Escolar Documentos
Profissional Documentos
Cultura Documentos
SAFETY RECOMMENDATIONS
It is strongly recommended that the product be designed, constructed, assembled and installed in accordance
with nationally recognized safety requirements appropriate for products covered by this standard.
AHRI, as a manufacturers' trade association, uses its best efforts to develop standards employing state-of-the-
art and accepted industry practices. However, AHRI does not certify or guarantee safety of any products or
systems designed, tested, rated, installed or operated in accordance with these standards or that any tests
conducted under its standards will be non-hazardous or free from risk.
Note:
Note:
This version of the standard differs from that of 1986 in the following ways:
a. The single number, A-Weighted, sound rating level (SR) in bels has been replaced by
a rating comprised of three sound level descriptors, all expressed in decibels:
b. The frequency range of interest has been expanded to include the 63 Hz Octave Band
c. All sound levels are determined from One-Third Octave Band measurements
d. In addition to a sound rating for the complete unit, the scope of the rating has been
expanded to include sound levels for “fan only” operation as well
e. A new test procedure is specified for determining Sound Power Levels based upon
measurements of sound pressure in an essentially free-field
f. The area of equivalent hemisphere is used to ensure closure between Sound Power
Levels obtained using reverberation room and survey methods.
SECTION PAGE
TABLES
APPENDICES
Table D1. One-Third Octave Band Adjustments for Tone Response ...............................10
Table F1. Example Calculation of Tone Adjusted, A-Weighted Sound Power Level .....12
1.1 Purpose. The purpose of this standard is to 3.2 Hertz (Hz). A unit of frequency equal to one cycle
establish methods for determining the sound ratings of the per second.
outdoor portions of factory-made commercial and
industrial Large Outdoor Refrigerating and Air- 3.3 Large Outdoor Refrigerating and Air-Conditioning
Conditioning Equipment. It establishes definitions; test Equipment. Equipment that consists of one or more
requirements; rating requirements; minimum data assemblies, including an outdoor coil and outdoor fan, and
requirements for Published Ratings; marking and which may include a compressor. Remote, mechanical-
nameplate data; and conformance conditions. draft, air-cooled and evaporative refrigerant condensers are
not included.
1.1.1 Intent. This standard is intended for the
guidance of the industry, including manufacturers, 3.4 Octave Band. A band of sound covering a range of
engineers, installers, contractors and users. frequencies such that the highest is twice the lowest. The
Octave Bands used in this standard are those defined in
1.1.2 Review and Amendment. This standard is ANSI Standard S1.11.
subject to review and amendment as technology
advances. 3.5 One-Third Octave Band. A band of sound covering
a range of frequencies such that the highest frequency is
the cube root of two times the lowest. The One-Third
Section 2. Scope Octave Bands used in this standard are those defined in
ANSI Standard S1.11.
2.1 Scope. This standard applies to the outdoor portions
of factory-made commercial and industrial Large Outdoor 3.6 Published Rating. A statement of the assigned
Refrigerating and Air-Conditioning Equipment, including values of those performance characteristics, under stated
heat pumps, used for refrigerating or air-conditioning of rating conditions, by which a unit may be chosen to fit its
spaces, as defined in Section 3 of this standard. application. These values apply to all units of like nominal
size and type (identification) produced by the same
2.2 Exclusions. This standard does not apply to the manufacturer. As used herein, the term Published Rating
outdoor portions of unitary air-conditioning or heat pump includes the rating of all performance characteristics
equipment which fall within the scope of AHRI Standard shown on the unit or published in specifications,
270 (cooling capacity ratings of less than 135,000 Btu/h advertising or other literature controlled by the
[40 kW]) nor does it apply to air or evaporatively cooled manufacturer, at stated rating conditions.
condensers that fall within the scope of AHRI Standards
460 and 490. 3.6.1 Application Rating. A rating based on tests
performed at Application Rating Conditions (other
than Standard Rating Conditions).
Section 3. Definitions
3.6.2 Standard Rating. A rating based on tests
All terms in this document shall follow the standard performed at Standard Rating Conditions.
industry definitions established in the current edition of
ASHRAE Terminology of Heating, Ventilation, Air- 3.7 Rating Conditions. Any set of operating conditions
Conditioning and Refrigeration, unless otherwise defined under which a single level of performance results, and
in this section. which cause only that level of performance to occur.
3.1 Comparison Method. A method of determining 3.7.1 Standard Rating Conditions. Rating
Sound Power Level of the equipment under test in a Conditions used as the basis of comparison for
reverberation room by comparing the average Sound performance characteristics.
Pressure Level of that equipment to the average Sound
Pressure Level of a Reference Sound Source of known 3.8 Reference Sound Source (RSS). A portable,
Sound Power Level output. The difference in Sound aerodynamic sound source that produces a known stable
Power Level is equal to the difference in Sound Pressure broad band sound power output.
