PARAMETER LIST
00 Language setting ( Turkish / English )
01 Lift type
02 Command type
03 Number of stops
04 Number of basement
05 Door Type
06 Busy time
07 Lock waiting time
08 Wait at floor time
09 High speed time
10 Low speed time
11 Max. Door time
12 Go to park time
13 Park stop
14 Fire stop
15 Direction arrow light
16 Change password
17 Cancel password
18 Maintenance done
19 Maintenance time
20 Error list
21 Digital setting
22 Special Door Setting
23 Rescue ( Active / Cancel )
24 Duplex setting
25 Call transfer
26 Phase protection ( Active / Cancel )
27 Ptc ( Active / Cancel )
28 Cabin serial card ( Active / Cancel )
29 Automatic door open time
30 Only one door full automatic
32 Revision movement type
01 Ocak 2016
www.hedefsan.net 2
TECHNICAL SPECIFICATIONS
Dimensions
267× 201 × 35
Lenght × Width × Hight (mm)
Operation Temperature ±0 - +60 °C
Protection Class IP20
Humidity %95
Network Control Inputs 3 x 380V, 50Hz, N
Control Feed Voltage 24 ± 5 Vdc
Power Usage Maks. 400mA 10W, 24VDC için
230Vac max. For hydraulic elevators in
Security Circuit Voltage
emergency descent 24Vdc
Control Signal Inputs 24 ± 5 Vdc
24 ± 5 Vdc
Control Signal Outputs
Short-Circuit Protection
01 Ocak 2016
www.hedefsan.net 3
MAJOR FEATURES
2-line 16-character LCD display and 4 button keyboard
RS-485 serial communication for group operation
RS-485 serial communication for serial system connection with cabin
Recording the last 20 errors
Including door bridging safety circuit
Including phase sequential motor protection circuit
Including in- and output control of 2 automatic doors
Short circuit protected digital and signal outputs
Setting of indicator possible via menu: 7-segment, Binary and Gray code
UPS support for emergency descent on hydraulic elevators
01 Ocak 2016
www.hedefsan.net 4
OPENING SCREEN
When you power on, you can view the software version and serial
HD 200 X S
number of the card on the opening screen. After a couple a seconds the
Ver:3.2 SerialNo:15222 screen changes to the MAIN SCREEN.
MAIN SCREEN
Waiting for Recording Here it shows the feed voltage (100) and the number of the floor where
D:15 +25.4V the elevator is at the present.
Revision from card Hold down the exit button for 2 seconds to enter the revision mode.
D:15 +24.0 V Then you can move the elevator with the up and down buttons.
01 Ocak 2016
www.hedefsan.net 5
ENTER MENU
To enter the menu press and hold the ENTER button for 3 seconds. If no
00:Language setting password is defined for an entry permit (0000: initial password), then
English the display shows the first parameter and the text "LISAN / LANGUAGE"
will appear.
PASSWORD MENU
If you previously defined a password, enter your password using the UP
Password ? 00000
and DOWN buttons correctly. Then press the ENTER button to confirm
Serialcode (ABGFY) the password.
01 Ocak 2016
www.hedefsan.net 6
EXIT MENU
Exit menu Press EXIT button to exit the menu. By pressing ENTER when you see
(ENTER) “EXIT MENU” you can exit the menu screen
LANGUAGE SETTINGS
LIFT TYPE
Single Speed Choose this setting for single speed roped elevators.
Double Speed Choose this setting for double speed roped elevators.
Continous gear (with asynchronous machine) and gearless (with
Roped VVVF
synchronous machine)
Hydraulic Choose this setting for hydraulic elevators
COMMAND TYPE
01 Ocak 2016
www.hedefsan.net 7
NUMBER OF STOP
NUMBER OF BASEMENT
DOOR TYPE
Aut. Unlimited Sadece otomatik limitli kabin kapısı bulunan asansörlerde kullanılır
Full Aut. Unlimited Tam otomatik limitli kapısı bulunan asansörlerde kullanılır.
Full Aut. limited Tam otomatik limitsiz kapısı bulunan asansörlerde kullanılır.
According to the EN 81-1/2 standarts in states of emergency stop, revision and take back automatic
doors must remain stationary
01 Ocak 2016
www.hedefsan.net 8
BUSY TIME
5 - 20 Seconds Set the cabin light delay time between the minimum and maximum.
According to the EN 81-1/2 standarts it is not allowed to bypass the cabin light delay.
On elevators with simple command (non-collective) this parameter must me equal to the “WAIT AT
STOP” time. And the busy time must be at least 2 seconds.
07: Lock waiting Set the maximum time to wait for the door lock signal (140) after
008 Seconds getting the door closed signal.
8 - 30 Seconds Set the lock waiting time between the minimum and maximum
WAIT AT STOP
08: Waiting Time at Floor Set the waiting time before going to other registrations while
008 Seconds collecting.
3 - 15 Seconds Set the waiting time at floor between the minimum and maximum.
