RATE /

UNIT

QTY. Labour
S No. DESCRIPTION UNIT (Rs.)

A B
1 MEDIUM VOLTAGE CABLES 280 Mtrs. set -

SUPPLY, LAYING (INCLUDING CABLE TRENCH, TRAY OR OTHER CABLEWAYS) TESTING,


TERMINATION, CABLE DRESSING, CABLE TAGGING, CABLE GLANDS, JOINTS & ACCESSORIES,
PRECOMMISSIONING & COMMISSIONING OF MEDIUM VOLTAGE POWER CABLES FROM
1.1 HESCO MV SWITCH BOARD TO OWNER'S MV SWITCH BOARD & FROM OWNER'S MV SWITCH 1 No. -
BOARD TO DISTRIBUTION TRANSFORMER 8.75/15KV VOLTAGE GRADE,
CU/XLPE/PVC/SWA/PVC, WITH HEAT SHRINKABLE TERMINATION KITS ON BOTH SIDES OF
CABLES AND AS PER k-ELECTRIC SPECS/CODES/STANDARDS ETC.

1.1.1 3C-185 SQ.MM 1 LOT -


2 MEDIUM VOLTAGE SWITCHBOARD 1 LOT -

SUPPLY, INSTALLATION, ERECTION, TESTING, PRECOMMISSIONING, COMMISSIONING OF


METAL CLAD, TYPE TESTED MEDIUM VOLTAGE 11KV+/-10%, 50HZ+/-2% AS OWNER'S MAIN MV
SWITCHGEAR PANELS COMPRISING OF 11KV VCB PANEL FACTORY ASSEMBLED, IP RATING
IP42 (MIN), FRONT OPERATED WITH REQUIRED METERING, PROTECTION(INDLUDING
2.1 TRANSFORMER PROTECTIONS), CONTROL, MEASUREMENT ETC. COMPLETE IN ALL
RESPECTS FOR SATISFACTORY OPERATION AS PER k-ELECTRIC SPECIFICATION, THE
SUPPLY OF EQUIPMENT SHALL INCLUDE THE INSTALLATION MATERIALS & COMPLETE CIVIL
WORKS FOR COMPLETE INSTALLATION, PROTECTION & METERING CTs, PTs COMPLETE IN
ALL RESPECT.

3 DISTRIBUTION TRANSFORMER

SUPPLY, INSTALLATION, ERECTION, TESTING, PRECOMMISSIONING AND COMMISSIONING OF


DISTRIBUTION TRANSFORMERS 11/0.4 KV, 2500 kVA(2000 kW) TAP CHANGER, DGPT UNIT, AIR
BREATHER CONSERVATOR TYPE/ HERMETICALLY SEALED WITH ROLLER WHEELS, BUCHOLZ
3.1
RELAY, TEMPERATURE INDICATOR/SWITCH ETC. FOR SATISFACTORY OPERATION FOR
SATISFACTORY OPERATION IN COMPLIANCE WITH ALL TECHNICAL REQUIREMENTS
MENTIONED IN REFERRED SPECIFICATION AND DATASHEET. THE SUPPLY OF EQUIPMENT

3.2 SHALL INCLUDE THE INSTALLATION MATERIALS FOR COMPLETE INSTALLATION OF THE

4 EQUIPMENT I.E. COMPLETE IN ALL RESPECT.


SUPPLY OF RECOMMENDED OPERATION AND MAINTENANCE SPARES FOR TWO (02) YEARS
4.1
OPERATION FOR DISTRIBUTION TRANSFORMERS.
L.V DISTRIBUTION SYSTEM

