyzed interpretation criteria and those that are being developed
transformer was made. This guide, in its “failure modes” can be used with some cautions.
section, analyzes the effects of transformer deformations Experience has shown that in distribution transformers it
on the SFRA curves -only end-to-end (EtoE) and end-to- is important consider the effect of magnetization on core
end short-circuit (EtoE Sc) type tests- for each frequency prior to SFRA tests.
range. In order to take full advantage of SFRA benefits, it is
For the five failure modes of this paper, Table 6 presents a imperative to train the testing staff and improve
verification of the diagnosis established in IEEE C57.149. interpretation criteria with the own experience.
Green color indicates that diagnosis of [4] is verified, and
red color means that the diagnosis [4] is not verified.
Table 6 CONCLUSIONS
20 Hz 5 kHz 50 kHz
Frequenc >1 The main conclusions are:
to 10 to 100 to 1
y Range MHz a) SFRA test is a useful tool to quickly assess the
kHz kHz MHz
transformer integrity after failures in low voltage grids
Test because it is capable of detect a wide variety of defects
EtoE Sc
EtoE Sc
EtoE Sc
EtoE Sc
EtoE
EtoE
EtoE
IS SFRA TEST AN ADEQUATE TOOL FOR Although some interpretation criteria were provided in this
THIS APPLICATION? work, the adequate training and experience of test operator
Definitely this test is an adequate tool for the transformer is essential to obtain reliable results.
assessment after incidents in medium/low voltage grids.
As could be seen, SFRA technique is capable of detecting
a wide variety of defects without the need to waste time REFERENCES
and resources in performing many tests. With little [1] TB CIGRE 445 WG A2.34, “Guide for Transformer
experience, it is possible to identify the affected Maintenance”, February 2011.
component and to take the decision of replacing or re- [2] TB CIGRE 342 WG A2.26, “Mechanical-condition
energizing the unit. assessment of transformer windings using frequency
SFRA test has the advantage of being a simple and safe response analysis (FRA)”, April 2008.
test since voltages involved do not exceed a few volts, [3] IEC 60076-18-2012: “Power Transformers -
important feature when doing tests in passable areas. Also, Measurement of Frequency Response”.
it is important to consider that the SFRA test is easy to [4] IEEE C57.149-2012: “IEEE Guide for the
perform in terms of its connections, since stairs, cranes, Application and Interpretation of Frequency
etc. are not needed due to the size of the distribution Response Analysis for Oil-Immersed Transformers”.
transformers.
CIRED2019 5/5