Escolar Documentos
Profissional Documentos
Cultura Documentos
600/1000 V copper Conductor PVC Insulated with Steel Wire Armour Cable
Cable Conductor Size Number of Cores
Area mm2 Neutral 1 2 3 3½ 4 5 7 10 12 19 27 37 48
1.5 20s 20s 20s 20s 20s 20 20 25 25 32 32
2.5 20s 20s 20s 20s 20 25 25 25 32 32 40
4 20s 20s 20 20 25 25 25 32 40 40 50
6 20s 20 20
10 25 25 25
16 25 25 25
25 16 25 25 32 32
35 16 25 32 32 32
50 25 25 32 32 32 40
70 35 25 32 40 40 40
95 50 25 40 40 50 50
120 70 25 40 50 50 50
150 70 32 40 50 50 50
185 95 32 50 50 63 63
240 120 40 50 63 63 63
300 150 40 63 63 75 75
300 185 75
400 185 50 63 75 75 75
500 50
630 50
800 63
1000 63
Glands manufactured as per BS 6121 PT 1 : 1989 for use with PVC SWA PVC 600/1000 V cables to BS
6346 : 1989
NOTE : This selection chart is given for guidance only Actual cable dimensions must be considered
before making final selections as these may vary due to manufacturing tolerances provided in BS 6346 :
1989
CABLE TYPE
UNARMOURED SINGLE WIRE ARMOUR
INNER & OUTER
CONDITION SEAL NO SEAL OUTER SEAL
SEAL
Clear & Dry A2 BW CW E1W
External Moisture A2 CW E1W
Internal Moisture A2 E1W
Dust & Oil A2 CW E1W
BW General purpose indoor application.
A2, CW, E1W indoor and outdoor application.
ENTRY THREAD :
Normally glands have metric entry thread forms.
Metric threads 1.5 mm pitch are standard upto 75 mm.
Other thread forms like IMPERIAL, PG, NPT are also available on request.
(PEARL Standard / NETA MTS-1997 Table 10.1)
Windings are never left floating for insulation resistance measurements. Solidly grounded winding must have the ground removed in order to
measure the insulation resistance of the winding grounded. If the ground cannot be removed, as in the case of some windings with solidly
grounded neutrals, the insulation resistance of the winding cannot be measured. Treat it as part of the grounded section of the circuit.
We need to test winding to winding and winding to ground ( E ).For three phase transformers, We need to test winding ( L1,L2,L3 ) with substitute
Earthing for Delta transformer or winding ( L1,L2,L3 ) with earthing ( E ) and neutral ( N ) for wye transformers.
Transformer Formula
1 Phase Transformer IR Value (MΩ) = C X E / (√KVA)
Where C= 1.5 for Oil filled T/C with Oil Tank, 30 for Oil filled T/C without Oil Tank or Dry Type T/C.
O O
C F Correction Factor
0 32 0.25
5 41 0.36
10 50 0.50
15 59 0.720
20 68 1.00
30 86 1.98
40 104 3.95
50 122 7.85
IR Value of Transformers:
IR Value in MΩ
IR (Min) = kV+1 For most windings made before about 1970, all field windings, and
others not described below
IR (Min) = 100 MΩ For most dc armature and ac windings built after about 1970 (form
wound coils)
IR (Min) = 5 MΩ For most machines with random -wound stator coils and form-wound
coils rated below 1kV
250V 500V DC 25 MΩ
New Motor 20 MΩ
11kV and 33kV Cables between Cores and Earth (As per ETSA Standard)
EHVLines. 5 KV 10MΩ
IR Value at IR Value at
Equipment Meggering Commissioning Maintenance
Time (MΩ) Time(MΩ)
HV Bus 200 MΩ 100 MΩ
Switchgear LV Bus 20 MΩ 10 MΩ
LV wiring 5 MΩ 0.5 MΩ
HV 100 MΩ 25 MΩ
Transformer Dry Type
LV 10 MΩ 2 MΩ
Main Circuit 2 MΩ / KV
Circuit Breaker
Control Circuit 5MΩ
LT Circuit-Earth 50MΩ
Relay
LT-D.C Circuit 40MΩ
LT-LT 70MΩ
3 Phase Wiring:
In the case of a very large installation where there are many earth paths in parallel, the reading would be expected to be lower. If this happens, the
installation should be subdivided and retested, when each part must meet the minimum requirement.
The IR tests must be carried out between Phase-Phase-Neutral-Earth with a minimum acceptable value for each test of 0.5 M Ohms.
Min IR Value = 50 MΩ / No of Electrical outlet. (All Electrical Points with fitting & Plugs).
Min IR Value = 100 MΩ / No of Electrical outlet. (All Electrical Points without fitting & Plugs).
Required Precautions:
Electronic equipment like electronic fluorescent starter switches, touch switches, dimmer switches, power controllers, delay timers could be
damaged by the application of the high test voltage should be disconnected.
Capacitors and indicator or pilot lamps must be disconnected or an inaccurate test reading will result.
Where any equipment is disconnected for testing purposes, it must be subjected to its own insulation test, using a voltage which is not likely to
result in damage. The result must conform with that specified in the British Standard concerned, or be at least 0.5 M Ohms if there is no Standard.