SUPPLY, INSTALLATION, TESTING & COMMISSIONING OF FOLLOWING LV SWITCHGEAR


PANELS/DISTRIBUTION BOARDS COMPLETE IN ALL RESPECTS INCLUDING SUPPLY &
INSTALLATION OF ALL NECESSARY MOUNTING AND INSTALLATION ACCESSORIES REQUIRED
FOR COMPLETION OF JOB AS PER REFERRED SPECIFICATIONS, DRAWINGS AND ACCEPTED
INDUSTRY PRACTICES.
MAIN DISTRIBUTION BOARD (MDB-001) (TYPE TESTED) IP 42 MIN ALSO INCLUDING THE
FOLLOWING: - TYPE TESTED
PANEL ALONG WITH ITS SWITCHGEAR COMPONENTS i.e., EMERGENCY LIGHT, EXHAUST FAN,
ANALOG VOLT & AMP. METERS WITH SELECTOR SWITCHES, COMPLETE IN ALL RESPECT,
AUTO/MANUAL SELECTOR SWITCH, MAGNETIC CONTACTORS, CIRCUIT BREAKERS MCCB,
INTERNAL POWER WIRING & CONTROL WIRING, WITH MICROPROCESSOR BASED
4.1.1 1 No.
ELECTRONIC MODULE TYPE WITH ALL NECESSARY ACCESSORIES COMPELTE IN ALL
RESPECT. - 2 NO,S 8 STEPS 300 kVAR
PFI PANEL IP 42 MIN ALONG WITH ITS SWITCHGEAR COMPNONENTS i.e., INDICATION LIGHTS,
EXHAUST FAN, CAPACITORS OF KVAR RATINGS, MAGNETIC CONTACTORS, POWER FACTOR
RELAY, CIRCUIT BREAKERS, CONTROL WIRING ETC., WITH ALL NECESSARY ACCESSORIES
COMPELTE IN ALL RESPECT.

4.1.2 POWER DISTRIBUTION PANEL (PDP-001) IP 42 MIN 1 No.


4.1.3 MOTOR CONTROL CENTER (MCC-RO-001) IP 42 MIN 1 No.

4.1.4 AREA LIGHTING DISTRIBUTION PANELS (ALDB-01 ~ ALDB-05) 5 Nos.

4.1.5 MOTOR CONTROL CENTER (EM-MCC-L/G-01) IP 42 MIN 1


4.1.6 MOTOR CONTROL CENTER (EM-MCC-REACTION-01) IP 42 MIN 1
4.1.7 MOTOR CONTROL CENTER (EM-MCC-SORBITOL-01) IP 42 MIN 1
5 LIGHTING POLES
STEEL PIPE, 10 METER HIGH WITH ARMS FOR MULTIPLE 150 WATT LED FLOODLIGHTS WELD
ON THE TOP OF THE POLE AS SHOWN ON TYPICAL DETAIL DRAWING, COMPLETE WITH BASE
5.1
PLATE, EARTHING BOSS ETC. AND OTHER INSTALLATION ACCESSORIES. THE JOB ALSO
INCLUDES CONSTRUCTION OF FOUNDATIONS AND ALL OTHER RELATED CIVIL WORKS
5.1.1 2 FLOOD LIGHTS PER POLE 26 NOS.
5.1.2 3 FLOOD LIGHTS PER POLE 23 NOS.
6 RECEPTACLES

SUPPLY, INSTALLATION, TESTING AND COMMISSIONING OF FOLLOWING INDUSTRIAL TYPE


SOCKET OUTLETS, MOUNTED ON ANGLE IRON STAND, POLYCARBONATE BODY, COMPLETE
6.1
WITH SUITABLE CABLE GLANDS (WEATHER PROOF WITH WEATHER PROOF SOCKETS)
COMPLETE IN ALL RESPECTS

63A, 5-PIN, 400V THREE PHASE SOCKET ( WEATHERPROOF TYPE, IP 55 ) (1 NO. CABLE ENTRY
6.1.1 6 NOS.
WITH INTEGRAL WEATHER PROOF GLANDS FOR 4C-25 50 SQ.MM. ARMOURED XLPE CABLE)

