UL, ULC, CSFM Listed; FM Approved; 4090-9120 Six Point Module with
MEA (NYC) Acceptance* Four T-Sense Inputs and Two Relay Outputs
Features
DISCONNECT POWER
Six point operation provides four supervised BEFORE SERVICING
24V
+2
24VC
+3
NC COM NO
OUTPUT 1
-4
or higher)
IDNet+
Typical applications include fan motor control centers,
NC COM NO
OUTPUT 2
IDNet-
monitoring fire pump motor running status, low ON
1 2 3 4 5 6 7 8
S4090-0009-6 11/2014
Product Selection
Model Description
4090-9120 Six Point Module
4090-9801 For semi-flush mounted box Optional trim plate with LED viewing window, includes mounting screws;
4090-9802 For surface mounted box galvanized steel
Wiring Reference
Maximum distance to contacts is 500 ft
(152 m) (inputs are for indoor wiring only)
To next device
2 S4090-0009-6 11/2014
Mounting Information
4-9/16" 4-5/16"
(116 mm) (109 mm)
3 S4090-0009-6 11/2014
Specifications
Electrical
Communications IDNet communications, one address
Voltage 18 to 32 VDC (nominal 24 VDC)
Input Power
Current 30 mA maximum @ 24 VDC from listed fire alarm power supply
Point Type MLPTIO
Point Allocation I/O Point Usage per Panel 6; 1 per relay, 1 per input
Reference
up to 7; 1 per relay, 1 per input, 1 for trouble; for points mapped to the Fire Alarm
Public Points Usage
Network
Normally open dry contacts
Input Requirements Up to 500 ft (152 m) total distance from Six Point Module
For indoor wiring applications only
Two required per T-sense input, refer to page 2 and to Installation Instructions
Input Supervision Resistors
574-876 for additional information and wiring detail
Screw terminals for input and output wiring, 18 to 14 AWG wire
Wire Connections
(0.82 mm2 to 2.08 mm2)
2 A @ 30 VDC, resistive
Relay Contact Ratings* Power-Limited from listed fire alarm supply
Form C (SPDT) 1 A @ 30 VDC, inductive
(not rated for 0.5 A @ 120 VAC, resistive
incandescent switching) Nonpower-Limited
0.25 A @ 120 VAC, inductive
* Provide circuit fusing and transient suppression as required per application. DC inductive loads can typically be diode suppressed;
120 VAC loads may require RC networks or varistors, depending on device type. Refer to Installation Instructions 574-876 for
additional information.
Up to 2500 ft (762 m) from the fire alarm control panel
IDNet Wiring Distance Reference Up to 10,000 ft (3048 m) total Class B wiring distance including T-Taps
Compatible with 2081-9044 Overvoltage Protectors
Mechanical
Dimensions 4-1/8” H x 4-1/8” W x 1-3/8” D (105 mm x 105 mm x 35 mm)
Mounting Bracket Galvanized sheet metal
Temperature 32° to 120° F (0° to 49° C) indoor operation only
Humidity Range 10 to 90% RH at 90° F (32° C)
Installation Instructions 574-876