Study on VFTO in UHV GIS Substation

WAN Yiru, CHEN Guang, ZHOU Hao


College of Electrical Engineering
Zhejiang Univ
Hangzhou, China

Abstract—In GIS substations, operations of disconnectors Compared to 500kV systems, characteristics of VFTO in
may cause very fast transient overvoltage (VFTO) with high 1000kV GIS are analysed in this paper. The preventive
amplitude and steep wave front. Considering the narrower measures are analyzed and summarized. Based on practical
insulation margin of UHV GIS equipments and larger absolute Jindongnan UHV GIS substation arrangement, a simulation
magnitude of VFTO in UHV GIS systems, VFTO in UHV GIS model is established by EMTP. The VFTO waveform and
systems could cause larger damage than those in EHV and lower amplitude generated by operating disconnectors are simulated
ones. Therefore study on VFTO in UHV GIS systems is of great and analyzed. The suppressive effect of shunt resistor is
significance to choose more economical and more effective discussed, and preventive measures are suggested.
measures to prevent VFTO, in order to finally improve the safety
and reliability of UHV GIS systems. In this paper, characteristics
and hazards of VFTO in UHV GIS systems are analyzed by II. CHARACTERISTICS OF VFTO IN UHV GIS
comparing it to that of EHV GIS systems. Comparison shows Firstly, as the system voltage increases from 500kV to
that the absolute value of VFTO in UHV GIS system is almost as 1000kV, the absolute VFTO value in 1000kV GIS substation
twice as that of EHV GIS systems, but the insulation level of is almost twice as that in 500 kV GIS substation. However, the
UHV GIS equipments is only 1.55 times as that of EHV ones,
insulation level of 1000kV GIS equipments only increases by
resulting in much more danger in the UHV GIS equipments.
Then, several preventive measures are analyzed and summarized
55% compared with 500kV GIS. Due to the narrower
in this paper, by simulating Jindongnan UHV GIS substation insulation margin of 1000 kV GIS, VFTO could cause larger
based on EMTP. The maximum amplitude of VFTO with no damage to the insulation structure of UHV GIS than that of
suppressing measures is up to 2.72 p.u., dangerously exceeding 500 kV and lower systems.
the limit level of insulation, which is about 2.32 p.u. in UHV GIS Secondly, owing to the simpler arrangement of 1000kV
systems. Analysis shows that installing proper shunt resistors in UHV GIS system, high-frequency components in VFTO are
disconnectors is the most feasible and effective preventive
much larger and the overvoltage front is steeper, making the
measure at present. In spite of the lack of practical applications,
VFTO is much severer.
ferromagnetic rings have great prospects of effectively
suppressing VFTO. All possible switching sequences in Thirdly, the transformer turn-to-turn insulation suffers
Jindongnan UHV GIS substation are analyzed and simulated, more from VFTO in UHV GIS than in 500kV GIS. The
among which the one that generates the severest VFTO is found extremely steep front of VFTO will produce uneven interturn
out. Because the transformer of Jindongnan UHV GIS substation voltage distribution in transformer windings and cause severe
is connected to bus through overhead lines for long distance, the damage to the turn-to-turn insulation, especially the insulation
steepness of wave front is effectively reduced, thus VFTO will not of the first several windings at the transformer entrance
threaten the transformer.
directly connected with GIS. The absolute value of VFTO in
Keywords-UHV, GIS, VFTO, disconnector, shunt resistor
1000kV GIS is about twice as that in 500kV GIS, and its
steepness is larger, making the transient voltage distribution in
the first several windings of transformer more uneven, which
I. INTRODUCTION causes greater threat.
At present, study on UHV GIS is inadequacy. Except
Fourth, because of the great significance of 1000kV GIS
China, former Soviet Union and Japa, few countries have built
substation in the UHV transmission system, 1000kV GIS
or designed 1000kV AC transmission lines. Because former
substation requires higher safety and reliability. Thus it’s
Soviet Union adopted AIS arrangement mode, their
necessary to pay sufficient attention to the VFTO of 1000 kV
engineering design, key technology and practical experience
GIS.
are not related to VFTO of UHV GIS substations. Japan has
built a double-circuit UHV AC transmission line in 1992,
which has been operating at 500kV ever since its III. SUPPRESSIVE MEASURES
establishment, therefore VFTO is relatively low. Considering the threat of 1000 kV GIS VFTO, taking
In 2009, the 1000kV Jindongnan - Nanyang - Jingmen effective measures to suppress VFTO become particularly
UHV AC pilot project has been formally put into practical important. Because of the constraints of measuring conditions
operation. Its GIS substation arrangement is different from and methods, a number of suppressive measures have many
those of former Soviet Union and Japan. Therefore, study technical problems. Practical applications are limited, making
based on the actual situation of Jindongnan GIS substation is many of them unfeasible to be applied into practice yet.
necessary[1-5].