32A, 5-PIN, 400V THREE PHASE SOCKET (WEATHER PROOF, IP 55) (1 NO. CABLE ENTRY WITH
6.1.2 4 NOS.
INTEGRAL WEATHER PROOF GLANDS FOR 4C-25 16 SQ.MM.
6.1.3 16A, 3-PIN, 230V SINGLE PHASE SOCKET (WEATHER PROOF, IP 55) 2 NOS.
7 JUNCTION BOX (FOR NON-HAZARDOUS AREA)
7.1 JUNCTION BOX FOR UTILITY SOCKET OUTLET

SUPPLY, INSTALLATION, TESTING AND COMMISSIONING OF WEATHER PROOF JUNCTION BOX


FOR UTILITY OUTLETS, IP55 (MIN), UV STABILIZED POLYCARBONATE OR SHEET METAL
ENCLOSURE, WITH TERMINALS SUITABLE FOR 2.5MM2 TO 16MM2 STRANDED CONDUCTORS
AS SHOWN IN THE REFERRED JB SCHEDULE, EARTHING TERMINAL RAIL, WITH SUITABLE
CABLE ENTRIES, ARMORED CABLE GLANDS AND INSTALLATION ACCESSORIES COMPLETE IN
ALL RESPECT ALONG WITH INTERNAL WIRING AND TERMINATIONS. THE JB SHALL HAVE
METALLIC GLAND PLATES, LOCKNUTS & WASHERS AND ALL OTHER ACCESSORIES

7.1.1 10 NOS.
7.1.1 10 NOS.
REQUIRED FOR INSTALLATION AS PER REFERRED ANNEXURES AND ACCEPTED INDUSTRY
PRACTICES. COMPLETE IN ALL RESPECT AND AS PER REFERRED TYPICAL INSTALLATION
DRAWING.

EACH JB SHALL HAVE FOLLOWING MINIMUM CONFIGURATION


- 12 NOS. TERMINAL FOR WIRING FROM 2.5 TO 25 SQ.MM CORE
- 4 NOS. M20/M25 ENTRIES
- EARTHING TERMINAL RAIL
- CABLE GLANDS FOR EACH CABLE ENTRY (EX RATED)
8 G.I. CONDUIT

SUPPLY, INSTALLATION OF G.I. CONDUIT OF MEDIUM GAUGE OF MISC SIZES. THE SUPPLY OF
EQUIPMENT SHALL INCLUDE THE INSTALLATION MATERIAL LIKE C/I CHANNEL, BASE PLATE,
8.1
ALONGWITH COMPLETE CIVIL WORKS INCLUDING FOUNDATION ETC. I.E. COMPLETE IN ALL
RESPECT.

8.1.1 1" DIA. 250 R. Mtrs


8.1.2 2" DIA. 150 R. Mtrs
8.1.3 3" DIA. 100 R. Mtrs
9 UPVC CONDUITS

SUPPLY, ERECTION, LAYING, INSTALLATION, TESTING AND COMMISSIONING OF CLASS D


UPVC CONDUIT AS BURIED RUNS OF IT REQUIREMENT AS PER REFERRED DRAWING AT
9.1
DIFFERENT TERMINAL LOCATION. THE JOBS INCLUDES ALL CONDUIT FITTINGS,
REQUIREMENTS FOR COMPLETION OF JOB.
9.1.1 1" DIA. 150 R. Mtrs
9.1.2 4" DIA. 300 R. Mtrs
9.1.3 6" DIA. 100 R. Mtrs
10 CABLE TRAY

SUPPLY AND INSTALLATION OF 16 SWG, PERFORATED GI CABLE TRAY (ASTM A123, CLASS B2)
OF FOLLOWING SIZES COMPLETE WITH TOP COVERS. THE JOB ALSO INCLUDES PROVIDING
10.1 AND INSTALLATION OF TRAY BENDS, SPLICES, TRAY COVER, COVER CLAMPS AND ALL OTHER
MOUNTING AND INSTALLATION ACCESSORIES INCLUDING THE METAL SUPPORT STRUCTURE
REQUIRED FOR TRAY SUPPORT I.E: COMPLETE IN ALL RESPECTS.

