Point of ● Run CPU ● DI120~150

TCD - 018 Speed CPU and Communication SYNC ERROR Application


Detection ○ Speed CPU ● DI180~420
When a discrepancy is found between Run CPU SYNC data and Speed [Actions to take]
[Meaning] CPU SYNC data for 5 or more consecutive times in the DRAAM
communication of Speed CUP and Run CPU at 10ms interval. 1. Check +5[V] voltage.
(Run CPU Error Set)
Must be at least +4.8[V] or more.
[Explanation] 1) DOC-200 PCB: +5[V] => Connector MG/1, MG/6
GND=> TP16(Located just above Connector MG)
START
2) DOR-230 PCB: +5[V] => Connector SMP/1, SMP/6
GND=> TP10(Located just above Connector OUT)
Read Sync Data of Speed CPU 3) DPC-1XX PCB: +5[V] => Connector VF/1
from DPRAM
GND=> Connector VF/4, VF/5

Run CPU Sync Data == 2. Verify if DOR-230 PCBs are well connected to connectors.
Speed CPU Sync Data ?
Check contact status for cables for PCB connecting
No connector(MA, VE).
Inv_Sync.Err_Detect
Inv_Sync.Err_Detect == True
== True ? 3. Check switch setting status after replacing
Yes DPC-1XX(or 300) PCB switch.
No
Inv_Sync.Err_Count >3
4. Try replacing DOR-230, DPC-1XX(or 300), and DOC-200
Yes in sequence.

TCD 18 Set

END