PROJECT : CONSTRUCTION OF MULTIMODAL INLAND WATER TERMINAL AT HALDIA,WEST BENGAL ON RIVER GANGA, NW – 1,

A/C ITD CEMENTATION LTD.

SUBJECT : LIST OF ADDITIONAL INPUTS / CLARIFICATIONS NEEDED IN ENQUIRY FOR SUPPLY OF ELECTRICAL EQUIPMENT
INCLUDING ELECTRICAL SYSTEM DESIGN

Sr. No. Item/Page No Clarification Required Client/Consultant Clarification

1 3.02.01 / E0: 6 Plant Layout in Autocad format may please be


issued for estimation of quantities for Cable,
Earthing, Cable trays etc.

2 3.02.01 / E0: 6 Drawing of Sub Station building & Terminal


Building elevation and sizes, may please be issued
for estimation of Lighting quantities

3 3.02.01 / E0: 6 Distance of DP / Metering Cubicle may please be


given

4 5.10.0 / E0: 16 Soil Resistivity value may please be forwarded


for Earthing design.

5 5.11.3 / E0: 17 40 mm dia 3 m long Galvanized Steel pipe of 6mm


thickness is specified for Earth Electrode. As per
5.02.2 / E12: 13
IS 1239 part 1, thickness for Medium (B class) pipe
for 40 dia is 3.25 mm & for Heavy (C class) it is
4.05 mm. Generally for Earth Electrodes, B
class pipe is used which may please be accepted.
6 10.0 / E0: 23 As per details given in Exclusions cables, Eathing,
Lighting & Lightning protection, internal
electrification of buildings specified is not part of
the scope. Only incoming power supply to other
agencies with earthing connection shall be
considered. Please confirm.

7 3.07.01 / E2:2 & Maximum Bus bar current density for Aluminium
is specified. The same may please be changed to
3.03.00 / E3:2
the current density as per OEM type tested
design of panel having identical current rating.

8 3.07.02 / E2:3 Insulating sleeves for bus bars and cast resin
shrouds for joints shall be provided. The same may
please be changed as per OEM type tested design
of panel having identical rating.

9 3.14.02 & 03/ E2:7 For Incoming feeders Voltage & Current
& Transducers & for outgoing feeders Current
Transducers in addition to Multi Function meter
5.15.02 / E3:11
with RS comm. Port. With serial interphase
connection all the required data can be
communicated for monitoring & control, hence
this duplication may please be avoided.

10 3.05.00 / E3:2 & 220V control supply shall be derived from 415/220V
control supply transformer located in respective
5.09.02 / E3:9
module. The arrangement of common control
transformer with changeover & redundancy may
please be accepted.
11 4.01.00 / E3:3 Thickness of gland plates shall not be less than 4.0
mm for sheet steel & 4.0mm for nonmagnetic
material. Thickness of sheet steel may please be
changed to 3mm instead of 4 mm.

12 5.02.01 / E3:6 MCCBs shall be provided with thermo-magnetic type


release for over current and short circuit protection.
These shall be microprocessor based with RS 485
communication facility. Both the requirements
cannot be met. The same may please be clarified.

13 3.03.01 / E4:3 Maximum current density shall not exceed 2.5A per
sq.mm. has been specified. The same may please
be changed as per type tested design for
acceptable temp rise.

13 3.03.01 / E4:3 The flux density in core shall not exceed 1.6 Tesla
under over voltage conditions and to this effect
calculations shall be submitted.
Whereas in clause No. 5.03.06/E0:11 The
maximum flux density in any part of core and yoke
shall not exceed 1.9 Tesla is mentioned.
The same may please be clarified.

14 4.03.04 / E6:3 Following accessories shall be provided with


batteries.
Syringe type Hydrometer 2 Nos. per Battery
Thermometer with specific gravity correction scale 2
Nos. per Battery
Acid resistant funnel 2 Nos. per Battery Acid
resistant jug. 2 Nos. per Battery
Rubber apron and gloves 2 sets per Battery
For sealed Maintenance Free batteries these
components are not used & hence may please be
deleted.

15 4.01.04 / E7:2 & Capacitor bank shall be double layer construction


(film + paper + foil) gas impregnated type.
4.01.04 / E8:2
Mix dielectric capacitors have been replaced by
Capacitor with All PP film. Hence the same may
please be accepted.

16 4.02.04 / E2:11 The resistance between any point on each earthing


system and the earth electrode shall not exceed 0.1
ohm. The same may please be interpreted as the
overall resistance between the earthing installation
at any point & Earth Electrode shall be less than 1
ohm as per IS 3043