978-1-4577-0365-2/11/$26.00 ©2011 IEEE 1756


A. Shunt Resistor in Disconnector series with GIS conductor as shown in Fig.3 above. The ferrite
Among a variety of suppressive measures for VFTO, shunt rings show different magnetic property in the low and high
resistor has the most obvious effect and mature technology, frequency working conditions.In the low frequency working
and has been widely applied. Taking operating cost into condition,the ferrite rings mainly show inductance
consideration, 500kV system does not necessarily need shunt characteristic, the non-linear resistor Rd is short-circuited,
resistor. With narrower insulation margin, higher VFTO magnetic loss is little.In the high frequency working condition,
amplitude and steeper wavefront, installation of shunt resistor the ferrite rings mainly show resistance characteristic,most of
is recommended in 1000kV GIS. the current flows through the resistance Rd, and the high
frequency energy transforms into heat energy, which plays the
role of overvoltage suppression.
Currently, the ferrite material is mainly used for high-
frequency attenuator, etc, the application for the suppression
of VFTO still needs further study and experimental
verification.

(a) Internal structure of disconnector with shunt resistor;


(b) Disconnector in closed position; (c) Middle position 1;
(d) Middle position 2; (e) Complete breaking position;
(f) Equivalent citcuit of disconnector with shunt resistor
Figure.1. Internal structure and the operate process of disconnector with shunt
resistor

Fig.1 shows the internal structure and the operating


process of disconnector with shunt resistor. The on and off
resistor may share the same one. When the disconnector
breaks, the main contact breaks first, the remaining charge on Figure.2. Ferrite rings Application Diagram
the stationary contact leaks through the shunt resistor branch,
then the vice contact breaks. When the disconnector closes,
the vice contact closes first, current flows through the shunt
resistor branch, then the main contact closes. In both
operations, the shunt resistor acts as an buffering element to
the transient process, leaking the remaining charge and
absorbing the overvoltage energy[6-8].

B. Coupling Capacitors
Installation of parallel coupling capacitors on the
transformer’s high-voltage side can reduce the voltage Figure.3. Equivalent circuit of ferrite rings
amplitude and the steepness of wave front at the transformer E. Improvement of GIS Arrangement and Operating
entrance and filter the high-frequency components of VFTO.
Procedure.
However, in some cases, it may cause maximum over-voltage
in the substation increase remarkably.
IV. ANALYSIS OF VFTO IN JINDONGNAN GIS
SUBSTATION
C. Wave Trapper
Connection of wave trapper on the transformer high side
can filter high-frequency components significantly, but the Fig.4. shows the main circuit of Jindongnan GIS
effect of reducing voltage amplitude is not obvious and it may substation, which is in double-breaker and single-bus
induce high-frequency harmonics in the substation. connection mode, with one outgoing line and one transformer.
Based on the main circuit diagram, the systematical simulation
model is built. Considering the worst situation, the remaining
D. Ferrite Rings
load side voltage is regarded as -1.0pu when reignition
Ferrite is a kind of high-frequency magnetic material, happens, while the source side voltage is regarded as +1.0 pu.
which is nonlinear. Putting ferrite rings around a GIS Multiple reignition is ignored[9].
conductor as Fig. 2, can absorb the transient energy when the
disconnecting switch restrikes to inhibit the VFTO.
The ferrite rings around a GIS conductor can be simplified
to a set of nonlinear inductance and nonlinear resistance, in

1757
In addition, the transformer connects to the GIS conductor
through overhead lines for long distance. So the VFTO
generated by breaking the four disconnectors will be
effectively reduced to about 1.0 p.u. at the antrance of
transformer, and the steepness of wave front is also more
gentle.In fact, it can not be called VFTO anymore. Thus the
VFTO generated by breaking the disconnectors will not
threaten the transformer insulation.

