Você está na página 1de 5

1

2006 IEEE PES Transmission and Distribution Conference and Exposition Latin America, Venezuela

Protection System Considerations for 400 kV


Series Compensated Transmission Lines of
the Central Western Network in Venezuela
Rogelio A. Castro and Hector A. Pineda

kV transmission lines: 1, 2 and 3 Yaracuy – Tablazo, Yaracuy


– Planta Centro and Yaracuy – Arenosa (see Fig. 1). These
capacitor banks were installed in order to reduce the line
equivalent reactances and thus increase power transmission
limits.
Previous studies [1] carried out to verify the effects of se-
ries compensation in the existing protections, for the system
mentioned above, determined the necessity to replace those
protections since they would be affected by inherent pheno-
mena such as voltage reversals and subsynchronous oscilla-
tions; and the necessity to adapt solid-state LZ96 protections,
for the 765 kV line Arenosa – Yaracuy, through the installa-
tion of ancillary modules KR91 and EM91 designed for series-
compensated lines.
New numerical protection, designed to operate in series
compensated systems, replaced existing relays; nevertheless, it
was necessary to carry out a study to determine new settings
Index Terms-- Capacitor compensated transmission lines, Pro- considering series compensation effects, emphasizing first and
tective relaying, Subsynchronous resonance. second zone evaluations due to under and overreaching pro-
blems that could affect impedance measurement in distance
I. INTRODUCTION protections. In the present work main factors considered in the
determination of settings for the new protections of the Central
T HE Series Compensation Project was carried out between
2002 and 2004, and contemplated the installation and
commissioning of five (5) capacitor banks in the existing 400
– Western Network including 765 kV line Arenosa – Yaracuy
are presented.

Fig. 1. 400 kV Central – Western Network (First Stage).

1-4244-0288-3/06/$20.00 ©2006 IEEE


2

15

II. BASIC THEORY 10

E q u iv a le n t R e s is ta n c e a n d R e a c ta n c e
5
The phenomena that influence the performance of dis-
0
tance protections in series-compensated systems are des-
-5
cribed as follows.

(o h m s )
Rc
-10
A. Current and Voltage Reversals -15 Xc
Voltage reversal effect is presented when the apparent -20

impedance between the relay location and the fault point, -25

within the protected line, is mainly capacitive, as a result of -30

the capacitor bank influence. Under these conditions the -35

voltage seen by the protection will be in anti-phase to the 0 1 2 3 4 5 6 7 8 9 10 11


Multiples of Capacitor Bank Current
source voltage as may be observed in Fig. 2. On the other
hand, the current reversal phenomenon is presented when
Fig. 4. Resistance and reactance equivalents
the total impedance between the source and the fault point
is mainly capacitive. The studies determined that current
This increment of the resistance, as a consequence of
reversals are not produced in the 400 kV Central –Western
MOV conduction, should be considered in the setting crite-
Network.
ria of zone reach of the distance protection, in series-com-
pensated systems.
C. Subsynchronous Oscillations
In series compensated networks low frequency transients
are due to the resonant condition created between the series
capacitors and the network series inductances, which are
always subsynchronous frequency transients. The sub-
synchronous frequency response superimposes a subsyn-
chronous component on the current and voltage that are
Fig. 2. Voltage profile considering series capacitor effect. observed by the transmission line protective relays. Be-
cause the frequency is so low, it is difficult to filter the sub-
B. Capacitor Bank Non-linear Apparent Impedance synchronous frequency component rapidly enough to pro-
Series compensation banks installed in the 400 kV Cen- vide a satisfactory relay speed of response. The subsyn-
tral – Western Network use as a primary overvoltage pro- chronous frequency component can be relatively large and
tection a metal oxide varistor (MOV). When the peak vol- the current peaks may exceed the current peaks for the un-
tage reaches the protective threshold level, the MOV con- compensated line due to the addition of the synchronous
ducts limiting excessive voltage across the capacitor. Ac- and subsynchronous values. These higher currents may
cording to Goldsworthy model [2], the apparent impedance cause capacitor overvoltage devices to bypass the capacitor.
of the capacitor/varistor arrangement, as a function of the Low frequency transients can cause problems to the
current flowing in the line, can be represented in the measurement elements of the protective relays, both in fault
equivalent circuit shown in Fig. 3. location and directional performance.
D. Under and Overreaching problems
Voltage reversals, produced during fault conditions, can
cause a wrong directional decision of “self-polarized” im-
pedance based relays, due to the fact that those relays are
polarized by the voltage of the faulty phase to perform di-
rectional decision. This problem is more critical in case of
faults close to the capacitor bank, where the apparent im-
pedance seen by the relay is located out of the first zone of
protection, producing an underreaching effect and thereby
Fig. 3. Capacitor/varistor Goldsworthy equivalent model
the fault is not cleared adequately (see Fig. 5).
On the other hand, for this type of faults there is a risk
As the current through the capacitor bank increases, as
that the first zone of remote protections, in adjacent lines,
well as the conduction of the MOV, the capacitive reac-
may present overreachings, depending if the series capaci-
tance begins to decrease, appearing a resistive component
tor is short-circuited or not by the overvoltage protection
whose peak occurs for 2 times the threshold current (see
scheme. It is important to consider that the reach of dis-
Fig. 4).
tance protection is affected by the series capacitor steady
state influence and by the subsynchronous oscillations pro-
3