10.1.1 900 (W) X 150 (H) 100 RMs


10.1.2 150 (W) X 75 (H) 100 RMs
11 CABLE GLANDS (FOR NON- HAZARDOUS AREA)

INSTALLATION OF BRASS CABLE GLANDS OF FOLLOWING SIZES CONFORMING TO BS 6121


AND SUITABLE FOR CU/XLPE/SWA/PVC LOW VOLTAGE CABLES. GLANDS TO BE SUPPLIED
11.1 -
COMPLETE WITH PCP SHROUD AND SHALL BE, E1W, WEATHERPROOF, SUITABLE FOR IP 66
APPLICATIONS.

E1W20 236
E1W25 12
E1W32 164
E1W40 218
E1W75 4
12 ARMOURED LOW VOLTAGE CABLES (FOR POWER APPLICATIONS).

LAYING, INSTALLATION, TESTING, TERMINATION, CABLE DRESSING, CABLE GLANDS(AS PER

12.1
SITE CONDITION & ENVIRONMENT) TAGGING, PRECOMMISSIONING & COMMISSIONING OF
LOW VOLTAGE POWER AND CONTROL CABLES 600/1000V VOLTAGE GRADE, PVC INSULATED,
12.1 PVC SHEATHED, SINGLE WIRE ARMOURED, ANNEALED COPPER CONDUCTOR WITH TINNED
COPPER LUGS, CRIMPING TYPE WITH CORROSION RESISTANCE, WEATHER PROOF FINISH
COMPLETE IN ALL RESPECT OF THE FOLLOWING SIZES AS PER MENTIONED CABLE
SCHEDULE DETAILS:

12.1.1 1C-120 SQMM-CUPVC/AWA/PVC 100 RM.


12.1.2 1C-185 SQMM-CU/PVC/AWA/PVC 10,070 RM.
12.1.3 1C-240 SQMM-CU/PVC/AWA/PVC 5,250 RM.
12.1.4 1C-300 SQMM-CU/PVC/PVC 1,871 RM.
12.1.5 3C-2.5 SQMM-CU/PVC/SWA/PVC 2,400 RM.
12.1.6 3C-6 SQMM-CU/PVC/SWA/PVC 75 RM.
12.1.7 4C-2.5 SQMM-CU/PVC/SWA/PVC 100 RM.
12.1.8 4C-4 SQMM-CU/PVC/SWA/PVC 3,350 RM.
12.1.9 4C-16 SQMM-CU/PVC/SWA/PVC 665 RM.
12.1.10 4C-25 SQMM-CU/PVC/SWA/PVC 1,785 RM.
12.1.11 4C-35 SQMM-CU/PVC/SWA/PVC 550 RM.
12.1.12 4C-50 SQMM-CU/PVC/SWA/PVC 1,460 RM.
12.1.13 4C-70 SQMM-CU/PVC/SWA/PVC 550 RM.
12.1.14 4C-95 SQMM-CU/PVC/SWA/PVC 580 RM.
12.1.15 10C-2.5 SQMM-CU/PVC/SWA/PVC (450/750 V) 150 RM.
12.1.16 10C-2.5 SQMM-CU/PVC/PVC (450/750 V) 250 RM.
13 EARTHING SYSTEM

SUPPLY AND INSTALLATION OF 25MM DIA X 3M LONG COPPER EARTH ELECTRODE WITHOUT
EARTH PITS COMPLETE IN ALL RESPECTS AS PER RELEVANT DRAWINGS AND
13.1 SPECIFICATIONS. 26 Nos.

SUPPLY AND INSTALLATION OF 25MM DIA X 3M LONG COPPER EARTH ELECTRODE IN


13.2 CONCRETE EARTH PITS COMPLETE IN ALL RESPECTS INCLUDING CONSTRUCTION OF EARTH 15 Nos.
PITS AS PER RELEVANT DRAWINGS AND SPECIFICATIONS.

