Applicator Sizing - Flow

Project :
Customer: Carrier C.Project No.:
Contact person: Phone: Fax:
eMail:

TAG : TBA
Timestamp: --- Review number: ---
Sales order number:

Sizing Sheet
General Parameters
Fluid Water, process
State Liquid
Character Clean Atmospheric Pressure 1.013 bar_a
Abrasivity Not abrasive Standard EN/DIN/ISO
Fluid Group (PED) Normal Fluid (Fluid group 2)

Operating Conditions
minimum nominal maximum
Requested Flow 100 400 580 m3/h
Pressure 3 bar_g
Temperature 30 °C
Density 995.79 kg/m3
Viscosity 0.79732 cP
Sound Velocity 1 511 m/s
Pressure (min/max) 3 3 bar_g
Temp. (min/max) 30 30 °C
Vapor Pressure 0.0425 0.0425 0.0425 bar_a

Flowmeter : Promag 10L


Flow Principle Electromagnetic (Promag)
Meter Size DN 300
Minimum Flow 0   m3/h
Maximum Flow 2 699.66   m3/h
Material (sensor) * Polyurethan-Liner (-20...+50°C)
Process connection* PN 10 EN 1092-1 / 1.4306 lap joint flange
PED category** ** : Flowmeter excluded

  Extended order code


Qty Item Description Extended order code
1 Flowmeter Promag 10L 10L3H-UJ

*The user is responsible for the selection of process-wetted materials in view of their corrosion resistance. Endress+Hauser makes no guarantees and
assumes no liability for the corrosion resistance of the materials selected here for the application described above.
** The PED category is an Endress+Hauser recommendation and depends on the fluid category, process data as well from the max. permissible
pressure of the selected pressure rating.The fluids of the Applicator data base are classified to 67/548/EWG.

Print date: 08.03.2013 01:10 PM -1/3-


Applicator®: 10.14.00 / 121
 

Under no circumstances is Endress+Hauser liable for errors, neither in the Software and in its documentation, nor for any errors
and consequential damage which may arise out of their use. The results in Applicator apply to parameters entered by the user. A
change in these parameters could lead to different results. Mandatory data are in the according technical information (TI).
Applicator Sizing - Flow
Project :
Customer: Carrier C.Project No.:
Contact person: Phone: Fax:
eMail:

TAG : TBA
Timestamp: --- Review number: ---
Sales order number:

Sizing Sheet
Sizing and Calculated Results
minimum nominal maximum
Requested Flow 100 400 580 m3/h
Velocity (meas. tube) 0.37 1.482 2.148 m/s
Measured error Vol.*** 1.04 0.63 0.59 %
Reynolds No. 571 798
***For error calculation, the specified reference conditions for the calibration of the flowmeter according to ISO/IEC 17025 apply. Further information in
technical documentation.

Warnings / Messages

Print date: 08.03.2013 01:10 PM -2/3-


Applicator®: 10.14.00 / 121
 

Under no circumstances is Endress+Hauser liable for errors, neither in the Software and in its documentation, nor for any errors
and consequential damage which may arise out of their use. The results in Applicator apply to parameters entered by the user. A
change in these parameters could lead to different results. Mandatory data are in the according technical information (TI).
Applicator Sizing - Flow
Project :
Customer: Carrier C.Project No.:
Contact person: Phone: Fax:
eMail:

TAG : TBA
Timestamp: --- Review number: ---
Sales order number:

Tri-Size Sheet
General Parameters
Fluid Water, process
State Liquid
Character Clean Atmospheric Pressure 1.013 bar_a
Abrasivity Not abrasive Standard EN/DIN/ISO
Fluid Group (PED) Normal Fluid (Fluid group 2)

Sizing and Calculated Results


Next Smaller Size Current Size Next Bigger Size
Flow meter Promag 10L Promag 10L Promag 10L
Flow Principle Electromagnetic (Promag) Electromagnetic (Promag) Electromagnetic (Promag)
Meter Size DN 250 DN 300 DN 350
Process connection* PN 10 EN 1092-1 / 1.4306 PN 10 EN 1092-1 / 1.4306 PN 6 EN 1092-1 (DIN2501)
Minimum Flow 0 0 0 m3/h
Maximum Flow 1 882.05 2 699.66 3 345.87 m3/h
Velocity (meas. tube) at req. Flow min. 0.531 0.37 0.299 m/s
Velocity (meas. tube) at req. Flow nom. 2.125 1.482 1.196 m/s
Velocity (meas. tube) at req. Flow max. 3.082 2.148 1.733 m/s
Meas. error Vol. at req. Flow min.*** 0.88 1.04 1.17 %
Meas. error Vol. at req. Flow nom.*** 0.59 0.63 0.67 %
Meas. error Vol. at req. Flow max.*** 0.56 0.59 0.62 %
Reynolds No. 684 828 571 798 513 621
*The user is responsible for the selection of process-wetted materials in view of their corrosion resistance. Endress+Hauser makes no guarantees and
assumes no liability for the corrosion resistance of the materials selected here for the application described above.
***For error calculation, the specified reference conditions for the calibration of the flowmeter according to ISO/IEC 17025 apply. Further information in
technical documentation.

Print date: 08.03.2013 01:10 PM -3/3-


Applicator®: 10.14.00 / 121
 

Under no circumstances is Endress+Hauser liable for errors, neither in the Software and in its documentation, nor for any errors
and consequential damage which may arise out of their use. The results in Applicator apply to parameters entered by the user. A
change in these parameters could lead to different results. Mandatory data are in the according technical information (TI).

Você também pode gostar