CVT
If one of the circuit breakers needs maintenance, and the
other circuit breaker still keep running, tnen the routine
operation sequence is: firstly break the circuit breaker that
needs maintenance, secondly break the disconnector of the bus
side, last break the disconnector of the outgoing line side. The
Figure.4 Main circuit of Jindongnan GIS substation VFTO generated by breaking the disconnectors when
maintaining circuit breaker CB1 and CB2 were calculated,
Before breaking the four disconnectors theresults was shown in Table 2.
(DS11,DS12,DS21,DS22)on the high voltage side of the
transformer, circuit breakers CB1, CB2 must be broken. When
breaking the four disconnectors (DS11,DS12,DS21,DS22), TABLE II. MAXIMUM VFTO IN JINDONGNAN GIS SUBSTATION BY
BREAKING THE DISCONNECTORS WHEN MAINTAINING CIRCUIT BREAKER
one side of the disconnector is connected to the power source,
and the other side of the disconnector is connected to a branch Maintain CB1 Maintain CB2
conductor with a fracture. So there is huge voltage difference
between two sides of the disconnector, thus when operating operation maximum operation maximum
these disconnectors, large VFTO will be ganerated. GIS sequence VFTO/p.u. sequence VFTO/p.u.
internal maximum VFTO appears at the fracture between the
disconnector oprated and the circuit breaker nearby. The high DS1B 1.78 DS2B 1.75
voltage at the branch end is the result of repeated refraction
and reflection of the voltage waveform. There are four DS1A 2.27 DS2A 2.39
different operation sequences when breaking these four
disconnectors, table 1 shows the four kind of operation
sequences and the maximum VFTO every kind generated. From the table 2 it can be seen that, the maximum VFTO
When calculation the remaining load side voltage is regarded appears when breaking the disconnector DS2A for maitenance
as -1.0pu when reignition happens, while the source side of circuit breakers CB2, the amplitude is 2.39p.u., exceeding
voltage is regarded as +1.0 pu. the limit level of insulation, which is about 2.32 p.u. in UHV
GIS systems. And the VFTO generated by breaking the
TABLE I. MAXIMUM VFTO IN JINDONGNAN GIS SUBSTATION FOR disconnector DS1A when maitenance of circuit breakers CB1
EVERY OPERATION SEQUENCE is 2.27p.u.. The amplitude is under the limit level of insulation
operation sequence sequence sequence sequence
in UHV GIS systems, but it is extremely close to the limit
level (2.32 p.u.). So The VFTO generated by breaking the
steps A B C D disconnectors when maintaining circuit breaker will cause
great damage to the GIS insulation.
1 DS1B DS1A DS2A DS2B
In addition, the transformer connects to the GIS conductor
2 DS1A DS1B DS2B DS2A through overhead lines for long distance. So the VFTO at the
antrance of transformer will be effectively reduced.In fact, it
3 DS2B DS2A DS1A DS1B can not be called VFTO anymore. Thus the VFTO generated
by breaking the disconnectors when maintaining circuit
4 DS2A DS2B DS1B DS1A
breaker will not threaten the transformer insulation.
maximum the VFTO generated by Closing the disconnectors is
2.72 2.39 2.39 2.45
VFTO/p.u. similar to above situation of breaking the disconnectors, so the
review of VFTO is Omitted.
the bold disconnector is the one generate maximum VFTO during the operation sequence
Meanwhile, the VFTO at arresters, CVT, reactors and
other equipment in Jindongnan GIS substation is all under the
From the table 1 it can be concluded that the sequence A limit level of insulation, it will not threaten the insulation of
generated the most severe VFTO, and no matter in which these equipment.
operation sequences, the VFTO generated by breaking the It can be summarized that the VFTO generated by
disconnectors will exceed the limit level of insulation, which operating the disconnectors in Jindongnan GIS substation will
is about 2.32 p.u. in UHV GIS systems, causeing great cause great damage to the GIS insulation. Because the
damage to the GIS insulation[10]. transformer connects to the GIS conductor through overhead