duced by the compensation. distance protection in series-compensated networks, the po-


larization voltage, used for fault detection and phase selec-
tion, is controlled by an impedance based non-directional
zone; this information is used for the disconnection of the
faulty phase voltage of the positive sequence filter in order
to prevent its use.
Constructively, distance protections designed for series-
compensated systems use additional filtering processes
both for high frequency transients produced by spark gap
discharges of the series compensation bank, and for very
low frequency oscillations.

III. PROTECTIONS SETTING CRITERIA FOR CENTRAL –


WESTERN NETWORK
The setting criteria determination and validation, related
to new protections REL531 installed in 400 kV Central –
Western Network, were performed among the companies
Fig. 5. Directionality loss and overreach effect.
ENELVEN, CADAFE and EDELCA during OPSIS Pro-
tection Coordination and Faults Analysis Work Group
To determine the optimum reach of first zone, the de-
meetings. In those meetings the studies carried out by the
crease of the series reactance of the transmission line,
manufacturer, which simulated the non-linear MOV cha-
caused by the capacitors inclusion, should be considered:
racteristic in order to calculate apparent impedance seen by
Zl − jXc , (1) the relays in different points of the system, were revised in
Where Zl is the protected line impedance, and Xc the ca- order to verify the theoretical recommended adjustment. It
pacitor bank reactance; is important to notice that the manufacturer’s studies were
The first zone reduction should be large enough to avoid carried out using the computational tool PSS/E and
overreachings produced by voltage inversion and/or sub- EDELCA, in order to validate those studies, developed an
synchronous oscillations in the remote protections of adja- alternative model using ATP, with similar results.
cent lines (see Fig. 6). The results of the evaluations carried out for the first
zone (Z1), second zone (Z2) and ancillary zone for com-
pensated systems (ZR) are presented subsequently, since
these are the most impacted distance protection zones by
voltage reversal and subsynchronous oscillations effects.
A. First Zone Evaluation
Due to the effect of subsynchronous oscillations caused
by series capacitor, during fault conditions, the basic
evaluation adjustment of the distance protection first zone
[3] should be reduced with respect to the conventional cri-
teria, as it is detailed in Fig. 7.

Fig. 6. First zone reduction.

