Você está na página 1de 2

www.edmi-meters.

com

Mk10E
– Class 0.5S and Class 1

Three Phase CT/WC Smart Meter

Built on the advanced Atlas metering platform, the


Mk10E has a Class 0.5S measurement engine with
many enhancements including smart grid solutions,
high data storage, data processing, UPS configuration
and enhanced communications capabilities.

Key Features

Mk10E Factsheet | MKT-FS-022 Rev 02 Copyright © 2019 EDMI Limited


175mm (W)

Mk10E
- Class 0.5S and Class 1
262mm (H)
95mm (D)

Three Phase CT/WC Smart Meter

Weight: 2kg

Standards and Compliance Battery Load Survey/Profile Security


• Class 0.5S and Class 1 • Internal battery • Over 5000 days storage (2 channels, • Multi-level security (username and
• IEC 62052-11, 62053-21, *62052-31, • Option for external for backup 30-minute intervals) password including encrypted log-in)
62053-22, 62053-23, *62053-24 • Option for UPS battery • Supports Advanced Demand • Up to 7 independent security levels
• AS 62052.11, 62053.21, 62053.22, • Option for additional Supercap Management (ADM) with prioritised • Up to 6 individual users
62053.23 rules • AES128 bit encryption
(72 hours)
• NMI M6 • AMI ready
• Backup time: 10 years without power
(Lithium Battery) • Up to 32 channels and 4 independent
Measurement surveys Communications
• 3 phase 3 wire Real-time Clock • Intervals programmable from 1 to 60 • Up to 3 independently working
• 3 phase 4 wire • Accuracy (internal) within 15 seconds minutes communication ports:
• Option for neutral current per month at 23ºC • Energy, instantaneous readings, pulsing - Optical port: FLAG (IEC 62056-21)
measurement input as channel sources
or ANSI Type 2 (ANSI C12.18)
Data Memory • Ability to store average/minimum/
Voltage - RS-232 with modem power supply
• 2 MB of non-volatile memory maximum values for interval duration
• Nominal voltage: 57.7V – 240V (2G/3G/4G LTE supported)
• Operating range: 52V – 290V Display Time of Use - RS-485 multi-drop (2 or 4-wire
• Withstand: Up to 290V • Large 7 segment alphanumeric • Up to 8 rates plus unified rate RJ45 or 2-wire screw terminal)
• Burden: IEC 62053-61 compliant display with 10.7mm x 6.67mm digit • Up to 32 separate import and export • UDP/IP GPRS/PPP capable
size registers • Compatible with MV-90™
Auxiliary Supply Options • *Large 14 segment alphanumeric • Daily, weekly, monthly, yearly and special • Supports Function Based Setup
• 57.7V - 240V Auxiliary Supply display with 10.5mm x 5.1mm digit days
• Battery UPS size • Up to 200 programmable special days Protocol
• Up to 60 user-defined screens of • Up to 61 previous billing periods plus
Current • EDMI command line
any meter parameter billing totals
• CT range: 1/4A, 1/10A, 5/6A, • DLMS
• Definable enunciators • Block or rolling maximum demand
5/10A, 5/20A • MODBUS
• Display available without main power • Time of maximum demand
• CT limit: 20 x Imax for 0.5 seconds • LED Backlight Option • Energy, pulsing inputs
• WC range: 5/100A, 10/100A
Calendar Software
• Burden: <0.5VA/phase
• EDMI EziView software available for
Measured Values • Supports Daylight Saving time
Frequency meter programming and reading
• 3 elements 4 quadrants • Supports Gregorian or Persian calendars
• 45Hz - 65Hz (Windows® compatible)
• Import/Export/Absolute Wh, varh and
• EDMI MultiDrive software available for
Inputs/Outputs Configuration VAh Tamper Detection and Alarms large scale AMI and AMR solutions
• Up to 4 independently isolated I/O • Fundamental Wh • Provision for sealing with conventional (Windows® compatible)
• Per quadrant Wh, varh and VAh wire or plastic seals
• Options include: Passive/Active • Supported by many popular third-party
inputs, S0/BOSFET/Relay outputs • Phase A,B,C and Total • Bypassing current and reverse current multi-vendor AMR systems
• W, var, VA, Vrms, Irms detection
• Passive input voltage:
• Power factor, frequency, phasor angles • Advanced tamper detection and logging
5V, 12V, 48V, 110V, 240V
• Active input voltage: • Supports ripple control/AFLC • Pre-programmed alarms for meter self- Environmental
check • Specified operating range:
12V (common ground)
Power Quality Indication • Alarms trigger LEDs, enunciators, relay -25˚C to +60˚C
• S0 Output: 27V, 27mA maximum
• Total Harmonic Distortion (THD) outputs or communications event • Operating range limit:
• BOSFET output: 240V, 100mA
• Unbalance (sequence components) • Alarms are stored in event logs -40˚C to +70˚C
maximum
• Option for live waveform display • Option for fixed-threshold magnetic • Storage range limit:
• Relay output: 240V, 2A
• Sag/Swell tamper detection -40˚C to +80˚C
• 2 Programmable LED indicators
- 5 Cycle resolution • *Option for high-sensitivity 3D • Relative humidity:
• Programmable output pulse
- Records time/date/phase/duration/ magnetic tamper detection with Up to 95% non-condensing for 30 days
width: 1ms to 100ms
average and worst excursion configurable threshold • Ingress protection: IP54
- Programmable trigger levels • Source impedance monitoring • Protective Class II
• Surge Test: 5kV
• Impulse Test: 10kV
Specifications with * symbol available in manufacturing codes with prefix 1Ex3

EDMI Limited www.edmi-meters.com


(Headquarters)
47 Yishun Industrial Park A, Singapore 768724
Tel: +65 6756 2938 Fax: +65 6756 0125
Email: marketing@edmi-meters.com
techsupport@edmi-meters.com
Copyright © 2019 EDMI Limited. All Rights Reserved. All trademarks are the property of their respective holders. EDMI’s Policy is one of continuous product development and the right is reserved to modify specifications contained herein without notice.