Escolar Documentos
Profissional Documentos
Cultura Documentos
Earthing In a Nutshell (Classification, Isolated Neutral, Methods Of Neutral Grounding) - on photo: Arc Suppression
Coil; credit: swedishneutral.se
The neutral grounding is an important aspect of power system design because the
performance of the system in terms of short circuits, stability, protection, etc., is greatly
affected by the condition of the neutral.
Contents:
1. Objects Of Earthing
2. Classification Of Earthing
1. Equipment Grounding
1/14
1.
1. Ungrounded enclosure
2. Enclosure connected to neutral wire
3. Ground wire connected to enclosure
2. System Grounding
3. Isolated Neutral Or Undergrounded Neutral
1. Circuit Behavior Under Single-Line-to-ground Fault
4. Advantages Of Neutral Grounding
5. Methods Of Neutral Grounding
1. Solid Grounding
2. Resistance Grounding
3. Reactance Grounding
4. Arc Suppression Coil Grounding (Or Resonant Grounding)
1. Objects Of Grounding
1. To save human life from danger or shock or by death by blowing fuse of any
apparatus which becomes leaky.
2. To protect all machines fed from overhead lines from lightning.
3. To protect large buildings from atmospheric lightning.
4. To maintain the line voltage constant (since neutral of every alternator,
transformer is earthed).
Go back to contents ↑
2. Classification Of Earthing
Earthing may be classifed as:
1. Equipment grounding
2. System grounding
We are frequently in touch with electrical equipment of all kinds, ranging from domestic
appliances and hand-held tools to industrial motors.
2/14
Let’s illustrate the need of effective equipment grounding by considering a single-
phase circuit composed of a 230-V source connected to a motor M (see Figure 1).
Note that neutral is solidly grounded at the service entrance.
In the interest of easy understanding, we shall divide the discussion into three
heads:
But if the winding insulation becomes faulty, the resistance Re between the motor
and the enclosure drops to a low voltage (a few hundred ohms or less). A person having
a body resistance R b would complete the current path as shown in Figure 1.
Figure 1 – A person having a body resistance Rb would complete the current path
If Re is small, the leakage current IL through the person’s body could be dangerously
high. As a result the person would get electric shock which may be fatal. Therefore, this
system is unsafe.
Go back to contents ↑
3/14
Figure 2 – Connecting the enclosure to the grounded neutral wire
The trouble with this method is that the neutral wire may become open either
accidentally or due to a faulty installation.
For example, if the switch is inadvertently in series with the neutral rather than the live
wire shown in Figure 3, the motor can still be turned on and off.
However, if someone touched the enclosure when the motor is off, he would receive a
severe electric shock. It is because when the motor is off, the potential of the enclosure
rises to that of the live conductor.
Go back to contents ↑
4/14
Figure 4 – Ground wire, between the enclosure and the system ground
Go back to contents ↑
Go back to contents ↑
5/14
The effect of line capacitances on the grounding characteristic of the system is little and
therefore can be neglected. The circuit then reduces to the one shown in Figure 6a.
First of all consider a three-phase line (perfectly transposed) having some capacitances to
ground. In such a line, the charging currents for each line to earth capacitor lead the
phase voltage by 90° and are equal.
where Vph is the phase voltage and XC is the reactance due to the capacitance of the line
to ground.
Figure 6 – (a) Tree phase system with isolated neutral. (b) Phasor diagram for isolated neutral system.
The capacitive currents ICR, ICY, and ICB are balanced and their resultant is zero and
no current flows to the earth and the potential of neutral is the same as the ground
potential.
Phasor diagram as shown in Figure 6b above.
Go back to contents ↑
The capacitance current becomes unbalanced and fault current IF flows through
the faulty line into the fault and returns to the system via earth and the earth
6/14
capacitances CR and CB. Thus fault current IF has two components I CR and ICB which flows
through capacitances CR and CB, respectively, under the potential differences of V RY and
VBY, respectively.
The currents lead their respective voltages by 90° and their phasor sum is equal to fault
current IF.
Similarly,
Now IF is equal to phasor sum of ICR and ICB. Magnitude of ICR and ICB are equal to
angle between them 60°.
Figure 7 – (a) Isolated neutral system with fault on one phase. (b) Phasor diagram for fault on phase Y.
Therefore,
7/14
When a single line-to-ground fault occurs on an underground neutral system, following
effects are produced in the system:
Effect #2 – The capacitive current in the two healthy phases increase to 3 times the
normal value.
Effect #3 – The capacitive fault current I F becomes three times the normal per-phase
capacitive current.
Effect #4 – The system cannot provide adequate protection against earth faults. It is
because the capacitive fault current is small in magnitude and cannot operate protective
device.
Effect #5 – The capacitive fault current flows IF into earth. Experience shows that IF in
excess of 4 or 5 A is sufficient to maintain an arc in the ionized path of the fault. If this
current is once maintained, it may exist even afer the earth fault is cleared.
This phenomenon of persistent arc is called arcing ground. Due to arcing ground, the
system capacity is charged and discharged in a cyclic order. This sets up high frequency
oscillation on the whole system, and the phase voltage of healthy conductors may
rise to five to six times its normal value.
The over voltages in healthy conductors may damage the insulation in the line.
Due to above disadvantage undergrounded system is not used these days. The modern high-
voltage three-phase system employs grounded neutral owing to a number of advantages.