E. Relay Operation Principles for Series-Compensated


Networks
Conventional distance protection cannot perform an ap-
propriate discrimination of the fault direction in the pres-
ence of voltage inversion phenomenon since the relay uses
the voltage of the faulty phase (which is inverted) to deter-
mine the fault direction. Relays designed for series-com-
pensated systems use the voltages of the healthy phases as
polarization quantities for asymmetric faults, known as
cross-polarization. In the case of three phase faults, where
the three voltages can be inverted or affected by subsyn- Fig. 7. First zone maximum reach as a function of the degree of compen-
sation
chronous oscillations, memory units with positive sequence
filters are used to perform the polarization. Commonly, for
4

“C”, the degree of compensation of the line is defined TABLE II


SUMMARY OF FIRST ZONE SETTING CRITERIA
as:
C = ( Xc / Xl ) ⋅100% (2)
Being “Xc” and “Xl” the capacitor bank and the pro-
tected line reactance respectively.
The “p” value corresponds to the maximum permitted
first zone reach, due to subsynchronous oscillations, as a
percentage of the line impedance for a given value of “C”.
Table I details the compensation percentages of the 400
kV lines. Lines Planta Centro – Arenosa do not have com-
pensation, hence an 80% of the line impedance is used as
basic criterion. Meanwhile, relatively short lines Tablazo –
Cuatricentenario use a basic setting of 75% since they have
compensation banks in adjacent lines.

TABLE I
DEGREE OF COMPENSATION AND MAXIMUM PERMITTED REACH IN
COMPENSATED LINES

B. Second Zone Evaluation


The second zone of new REL531 distance protection is
used both for Permissive Overreaching Transfer Trip
In the basic setting evaluation, considering compensated
(POTT) scheme and as a conventional backup delayed
lines, the “p” value is applied in both extremes to the dif-
zone.
ference given by (1).
In Table III the adjustment criteria for distance protec-
This rule is applied excepting the case in which the po-
tion second zones of the 400 kV Central – Western Net-
tential transformer location is in the line side of the ca-
work are presented.
pacitor bank. This is the case of the line Yaracuy – Planta
Centro in the busbar Yaracuy, where “p” is directly applied The POTT scheme was the Pilot Protection Scheme se-
lected due to the necessity to protect the whole line in a
to line impedance.
non-delayed zone facing the critical underreaching pro-
In Table II the summary of setting criteria for the first
blems presented by the first zone in many cases.
zone is presented.
The simulations carried out to verify the first zone reach
TABLE III
in 400 kV lines, showed that, in the compensated line ter- SUMMARY OF SECOND ZONE SETTING CRITERIA
minals located in the opposite side of the capacitors bank,
distance protections overreach the remote busbar for some
fault conditions; thereby it was necessary to perform a con-
siderable reduction of first zone reach. The most critical
case is presented in the line Yaracuy – Arenosa in busbar
Arenosa, in which an outstanding first zone reach reduction
is shown with less than 7% of the line impedance.
For the lines Yaracuy – Tablazo, in busbar Yaracuy, the
first zone reach reduction obeys to the fact that for single
phase faults in the remote busbar, considering basic crite-
rion, overreachings are produced; nevertheless, for phase –
phase faults these overreachings are not produced, so that
the first zone phase – phase reach (which can be set inde-
pendently) corresponds to the basic setting with a resistive
reach reduction, and for single phase faults the first zone
reach is set as shown in Table I.
The critical case of the lines Yaracuy – Planta Centro
and Yaracuy – Arenosa settings corresponds to three phase
faults in the remote busbar, in which overreachings may be
produced.
The basic criterion of the second zone should consider
5

