Escolar Documentos
Profissional Documentos
Cultura Documentos
Flow?
Over the years use of the term “minimum flow” has evolved. Decades ago
industrial centrifugal pump manufacturers quoted a single, relatively low value
for minimum flow intended to prevent users from running their pumps to
destruction. The term “minimum flow” generally meant the lowest continuous
flow the pump was permitted to operate, without reference to duration,
vibration level or other criteria. Today we have minimum flow values for
continuous operation, for intermittent operation and for permissible
temperature rise.
The quoted minimum flow for continuous operation is usually called “Minimum
Continuous Stable Flow” or its more common abbreviation “MCSF.” It is the
flow below which the pump should not be operated continuously. The usual
purpose of MCSF is to achieve satisfactory bearing and seal life; however
MCSF may be based on other considerations. Any of the following factors
may be considered in establishing the MCSF:
manufacturer’s experience
rule of thumb
radial thrust
temperature rise
maximum permissible power rise (high specific speed and axial flow
pumps)
Vibration limits for Allowable Operating Range and Preferred Operating Range
MCSF is a value that can range from roughly 10% to 80% of Best Efficiency
Point flow depending on pump size and type, operating speed, impeller
suction geometry, liquid density, and other factors. A size 2” (50mm)
discharge single-stage process pump may have an MCSF as low as 10% of
BEP flow. MCSF is often in the range of 30% to 60% of BEP flow for process
pumps with discharge sizes 3” (75 mm) and larger. Large mixed flow vertical
pumps and very high head-per-stage centrifugal pumps may have an MCSF
greater than 60% of BEP flow. Axial flow pumps have a power curve that
rises toward shutoff and minimum flow may be limited by the power rating of
its driver.
The purpose of minimum flow is generally to prevent undue wear and tear or
damage to the pump. In the real environment of a process or utility plant, a
pump is operated at just about any condition demanded by the situation at
hand. Thus there are different pump minimum flows for different purposes.
My friend, In this posting we will discuss about the pump recycle systems. The pump shall be
protected from minimum flow, due to the following reasons;
1. Thermal consideration which has effect to the pump efficiency (The efficiency will decrease
significantly at low flow)
4. liquid containing a large amount of abrasive particles must flow continuously through the
pump. at low flow, the particles can circulate inside the pump and erode the impeller.
The three types of pump recycle systems which are generally applied are ;
1. ORIFICE
This system will provide continuous recycle flow whenever pump is running, regardless
of the process demand.
Typically applied for pump below 50 hp (38kW), or small capacity.
Don’t forget, you must consider the additional capacity of the pump (the capacity is
included recycle flow)
For initial estimation, 30% of rated flow can be used as recycle flow basis.
Take care for high pressure drop condition, is there any flashing? Two phase? Or
vibration? If two phases is occurred, the orifice should be located at the end of the recycle line.
2. CONTROL VALVE
When the minimum flow is reached, the valve start to open. The flowmeter shall be
located at pump discharge side (installing at suction side will decrease the suction pressure,
decrease NPSHa )
The flow meter should be located before(upstream the) recycle line connection.
Be careful with high pressure drop, control valve may be noise and vibration (an orifice
in series with the control valve may be required)p
3. AUTOMATIC RECIRCULATION
This type is the spring loaded, combined recycle and check valve
The spring loaded is set at a pressure correspond to minimum flow (based on pump
curve) where the recycle starts to open.
Check this link for the detail how the ARC valve work.
No need additional check valve in the discharge system. The ARC provides back flow
protection.
Take care with pump with high discharge pressure ( while low pressure source) . The orifice may
be required at the recycle line to avoid very big change of momentum
General Guide.
Recycle line should be routed back to the source (tank or vessel) NOT to pump suction. Bubble of two
phases can be formed during pressure reduction by orifice or control valve. It may be introduced into the
pump.
Routing to suction line may causes excessive temperature build up in a very short time.
For 2 x 100% operation, the recycle line can be connected at combined line.
For 2 x 50 % operation, each pump shall have its own recycle system.
Generally, the recycle system is not shown in the PFD. There are two specific pumps when a recycle system
should be included in the PFD. These are the BFW pump and pump with the high head or capacity. (discharge
pressure > 1000 psig)
Let say, 100 gpm liquid shall be transferred via pump to a tank. The recycle is continuous of 30 gpm use orifice.