2 Actuators
1B95080 - 08/2019-2

Installation and Operation Instruction


The actuator types FlowCon FN.0.2, FN.0.4
and FN.1.2 are electrical actuators. FN.0.2 is
24V modulating and FN.0.4 is 24V 3-point float-
ing and 2-position. FN.1.2 is 24V modulating and
2-position failsafe version.

 
Fitting and Re-fitting

Figure 2

Do not connect power to the actuator unless Orientation


the actuator is already fitted on the valve Upside-down installation is allowed (reduced IP
and NEVER install the actuator in closed rating applies) along with the standard horizontal
position - this may damage the valve. Actu- and vertical installation.
ator is supplied in open position to ensure
easy commissioning of the system. 360º

Mount the actuator on the valve and finger


tighten the connection union. Do not use addi-
tional tools. In case the actuator will have to be
removed, it is recommended to electrically open
the actuator by activating DIP switch #6 for eas-
ier removal. Hereafter finger loosen the connec-
tion union. Again, no need for additional tools.
Please make sure that the actuator is electrically
opened, before re-fitting it on the valve.

Figure 3

Figure 1

This paper is a supplement to the FlowCon General Instruction Page 1 of 4


Latest release of any FlowCon material is available on www.flowcon.com
FlowCon FN.0.2, FN.0.4 and FN.1.2 Actuators
1B95080 - 08/2019-2

Wiring Start-up Sequence


When power to the actuator is turned on, the
FlowCon FN (analog)
actuator will automatically calibrate to determine
FN.0.2 / FN.1.2 Actuator closing point. Hereafter it will proceed to normal
0(2)-10V modulating
Yellow
operation mode (according to control signal).
Brown

Green
Grey
Blue

For the failsafe version (FN.1.2), capacitor


Input signal
0(2)-10V DC
Feedback signal
0(2)-10V DC charging will be prioritized (max. 120 sec de-
<0.5mA pending on capacitor energy level) during start-
Power 24V AC/DC up and re-powering. After completion of charging
Ground/common mode followed by calibration mode, the actuator
Feedback ground
0V DC
will proceed to normal operation mode.

FlowCon FN (digital) Auto Cycle Sequence


FN.0.4 Actuator
Auto Cycle can be activated during commission-
2-Position, Normally Closed ing. It prevents the valve from jamming when the
valve is not moved for a longer period of inactiv-
ity. By moving DIP switch #1 from OFF to ON,
Brown

Grey
Blue

Auto Cycle is activated. Actuator will then per-


Close Open form 50% stroke cycle every 3 weeks if no stroke
movement has occurred.
Power 24V AC/DC

Ground/common Electrical Override


By moving DIP switch #6 from OFF to ON, elec-
trical override is activated and the actuator will
FN.0.4 Actuator
3-Point Floating, Normally Closed
open valve fully. During electrical override the
LED indicator will blink red and green. When DIP
switch #6 is moved back to OFF, the actuator will
Brown

Grey
Blue

re-calibrate and thereafter go into normal opera-


Stop
Close Open tion mode. Electrical override is performed with
power supply on.
Power 24V AC/DC

Ground/common Failsafe Mode (FlowCon FN.1.2)


When power is lost, the actuator will go into fail-
safe mode after a few seconds, mandatory that
FN.1.2 Actuator capacitor charging and start-up sequence are
2-Position, Normally Closed
completed. The actuator will perform failsafe
action (open or close) and stay in failsafe final
Yellow
Brown

Green

position until return of power. Upon power, the


Grey
Blue

Feedback signal
0-10V DC
actuator remains in the final failsafe position until
Close Open
charging mode is reached (max. 60 sec). Here-
Power 24V AC/DC after the actuator will return to normal operation
Ground/common
mode.
Feedback ground
0V DC

This paper is a supplement to the FlowCon General Instruction Page 2 of 4


Latest release of any FlowCon material is available on www.flowcon.com
FlowCon FN.0.2, FN.0.4 and FN.1.2 Actuators
1B95080 - 08/2019-2

DIP Switch Settings


The valve functions are set on DIP switches found under the connection cover. PCB mounted electri-
cal components will not be directly exposed when DIP switches are to be set. Factory setting for all
switches is OFF.

FlowCon FN.0.2 Actuator


DIP Function ON Function OFF
switch
#6 Electrical override ON Electrical override OFF
6
 
#5 No function 5 No function
%
 % % 4
 %
#4 Equal percentage Linear

#3 %
% Normally Open %
% % 3
% %
% Normally Closed
2
#2 Control signal 2-10V Control signal 0-10V
1
#1 Auto cycle ON Auto cycle OFF

FlowCon FN.0.4 Actuator


DIP Function ON Function OFF
switch
#6 Electrical override ON Electrical override OFF
6
 
#5 No function 5 No function
%  % % 4  %
#4 No function No function

#3 % Normally Open % % 3 % Normally Closed


2
#2 No function No function
1
#1 No function No function

FlowCon FN.1.2 Actuator


DIP Function ON Function OFF
switch
#6 Electrical override ON Electrical override OFF
6
 