providing protection to the whole line even in the case of resulted insufficient in line protection; thereby it was
capacitor banks being out of service, in a preliminary con- necessary to enlarge second zone reach regarding rec-
sideration. For all the 400 kV lines a basic adjustment of ommended value.
120% of the line impedance without compensation was • The protection scheme selected for all 400 kV lines
considered. was Permissive Overreaching Transfer Trip, implying
In the performed simulations could be determined that a greater dependency of teleprotection equipments.
the basic criterion does not permit providing protection to
the whole line for some conditions. V. ACKNOWLEDGMENT
As may be observed, the cases in which second zone The authors gratefully acknowledge to A. Garcia
reach was increased, with respect to basic adjustment, co- (ENELVEN), E. Lugo (ENELVEN), L. Perdomo
rrespond to relatively short lines Cuatricentenario – El (CADAFE) and E. Quintero (OPSIS), whose contribution
Tablazo, close to compensated long lines Yaracuy – El in a cooperative effort permitted the development of this
Tablazo; and, lines Planta Centro – Arenosa close to high- paper.
est compensation degree lines.
VI. REFERENCES
C. Ancillary Zone for Compensated Systems Evaluation [1] L. Messing, “Investigation Report Distance Protection in Series
Compensated Systems, Enelven” ABB Power Systems. Sweden.
The ancillary zone for compensated systems ZR should Apr. 2002
be larger than the compensation bank capacitance and at the [2] Goldsworthy, Daniel L., “A Linearized Model for MOV–Protected
same time larger than the first (Z1) and second (Z2) zones, Series Capacitors” IEEE Trans. on Power Systems, p. 953-58 Nov.
1987.
which are the most impacted ones by voltage reversals. For [3] Asea Brown Boveri, “REL 531*2.3 High speed line distance pro-
the protection REL531 the adjustment criterion selected for tection terminal”. ABB Publication 1MRK 506 107-UEN, p. 54-
the ancillary zone ZR was: 105. Jul. 2001.
[4] Alexander, G.E., J. G. Andrichak; S.D. Rowe, and S.B. Wilkinson,
“Series Compensated Line Protection: A Practical Evaluation”, a
ZR > Z 2 ∴ ZR = 120% Z 2 (3) paper presented to the Pennsylvania Electric Association, Pitts-
burgh, PA., January 26-27, 1989.
[5] GE Power Management “Series Compensated Line Protection:
In the 765 kV line Arenosa – Yaracuy was installed a Evaluation & Solutions”. GE Publication GER-3736. 1998.
complementary directional unit composed of 2 modules [6] Stan Wilkinson “Series Compensated Line Protection Issues”. GE
(KR91+EM91) being applied the following criterion of Publication GER-3972. 1999.
[7] P.M. Anderson and R.G. Farmer. “Series Compensation of Power
adjustment: Systems”. PBLSH! Inc. Apr. 1996. pp. 151-224.
ZR > M 2 , (4) [8] W.A. Elmore, “Protective Relaying Theory and Applications”,
Marcel Dekker Inc., New York, 1994, p. 256-259.

Where “M2” is the overreaching zone of LZ96 solid-


VII. BIOGRAPHIES
state relay. Then,
ZR = 150% M 2 (5)
Rogelio A. Castro graduated in electrical engi-
neering from the Simon Bolivar University, Ca-
During the simulations performed it was verified that the racas, Venezuela in 1998.
ancillary zone for series-compensated systems, with the Since 1999 he works for CVG Electrificación
del Caroní, C.A. (EDELCA), Puerto Ordaz,
proposed adjustments, operate correctly during any voltage Venezuela in the Transmission Protection Main-
inversion; being guaranteed the correct directional decision tenance Department. His employment experience
of the relay for any faults in the protected line. includes studies, coordination and commissio-
ning of protection systems in several new substa-
tions, and; fault analysis development, improve-
IV. CONCLUSIONS ment projects and protection systems maintenance of EDELCA Transmis-
sion Network.
• Series compensation produces, during fault conditions,
voltage reversals and subsynchronous oscillations both Héctor A. Pineda graduated as electrical engi-
in the 400 kV Central – Western Network and in the neer in the Carabobo University, Valencia, Vene-
zuela in 1986.
765 kV line Arenosa – Yaracuy. He holds, in EDELCA, the head of Protection
• Due to series compensation effects it was necessary to Systems Engineering Section, in the Transmis-
replace the existing distance protections in the 400 kV sion Protection Maintenance Department, res-
ponsible to carry out and supervise the faults
Central – Western Network by new protection analyses, studies and coordination and improve-
REL531; and to adapt LZ96 protections of 765 kV line ment projects of the protections related to
Arenosa – Yaracuy. EDELCA Transmission System.
• The protection first zones in the line terminals located
in the opposite side of the capacitor bank were reduced
considerably due to overreaching problems.
• The basic second zone adjustment, in several cases,

Você também pode gostar