Go back to contents ↑
1. Voltages of the healthy phases with respect to ground remain at normal value.
2. The high voltages due to arcing grounds are eliminated.
3. The protective relays can be used to provide protection against earth faults.
4. The over voltages due to lightning arc discharged to earth.
8/14
5. It provides greater safety to personnel and equipment.
Go back to contents ↑
1. Solid Grounding
2. Resistance Grounding
3. Reactance Grounding
4. Arc Suppression Coil Grounding (Or Resonant Grounding)
It should be noted that in this system, in addition to capacitive current, the supply source
also supplies the fault current IF.
This current will go to the fault point F through the faulty phase and then return back
9/14
to supply source through the earth and neutral connection.
The fault current IF lags behind the faulty phase voltage by approximately 90° since the
circuit is predominately inductive (due to transformers, machines, and line inductance).
The fault current IF will be in phase opposition to capacitive current I C. Due to this effect
the capacitive current IC will be faulty neutralized by the large fault current.
Figure 9 (a) Solidly grounded system with ground fault on one phase. (b) Phasor diagram for fault on phase B.
In case of solid grounding when there is an earth fault on any phase of the system, the
phase to earth voltage of the faulty phase becomes zero.
However, the phase to earth voltage of the remaining two healthy phases remains at
normal-phase voltage because the potential of the neutral is fixed at earth potential.
This permits to insulate the equipment for phase voltage. Therefore, there is a
saving in the cost of equipment.
When there is an earth fault on any phase of the system, large fault current flows
between the fault point and the grounded neutral. This permits the easy operation of
earth relay.
Limitations
This method also has some limitations:
Limitation #1 – The solid grounding results in heavy earth fault currents. Since
the fault has to be cleared by the circuit breaker, the heavy earth fault currents may
cause the burning of circuit breaker contacts.
Application
10/14
This system of grounding is used for voltages up to 33 kV with total power capacity not
exceeding 5000 kVA.
Go back to contents ↑
The value of R should neither be very low or nor very high. If the value of is very low, the
earth fault current will be large and the system becomes similar to solid grounding
system. On the other hand, if the earthing resistance R is very high, the system condition
becomes similar to undergrounded system.
When there is a ground fault over any phase, neutral is displaced and the maximum
voltage across the healthy phases becomes equal to line-to-line voltage.
Figure 10a shows a ground fault on phase B of a resistance grounded system. The
phasor diagram for such a condition is illustrated in Figure 10b.
Figure 10 – (a) Resistance grounded system with ground fault on one phase. (b) Phasor diagram for fault on phase B.
Capacitive current ICR and ICY leads V BR and V BY, respectively, by 90°. Fault current IF lags
the phase voltage of the faulted phase by an angle ϕ, which depends on the grounding
resistance R and independent of the system up to the fault point.
The fault current IF can be resolved into two components, one in phase with the faulty
phase voltage and the other lagging the faulty phase voltage by 90° (IF sin ϕ). The
lagging component of fault current is in phase opposition to the capacitive current IC.
11/14
By adjusting the value of grounding resistance R to a sufficient low value, it is possible to
neutralize the effect of IC so as to avoid the occurrence of transient oscillations due to
the arcing ground.
In case the grounding resistance R is made sufficiently large so that the lagging component of
fault current becomes less than capacitive current IC, then the system conditions approach
that of the isolated neutral system the risk of high transient voltage occurrence.
Application
Resistance grounding is usually employed for the systems operating on voltage
exceeding 3.3 kV but not exceeding 33 kV.
For circuit below 3.3 kV (i.e., say 400 V distribution networks), the external resistance in
the neutral circuit is unnecessary because the voltage available between phase and
ground is only 230 V.
Go back to contents ↑
The purpose of reactance is to limit the earth fault current. By changing the earthing
resistance, the earth fault current can be changed to obtain the condition similar to that
of solid grounding.
This method is not used these days because of the following disadvantages:
1. In this system the fault current required to operate the protective device is higher
than that of resistance grounding for the same fault conditions.
12/14
2. High transient voltages appear under fault conditions.
Go back to contents ↑
When the value of L of arc suppression coil is such that the fault current I F exactly
balances the capacitive current IC, it is called Resonant grounding.
An arc suppression coil (also called Peterson coil) is an iron-cored coil connected
between the neutral and earth as shown in Figure 12.
The reactor is provided with tapings to change the inductance of the coil. By adjusting
the tapings on the coil, the coil can be tuned with the capacitance of the system, that is,
resonant grounding can be achieved.
Figure 12 – (a) Resonant grounded system with ground fault on one phase. (b) Phasor diagram for fault on phase B.
On occurrence of a ground fault (say on phase B), a lagging reactive current flows from
the faulted phase to the ground and returns to the system through the inductive coil.
Simultaneously capacitive current flows from healthy phase to ground. The lagging fault
current I F and leading capacitive current I C are almost in phase opposition.
By a proper selection of the value of inductance L of the arc suppression coil , the two
current can be made almost equal so that there is no current through the ground fault and so
there will be no arc.
13/14
The combination of neutral reactance L and line capacitance C acts as a parallel
resonant circuit.
Capacitive current:
Go back to contents ↑
Reference // Elements of Power Systems by Pradip Kumar Sadhu and Soumya Das
14/14