#5 Failsafe open 5 Failsafe close
%  % % 4  %
#4 Equal percentage Linear
% % % %
#3 % Normally Open %
% % % 3 % Normally Closed
2
#2 Control signal 2-10V Control signal 0-10V
1
#1 Auto cycle ON Auto cycle OFF

This paper is a supplement to the FlowCon General Instruction Page 3 of 4


Latest release of any FlowCon material is available on www.flowcon.com
FlowCon FN.0.2, FN.0.4 and FN.1.2 Actuators
1B95080 - 08/2019-2

LED Status
The LED indicator is visible through the dark colored transparent connection cover. The LED indica-
tion will give the following statuses.
FN.0.2 FN.0.4 FN.1.2

Normal operation mode Full on green Full on green Full on green

Charging mode (60 sec) n/a n/a Blinking red

Calibration mode Blinking green Blinking green Blinking green


(closing point adjustment)

Electrical override mode Blinking red/green Blinking red/green Blinking red/green

Failsafe mode n/a n/a OFF

FlowCon International assumes no responsibility for mistakes, if any, in any printed material.

This paper is a supplement to the FlowCon General Instruction Page 4 of 4


Latest release of any FlowCon material is available on www.flowcon.com
FlowCon General Instruction
1B95011 - 01/2019

FlowCon General Instruction


GENERAL:

Flushing:
Water must always be suitable treated, clean recommends 4-6 rounds of tape applied tightly
and free of debris (according to VDI 2035 re- in clockwise rotation. WHEN USING HEMP AS
commendation). PIPE SEALANT, ENSURE NO STRANDS ARE
In case of an insert-based valve, system is re- LEFT IN THE VALVE OR PIPING.
commended to be flushed before the insert is in-
stalled in the valve body. A suitable flushing cap For threaded connections including sealing O-
is available. In case of a one-unit-valve, system ring or sealing gasket additional sealing is not
is recommended to be flushed before the valve required. Please make sure the O-ring / gasket
is installed. If not possible, flush the system at is properly placed. After finger tightening O-ring
maximum flow setting equal to fully open valve. sealing requires 2-5 Nm torque.
Ensure that the valve is not in the fully closed
position when filling the system with water. EuroCone fittings will seal with FlowCon UniQ®
It is recommended that a strainer be installed and FlowCon Mini By-Pass without additional
prior to the valve body to prevent damage or sealing.
blockage due to debris.
O-rings:
Installation: Any O-ring (on valve, insert or accessory) is
INSTALL THE VALVE HOUSING WITH THE re-commended to be greased with silicone oil
FLOW DIRECTIONAL ARROW POINTING IN before installation. IMPORTANT: Never use mine-
THE CORRECT DIRECTION. Valves must be ral oil or petrol-based grease or oil on the O-
installed avoiding unnecessary pull or twist in rings.
the valve housing.
Pressure:
Thread Sealing: It is recommended to make some type of over-
For threaded connections please clear threads pressure limitation to avoid the inlet pressure
on both valve and piping of debris. FlowCon re- never exceeds the maximum operating pres-
commends thread sealant (Permabond A1044 sure. The valves shall be inspected for damage
or equivalent). When using Teflon tape, FlowCon after any overpressure condition.

WARRANTY:

Following recommendations will prolong valve Warranty is voided using other actuators than
life and give better functionality. supplied or recommended by FlowCon Interna-
tional.
Failure to abide by all recommendations as per
this General Instruction will void warranty. For any supplementary warranty obligations, plea-
se see the relevant product specific installation
and operation instruction.

Latest release of any FlowCon material is available on www.flowcon.com Page 1 of 4


FlowCon General Instruction
1B95011 - 01/2019

FLOWCON VALVE HOUSINGS: FlowCon K


The valve is available with fixed female-by-fe-
Install the selected valve housing as called for in male threaded connections for all model sizes.
the design drawings. P/t plugs with collar.

FlowCon A FlowCon Partner Ball


The housing is available with fixed female-by- The valve is available with fixed female-by-fe-
female threaded connections for all model sizes. male threaded connections for all model sizes.
The A model is only available for 20 mm (3/4”) P/t plugs without collar.
insert and model numbers are A15.X, A20.X and
A25.I.K. FlowCon Partner Globe
The valve is available for double flanged connec-
FlowCon AB tions for all model sizes. P/t plugs without collar.
The housing is similarly available with fixed
female-by-female threaded connections for all FlowCon PIM-DP
model sizes. The AB model is available for 20 The valve is available for double flanged connec-
mm (3/4”) insert (model numbers are AB15.X, tions for all model sizes. P/t plugs without collar.
AB20.X and AB25.I.K), 40 mm (1 1/2”) insert
(model numbers are AB25.X and AB32.X) and FlowCon QuickDisc®
50 mm (2”) insert (model numbers are AB40.X The valve is available with fixed female-by-fe-
and AB50.X). P/t plugs with collar. male threaded connections for all model sizes.
P/t plugs without collar.
FlowCon ABV
The housing is available with double union end FlowCon SM
connections for all model sizes. The ABV model The valve is available with double union end
is available for 20 mm (3/4”) insert (model num- connections or double flange connections de-
ber ABV1) and 40 mm (1 1/2”) insert (model pending on size. P/t plugs without collar.
number ABV2). P/t plugs with collar.
FlowCon Unimizer®
FlowCon AHU The valve is available with double union end
The valve is available for double flanged connec- connections or double flange connections de-
tions for all model sizes. P/t plugs without collar. pending on size. P/t plugs without collar.