Level when conditions in the room are the same for both
1
ANSI/AHRI STANDARD 370-2001______________________________________________________________
3.9 "Shall" or "Should". "Shall" or "should" shall be c. The volume of the equipment to be
interpreted as follows: tested shall not exceed 5% of the
volume of the room
3.9.1 Shall. Where "shall" or "shall not" is used d. The instrumentation and
for a provision specified, that provision is instrumentation systems employed in
mandatory if compliance with the standard is reverberation room testing shall meet
claimed. or exceed the requirements of ISO
3741.
3.9.2 Should. "Should" is used to indicate
provisions which are not mandatory but which are 4.1.2 Sound tests in a hemi-anechoic room which
desirable as good practice. affords a free field condition above the measurement
space or above a reflecting plane shall be conducted
3.10 Sound Power Level, Lw. This is ten times the in accordance ISO 3745, as adapted for Large
logarithm to the base ten of the ratio of the sound power Outdoor Refrigerating and Air-Conditioning
radiated by the source to a reference sound power, Equipment in Appendix C of this standard.
expressed in decibels, dB. The reference sound power
used in this standard is 1 picowatt (pW). 4.1.3 Sound tests in indoor or outdoor spaces that
qualify as an essentially free field over a reflecting
3.10.1 A-Weighted Sound Power Level, LWA. The plane shall be conducted in accordance with ISO
logarithmic summation of A-Weighted, One-Third 3744, as adapted for Large Outdoor Refrigerating
Octave Band levels and Air-Conditioning Equipment in Appendix C of
this standard.
3.11 Sound Pressure Level, Lp. This is twenty times the
logarithm to the base ten of the ratio of a given sound 4.2 Methods of Test. Sound tests shall be conducted as
pressure to a reference sound pressure of 20 :Pa, expressed prescribed below:
in decibels, dB.
4.2.1 Standard Sound Ratings. Standard sound
3.12 Tone. For the purposes of this standard, a tone is ratings shall be based on sound tests conducted with
considered to exist within a One-Third Octave Band when the unit operating at rated voltage, V, phase and
the sound level in that band exceeds the average of the frequency, Hz, as specified on the unit nameplate
levels of the two adjacent bands by 2 dB or more. and measured at the service connection. The tests
shall consist of two phases:
3.13 Tone Adjustment. An adjustment made to the One-
Third Octave Band data to account for the subjective a. In the first phase, the sound
response to the presence of tones. measurements shall be made with the
equipment operating at the AHRI
standard thermal rating condition
Section 4. Test Requirements b. In the second phase, the compression
equipment shall be turned off and
4.1 Test Requirements. All standard Sound Power Level sound readings taken with only the
ratings shall be determined by tests conducted in a qualified fans operating. During this phase, the
reverberation room, anechoic or hemianechoic room, or an temperature of the ambient air entering
indoor or outdoor space that is an essentially free field over a the unit shall be within ± 2.0 °F [1.1
reflecting plane. °C] of the temperature measured
during compressor operation.
4.1.1 Sound tests conducted in a reverberation room
shall use the Comparison Method in accordance with 4.2.2 Application Sound Ratings. Application
ISO 3741, using a Reference Sound Source calibrated Sound Ratings for conditions other than the AHRI
in a hemi-anechoic environment in accordance with standard thermal rating condition shall be based on
AHRI Standard 250. sound tests conducted with the equipment operating
at those conditions.
a. The room shall be qualified for measuring
sound containing pure tone components in 4.2.3 Test Condition Tolerances. During sound
accordance with ISO 3741, Annex A rating tests, the equipment operating conditions shall
b. Qualification to the 63 Hz Octave Band not deviate from the specified operating conditions
shall be in accordance with AHRI by more than the following tolerances:
Standard 280
Air Temperature ............± 2.0°F [± 1.1°C]
2
ANSI/AHRI STANDARD 370-2001
5.1 Introduction. The sound rating shall include two 400 -4.8
sets of Sound Power Levels, one for the complete unit and 500 -3.2
one for the unit operating with “fans only.” Each set shall 630 -1.9
be comprised of: Octave Band Sound Power Levels (Lw);
an A-Weighted Sound Power Level (LWA); a Tone Adjusted 800 -0.8
A-Weighted Sound Power Level (LWAT); and optionally, 1000 0
One-Third Octave Band Sound Power Levels. 1250 +0.6
where:
LWA = A-Weighted Sound Power Level,
3
ANSI/AHRI STANDARD 370-2001______________________________________________________________
4
ANSI/AHRI STANDARD 370-2001
6.2 Standard Sound Rating. When AHRI standard Section 7. Marking and Nameplate Data
thermal rating conditions have been established for the
equipment, a standard sound rating shall be published for 7.1 Marking and Nameplate Data. As a minimum, the
the unit operating at those conditions, accompanied by the nameplate shall display the manufacturer’s name, model
same data for the unit operating with “fans only.” designation, and electrical characteristics.