SUPPLY, LAYING, TESTING, TERMINATION, CABLE DRESSING AND COMMISSIONING OF BARE


TINNED COPPER CONDUCTOR, AS PER IEC 60228 CONSISTING OF CONCENTRIC-LAY
13.3
STRANDED CONDUCTORS MADE FROM UNCOATED ANNEALED ROUND SOFT DOWN COPPER
(TO BS 6360).

13.3.1 240 SQMM 1,500 R. Mtrs


13.3.2 70 SQMM 1,000 R. Mtrs

SUPPLY, LAYING, TERMINATION, TESTING & COMMISSIONING OF FOLLOWING SIZES PVC/PVC


13.4 GREEN / YELLOW EARTHING CABLE. CABLE TO BE INSTALLED EITHER BURIED OR IN
AVAILABLE CABLE TRAYS WHEREVER POSSIBLE.

13.4.1 240 SQMM 50 R. Mtrs


13.4.2 70 SQ. MM. 400 R. Mtrs
13.4.3 35 SQ. MM. 200 R. Mtrs
13.4.4 16 SQ. MM. 300 R. Mtrs
13.4.5 6 SQ. MM. 300 R. Mtrs
SUPPLY, INSTALLATION, TESTING & COMMISSIONING OF EARTH BARS MADE OF HARD DRAWN
COPPER (TINNED), SUITABLE FOR MOUNTING ON STEEL STRUCTURE, CONSISTING OF 10
NOS. EQUALLY SPACED M8 HOLES. EACH PLATE SHALL ALSO HAVE 2 NOS. M10 HOLES FOR
13.5 35 Nos.
MOUNTING. EACH PLATE SHALL BE SUPPLIED WITH 2 NOS. GALVANIZED MILD STEEL TUBE
SPACE RS, AND M10, ELECTROZINC PLATED NUTS, BOLTS AND STAR WASHERS, COMPLETE
IN ALL RESPECTS.

SUPPLY AND INSTALLATION OF MISCELLANEOUS ITEMS CADWELD MOULDS, TERMINATION


13.6 1 L.S JOB
LUGS, ETC
14 LED FLOOD LIGHTS (FOR NON-HAZARDOUS AREA) AREA LIGHTING

SUPPLY & INSTALLATION OF WEATHER PROOF 150W - 230V AC-50HZ LED FLOOD (YELLOW)
LIGHT FIXTURE, IP-65, POLE TOP MOUNTED, WITH INTEGRAL CONTROL GEAR, GLASS
REINFORCED POLYESTER (GRP) OR DIE-CAST ALUMINIUM ENCLOSURE COMPLETE WITH
BALLAST/ STARTERS/ CAPACITORS, ANODIZED ALUMINIUM REFLECTOR (ASYMMETRICAL),
14.1 LAMP ETC. CABLE ENTRIES SHALL BE PROVIDED FOR FIXTURE TO FIXTURE WIRING 132 Nos.
(LOOP/THROUGH WIRING). ALL MOUNTING ACCESSORIES SHALL BE SUPPLIED WITH
FIXTURE. COMPLETE IN ALL RESPECT AND AS PER REFERRED TYPICAL INSTALLATION

DRAWING. FIXTURE SHALL BE SUPPLIED WITH SUITABLE CABLE GLANDS


15 LINEAR LED LIGHTS (FOR NON-HAZARDOUS AREA) TANK LIGHTING

SUPPLY & INSTALLATION OF 36W, 230V 50HZ LINEAR LED LIGHT FIXTURE SUITABLE FOR
WEATHERPROOF PROTECTION TYPE IP-65, GLASS REINFORCED POLYESTER (GRP)
ENCLOSURE PROTECTED WITH HIGH IMPACT ACRYLIC POLYCARBONATE DIFFUSER
COMPLETE WITH ELECTRONIC BALLAST CONTROL GEAR, LED LAMPS, CABLE GLANDS ETC,
15.1 INCLUDING PROVISION OF 2 NOS. CABLE ENTRIES (FOR FIXTURE TO FIXTURE CABLING). ALL Nos.
MOUNTING AND INSTALLATION ACCESSORIES INCLUDING POLE, BRACKETS/CLAMPS
COMPLETE IN ALL RESPECTS AND AS PER REFERRED INSTALLATION DETAILS.