1758
lines for long distance, the VFTO at the antrance of (b) With 500Ωshunt resistor
transformer will not threaten the transformer insulation. Figure. 5 Maximun VFTO waveforms

VI. CONCLUSION
V. SUPPRESSIVE EFFECT OF SHUNT RESISTOR STALLED
In UHV GIS substations, the operations of disconnectors
IN DISCONNECTORS
will generate VFTO with larger voltage amplitude, frequency
Fig.5 shows waveform comparison between disconnectors and wave-front steepness than in 500kV GIS. VFTO has much
with and without a 500Ω shunt resistor. Without the shunt more threat to the 1000kV GIS insulation than to 500kV GIS,
resistor, the voltage waveform mutates during the therefore the shunt resistors in disconnectors is recommended
disconnector’s reignition, generating very steep pulses with to be installed.
maximum amplitude of 2.72pu and high oscillation
frequencies. In Jindongnan GIS substation, without suppressive
measures, the maximum VFTO in GIS is up to 2.72pu,
After the installation of 500Ω shunt resistor, the VFTO causing great damage to the GIS insulation. After the
reduces to 1.24pu, The installation of 500Ω shunt resistor installation of 500Ω shunt resistor, VFTO maximum drops to
effectively reduces the over-voltage amplitude, oscillation 1.24pu, and at the same time the steepness and high frequency
frequency, wave-front steepness and high-frequency both reduce. The suppressive effect is obvious.
component.
REFERENCES
[1] GU Ding xie, XIU Mu-hong, DAI Min. “Study on VFTO of 1000 kV
GIS substation,” High Voltage Engineering. 2007,(11)
[2] YamagataY,Nakada Y. “Very fast transients in 1000 kV gas insulated
switchgear,” Proceedings of 1999 IEEE Transmisslon and Distribution
ConferenceI Vol 2.[S.L],1999 : 501- 508.
[3] Povh D, Schmitt H, Valcker O. “Modeling and analysis guidelines for
very fast transients,” IEEE Trans on PWRD , 1996 ,11 (4) : 2028-2035.
[4] Ozawa J, Yamagiwa T, Ho sokawa M. “Suppression of very fast
transient overvoltage during gas disconnector switching in GIS,” IEEE
Trans on PWRD , 1986 ,1 (4) : 194-201.
[5] Yanagata Y, Tanaka K, Nishiwaki S. “Suppression of VFT in 1100kV
GIS by adopting resistor-fitted disconnector ,” IEEE Transactions on
Power Delivery, Vol. 11,No. 2, April 1996.
[6] RUAN Quanrong, SHI Wei. “Suppression of VFTO by Disconnector
with Opening and Closing Resistor in GIS,” High Voltage Engineering.
(a) Without shunt resistor 2005,(12)
[7] XIANG Zu-tao, DING Yang, BAN Lian-geng. “Suppressing VFTO in
UHV GIS with switching resistor,” Electric Power. 2007,(12)
[8] RUAN Quan-rong, SHI Wei, WANG Liang. “Study on Suppression of
Switching Overvoltage Caused by Operation of Disconnector in GIS,”
High Voltage Apparatus. 2006,(01).
[9] Shi Bao-zhuang, Zhang Wen-yuan,Gu Wen-guo.“Calculation and
Analysis of Very Fast Transient Overvoltage in GIS,” High Voltage
Engineering. 1997,(04) .
[10] GAO You-hua, SUN Tong, SHEN Li, LIANG Qin. “Research on Very
Fast Transient Over-voltage in GIS,” Journal of Shenyang Institute of
Engineering(Natural Science). 2008,(01)