01. General Arrangement drawing is missing & shall be submitted.

P2

01. On page no. 12, CD value of 1.95 is incorrect & it shall be taken as 2.2*(1+c/20d) but not more
than 4, for deck supported on plate girders, as per Cl. No. 209.3.3 of IRC 6.

Superstructure

01. Live load calculation on deck slab in transverse direction is not presented and shall be added.
02. Impact factor no considered in live load application in transverse direction for deck slab.