FIXTURES SHALL BE SUPPLIED WITH SUITABLE CABLE GLANDS.

STANCHION MOUNTED VERSION (COMLETE WITH STANCHION / PIPE & ACCESSORIES) 10 Nos.

SURFACE MOUNTED (COMPLETE WITH MOUNTING BRACKETS & ACCESSORIES) 66 Nos.


16 LINEAR LED LIGHTS (FOR NON-HAZARDOUS AREA) MAINTAINED TYPE

SUPPLY & INSTALLATION OF 36W, 230V 50HZ LINEAR LED LIGHT FIXTURE SUITABLE FOR
WEATHERPROOF PROTECTION TYPE IP-65, GLASS REINFORCED POLYESTER (GRP)
ENCLOSURE PROTECTED WITH HIGH IMPACT ACRYLIC POLYCARBONATE DIFFUSER
COMPLETE WITH ELECTRONIC BALLAST CONTROL GEAR, LED LAMPS, CABLE GLANDS ETC,
16.1 INCLUDING PROVISION OF 2 NOS. CABLE ENTRIES (FOR FIXTURE TO FIXTURE CABLING). ALL Nos.
MOUNTING AND INSTALLATION ACCESSORIES INCLUDING POLE, BRACKETS/CLAMPS
COMPLETE IN ALL RESPECTS AND AS PER REFERRED INSTALLATION DETAILS.

FIXTURES SHALL BE SUPPLIED WITH SUITABLE CABLE GLANDS.

STANCHION MOUNTED VERSION (COMLETE WITH STANCHION / PIPE & ACCESSORIES) 25 Nos.

SURFACE MOUNTED (COMPLETE WITH MOUNTING BRACKETS & ACCESSORIES) 5 Nos.


17 JUNCTION BOX (FOR NON-HAZARDOUS AREA)
17.1 JUNCTION BOX FOR POLE AND SHED LIGHTING
SUPPLY & INSTALLATION OF WEATHER PROOF JUNCTION BOX FOR LIGHTING, IP55 (MIN), UV
STABILIZED POLYCARBONATE OR SHEET METAL ENCLOSURE, WITH TERMINALS SUITABLE
FOR 2.5MM2 TO 25MM2 STRANDED CONDUCTORS AS SHOWN IN THE REFERRED JB
SCHEDULE, EARTHING TERMINAL RAIL, WITH SUITABLE CABLE ENTRIES AND INSTALLATION
ACCESSORIES COMPLETE IN ALL RESPECT ALONG WITH INTERNAL WIRING AND
TERMINATIONS. THE JB SHALL HAVE METALLIC GLAND PLATES, LOCKNUTS & WASHERS AND
ALL OTHER ACCESSORIES REQUIRED FOR INSTALLATION AS PER REFERRED ANNEXURES
AND ACCEPTED INDUSTRY PRACTICES. COMPLETE IN ALL RESPECT AND AS PER REFERRED
17.1.1 TYPICAL INSTALLATION DRAWING. 60 NOS.

EACH JB SHALL HAVE FOLLOWING MINIMUM CONFIGURATION


- 12 NOS. TERMINAL FOR WIRING FROM 2.5 TO 25 SQ.MM CORE
- 4 NOS. M20/M25 ENTRIES
- EARTHING TERMINAL RAIL
- CABLE GLANDS FOR EACH CABLE ENTRY (WEATHER PROOF)
18 EM-OFF CONTROL STATIONS (FOR NON HAZARDOUS AREA).