All claims to sound ratings within the scope of this Nameplate voltages for 60 Hertz systems shall include one
standard shall include the statement "Rated in accordance or more of the equipment nameplate voltage ratings shown
with AHRI Standard 370". All claims to ratings outside in Table 1 of AHRI Standard 110. Nameplate voltages for
the scope of this standard shall include the statement 50 Hertz systems shall include one or more of the
"Outside the scope of AHRI Standard 370". Wherever utilization voltages shown in Table 1 of IEC Standard
Application Sound Ratings are published or printed, they Publication 60038.
shall include a statement of the standard thermal rating
conditions at which the ratings apply and be accompanied
by the Standard Sound Rating. Section 8. Conformance Conditions
5
ANSI/AHRI STANDARD 370-2001______________________________________________________________
6
ANSI/AHRI STANDARD 370-2001
7
ANSI/AHRI STANDARD 370-2001______________________________________________________________
8
ANSI/AHRI STANDARD 370-2001
Section C5. Calculation of Results adjusted by adding the value of the environmental
correction, K2 to account for departures of the test
C5.1 Correction for Background Noise. Each of the environment from the ideal condition, such that:
measured Sound Pressure Levels (Lp(m)) shall be
compared to the measured background noise (Lp(b)) at the LPf = LP − K 2 C5
same position and frequency such that: where:
9
ANSI/AHRI STANDARD 370-2001______________________________________________________________
10
ANSI/AHRI STANDARD 370-2001
One-Third Projection of One-Third Octave Band above the arithmetic average of the two adjacent bands.
Octave Band
Frequency
2.0 2.5 3.0 3.5 4.0 4.5 5.0 5.5 6.0 6.5 7.0 7.5 8.0
50 † † † † † † † † † † † † †
63 † † † † † † † † † † † † †
80 † † † † † † † † † † † † †
100 † † † † † † † † † † † † †
125 † † † † † † † † † † † † †
160 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.2 0.2 0.2 0.2
200 0.5 0.5 0.6 0.7 0.7 0.8 0.8 0.9 0.9 0.9 1.0 1.0 1.0
250 0.8 1.0 1.1 1.2 1.3 1.4 1.5 1.5 1.6 1.6 1.7 1.7 1.7
315 1.2 1.4 1.6 1.7 1.8 1.9 2.0 2.1 2.2 2.2 2.3 2.3 2.4
400 1.5 1.8 2.0 2.1 2.3 2.4 2.5 2.6 2.7 2.8 2.8 2.9 3.0
500 1.8 2.1 2.3 2.5 2.7 2.8 2.9 3.0 3.1 3.2 3.3 3.3 3.4
630 2.1 2.4 2.6 2.8 3.0 3.2 3.3 3.4 3.5 3.6 3.7 3.7 3.8
800 2.3 2.6 2.9 3.1 3.3 3.5 3.6 3.7 3.8 3.9 4.0 4.1 4.1
1000 2.5 2.8 3.1 3.4 3.6 3.7 3.9 4.0 4.1 4.2 4.3 4.4 4.4
1250 2.7 3.0 3.3 3.6 3.8 4.0 4.1 4.3 4.4 4.5 4.6 4.6 4.7
1600 2.9 3.2 3.6 3.8 4.0 4.2 4.4 4.5 4.6 4.7 4.8 4.9 5.0
2000 3.0 3.4 3.7 4.0 4.2 4.4 4.6 4.7 4.8 4.9 5.0 5.1 5.2
2500 3.1 3.5 3.9 4.1 4.4 4.5 4.7 4.9 5.0 5.1 5.2 5.3 5.3
3150 3.2 3.6 4.0 4.2 4.5 4.7 4.8 5.0 5.1 5.2 5.3 5.4 5.4
4000 3.3 3.7 4.0 4.3 4.5 4.7 4.9 5.0 5.2 5.3 5.4 5.4 5.5
5000 3.3 3.7 4.0 4.3 4.5 4.7 4.9 5.0 5.1 5.3 5.4 5.4 5.5
6300 3.2 3.6 4.0 4.2 4.5 4.7 4.8 5.0 5.1 5.2 5.3 5.4 5.5
8000 3.2 3.6 3.9 4.2 4.4 4.6 4.8 4.9 5.0 5.1 5.2 5.3 5.4
10000 † † † † † † † † † † † † †
† Tone Adjustments are not applicable to frequencies below 160 Hz or above 8000 Hz.
11
ANSI/AHRI STANDARD 370-2001______________________________________________________________
Table F1. Example Calculation of Tone Adjusted, A-Weighted Sound Power Level
One-Third Tone Adjusted,
Equipment
Octave Band Tone A-Weighting A-Weighted 0.10 ⋅ LWAT ( n )
Sound 10
Center Adjustment Adjustment Sound Power
Power Level
Frequency (from Equation 3) (from Table 1) Level
(dB re 1 pW)
(Hz) (dB re 1 pW)
13