FlowCon FIT FlowCon UniQ®


The valve is available with double union end The valve is available with fixed female-by-female
connections or double flange connections de- threaded connections. Further, it is available
pending on size. P/t plugs without collar. with fixed 20 mm male ISO threaded connec-
tions suitable for DN15 EuroCone according
FlowCon Green.3 to EN215. The UniQ® model numbers are
The valve is available with fixed female-by-fe- U.0.XX.1.I, U.0.XX.2.I and U.0.XX.3.I.
male threaded connections for all model sizes.
P/t plugs with collar. FlowCon Wafer
The wafer is available for double flanged connec-
FlowCon Intelligent Meter tions for all model sizes. P/t plugs without collar.
The valve is available for double flanged connec-
tions for all model sizes. P/t plugs without collar.

Latest release of any FlowCon material is available on www.flowcon.com Page 2 of 4


FlowCon General Instruction
1B95011 - 01/2019

Valve Threaded Ends: Capillary tubes are not to be damaged.


Thread standard is either ISO 228, which is a Therefore, do not force the tube to compress or
straight metric thread (compatible with BS-2779) bend with a bending radius below 20 mm (3/4”).
or NPT threading standard, depending on the
product number ordered. Capillary tube for inserts (ACC00110)
Capillary tube is supplied with fixed M8 fitting
Valve Flanged Ends: and O-ring at each end. Ensure that the O-ring
Flange ends are compatible with DIN steel flang- is greased and correctly placed before finger
es PN10, PN16, PN25 and/or PN40 according to mounting the capillary tube in the FlowCon
EN1092-1 or ANSI steel flanges class 150 and/ QuickDisc® (DO NOT OVERTIGHTEN AS THIS
or 300 according to ASME B16.5. depending on WILL DAMAGE THE O-RING). If the capillary
product ordered. tube is to be mounted in a FlowCon Partner Ball
Flanges are not supplied by FlowCon. or other valve with 1/4” (ISO 7/1) tapping, a 1/4”
to M8 adaptor is available (ACC00121). Thread
sealing and O-ring lubrication are described else-
FLOWCON VALVE ACCESSORIES: where in this General Instruction.

Two different types of pressure/temperature fit- Capillary tube for PIM-DP (F212)
tings (p/t plugs) are available upon request for Capillary tube is supplied with fixed angled
valves with body tappings, i.e. p/t plugs with- 1/4” NPT fitting (F4039-14) at one end going
out collar and p/t plugs with collar. Suitable to the FlowCon Partner Globe with an adaptor
p/t plug choice will depend on the valve. Alterna- (ACC6584). The other tube end is to be as-
tive to p/t plugs, the valve body can be ordered sembled in the 1/4” NPT fitting already mounted
with plugs for the body tappings. Extended p/t on the FlowCon PIM-DP. Thread sealing is de-
plugs (without collar) are standard included with scribed elsewhere in this General Instruction.
FlowCon AHU and FlowCon Wafer.

Before finger mounting p/t plugs without collar in FLOWCON INSERTS:


the body tappings (DO NOT OVER TIGHTEN),
please seal the threads of the p/t plugs. Thread Please see specific installation instruction for
sealing is described elsewhere in this General selected insert (Green, EVS, E-JUST, Composite,
Instruction. P/t plugs with collar as well as plugs Stainless Steel, SDP, EDP, ADP or T-JUST) re-
are sealed by a gasket. After finger mounting, garding valve housing match, installation and
gasket sealing requires 1-3 Nm torque. setting.

Threaded union end connections (male or fe-


male) for union end connected valves must have FLOWCON ACTUATORS:
the union nuts and the end connections should
be removed for installation. Please see specific installation instruction for se-
lected actuator (EV, FT, FN, FH, SM, BB or T)
Soldered union end connections (sweat) for regarding product fitting, mounting position and
union ned connected valves must have the END wiring. For product match please read FlowCon
CONNECTIONS REMOVED FROM THE HOU- Actuator Matrix.
SING BEFORE SOLDERING. THIS ENSURES
THAT THE O-RINGS AND INTERNAL PARTS
ARE NOT DAMAGED BY HEAT.

Latest release of any FlowCon material is available on www.flowcon.com Page 3 of 4


FlowCon General Instruction
1B95011 - 01/2019

FlowCon International assumes no responsibility for mistakes, if any, in any printed material.