SUPPLY, INSTALLATION, TESTING AND COMMISSIONING OF LOCAL CONTROL STATION (OF


FOLLOWING TYPE) FOR LV MOTORS, IP-55. GRP POLYCARBONATE ENCLOSURE, COMPLETE
WITH CABLE ENTRY (WITH STOPPING PLUG) FOR 10C-2.5MM2 ARMOURED CABLE. LOCAL
18.1 CONTROL STATION SHALL BE SUPPLIED COMPLETE WITH ALL REQUIRED INTERNAL
TERMINALS, EARTHING TERMINALS, GLAND PLATE, NUTS, BOLTS, WASHERS, ETC

COMPLETE IN ALL RESPECT AND AS PER REFERRED TYPICAL INSTALLATION DRAWING.

18.1.1 1 NO. MUSHROOM STAY PUT (LATCHED CONTACT) TYPE OFF PUSH BUTTON WITH KEY LOCK 8 NOS

19 CABLE TRENCH AND DUCT BANKS

EXCAVATION OF CABLE TRENCH 450MM(W) X 800MM(D) AS PER CABLE LAYOUT DRAWING.


THE JOB ALSO INCLUDES BACKFILLING OF CABLE TRENCH AFTER CABLE LAYING. THIS
INCLUDES PROVIDING AND LAYING OF LAYER OF FINE SAND ABOVE AND BELOW THE

19.1 CABLE, PROVIDING AND LAYING OF CABLE TILES COVERING ENTIRE WIDTH OF THE TRENCH, 100 RM
BACKFILLING OF CABLE TRENCH WITH RUBBLE FREE SOIL, COMPACTING OF TRENCH,
INSTALLATION OF CABLE MARKERS.

EXCAVATION OF CABLE TRENCH 800MM(W) X 1000MM(D) AS PER CABLE LAYOUT DRAWING.


THE JOB ALSO INCLUDES BACKFILLING OF CABLE TRENCH AFTER CABLE LAYING. THIS
INCLUDES PROVIDING AND LAYING OF LAYER OF FINE SAND ABOVE AND BELOW THE
19.2 460 RM

CABLE, PROVIDING AND LAYING OF CABLE TILES COVERING ENTIRE WIDTH OF THE TRENCH,
BACKFILLING OF CABLE TRENCH WITH RUBBLE FREE SOIL, COMPACTING OF TRENCH,
INSTALLATION OF CABLE MARKERS.

CONSTRUCTION OF CABLE DUCT BANKS OF FOLLOWING TYPES AT ROAD CROSSING AS PER


REFERRED TYPICAL DETAILS COMPLETE IN ALL RESPECTS WITH ALL CIVIL MATERIAL,
19.3 INCLUDING SUPPLY AND LAYING OF MS PIPES (OF DIMENSIONS AND QUANTITY) AS SHOWN

IN REFERRED DRAWINGS. (ROAD WIDTH TO BE TAKEN AS 6 M FOR EACH ROAD CROSSING)

19.3.1 TYPE-A 3 NOS


19.3.2 TYPE-C 3 NOS
19.3.3 TYPE-D 3 NOS
CONSTRUCTION OF CABLE PITS / HAND HOLES / MAN HOLES OF FOLLOWING TYPES AS PER
19.4 REFERRED TYPICAL DETAIL DRAWINGS COMPLETE IN ALL RESPECTS WITH CIVIL MATERIAL
AS SHOWN IN REFERRED DRAWINGS
19.4.1 TYPE-A 3 NOS
19.4.2 TYPE-B 3 NOS
19.4.3 TYPE-C 3 NOS
19.4.4 TYPE-D 3 NOS
TOTAL
NOTES:
TOTAL OF

AMOUNT
Labour
(Rs.)
C=AXB
-

-
-
TOTAL