According to the EN81-1 and EN81-2 standarts, elevators with manual doors must have a waiting
time of al least 2 seconds when moving again after reaching its floor
On elevators with simple command (non-collective) this parameter must me equal to the “CABIN
LIGHT” time and must be at least 2 seconds.
01 Ocak 2016
www.hedefsan.net 9
5 - 120 Seconds Set the fast cruising time between the minimum and maximum.
According to the EN81-1 / 2 standards motor operation time work must not exceed the smaller of
the following:
45 seconds
Longest cruising distance +10 seconds
If longest cruising distance is less than 10 seconds, the timeout should be at least 20 seconds.
5 - 60 Seconds Set the slow cruising time between the minimum and maximum.
GO TO PARK TIME
0 - 250 Seconds Set the waiting time between the minimum and maximum.
01 Ocak 2016
www.hedefsan.net 10
PARK STOP
13: Park stop Set the park stop here. When elevator pauses its operation,it goes to this
05 floor and waits with open doors.
FIRE STOP
Set here the fire stop. When Fire input (at SIDE) is active the elevator
14: Fire Stop
goes to the defined floor directly and waits with its doors open.
01 Elevator will return to normal operation mode when fire signal is over.
This is the minimum and maximum time that is waited before going to
0 - 250 Seconds
park stop.
Cancel Fire stop is not defined in the system.
1 – 16 Fire stop is defined in the system.
ARROW FLASH
CHANGE PASSWORD
CANCEL PASSWORD
01 Ocak 2016
www.hedefsan.net 11
MAINTENANCE DONE
Maintenance done ! You can reset your maintenance time by pressing the enter key.
MAINTENANCE TIME
For every day the card operates the value of this parameter drops by
one. For example, if it is set for 45 days, this parameter will show a
19: Maintenance time value of 15 when 30 days have passed. After 45 days the value will be
0.
45 - 250 days Set the maintenance time between the minimum and maximum.
ERROR LIST
Here you can view the last 20 errors with their stop names, starting
20: Error list
with the last error. When reaching the first error, an option to delete
817 Doesn’t come the errors pops up. You can delete all errors by pressing ENTER.
DIGITAL SETTING
21:Digital setting
When the floor number is blinking, set the floor number with the
UPDOWN buttons till you come to the floor number you want to
change.Press the ENTER button and next you will see the digits
16
Indicator type
blinking. Set the value you like. When finished exit with the exit
button. Or if you want to set another stop/floor, press the enter
button, when floor number is blinking, repeat the steps.
01 Ocak 2016
www.hedefsan.net 12
RESCUE
DUPLEX SETTING
24:Duplex seçimi Set here the group ID of the control panel during the group operation.
A panel Group IDs A, B, C, D, E, or F can be used. The identity of each lift must
be different. Priority when in the same distance is given to the elevator
with the lowest group identity
A-B-C-D-E-F
CALL TRANSFER
If the elevator operates in group and external calls are connected to a
25:Call transfer
single panel, this paremeter should be ACTIVE, in other cases it should
Active be cancelled.
PHASE PROTECTION
01 Ocak 2016
www.hedefsan.net 13
PTC
27:Ptc
Choose the PTC motor thermistor input setting.
Aktif
ACTIVE Activates it
CANCEL Deactivates it.
28: Cabin Serial Card Activate this parameter when the serial communication card is
Active connected.
When this parameter is cancelled the serial communication continues but only the floor inputs and other
inputs will be canceled.
05 – 20 Seconds Set the door open-close time between the minimum and maximum
30:One door full On elevators with swing doors, set this parameter when there’s only
automatic one full automatic door.
01 Ocak 2016
www.hedefsan.net 14
When limit switches are enabled the elevator will stop before reaching
Until Limit switch
its floor.
Until Floor Even when limit switches are enabled the elevator will go to its floor.
39: Target floor display flash When this parameter is activated, the floor display flashes the number
Active of the target floor at each stop while moving down or up the shaft.
DISPLAY OUTPUT
40: Display output Set the display output of the HD One X S controller card and HD Seri
7 segment output card.
01 Ocak 2016
www.hedefsan.net 15
SAFETY DELAY
42: Safety delay Here set up the time to delay the movement of the elevator after the
0120 safety circuits 130 and 140 signals.
0000 – 1000 Milliseconds Set the safety delay time between the minimum and maximum.
COUNTER TYPE
46: Photocell waiting time Set the time of waiting for the photocell signal to close the door after
003 seconds the opening of the automatic door.
01 – 05 seconds Set the photocell waiting time between the minimum and maximum.
01 Ocak 2016
www.hedefsan.net 16
CONTACT FEEDBACK
Here the contactor feedback error delay is cancelled or activated. If
47: Contact Feedback
cancelled the controller card can't perceive any contactor adhesions.
Active Therefore, if it is canceled our company is not responsible.
49: Aut.Door.At.Park Set the open or closed position of the automatic door when waiting at
Wait closed park.
POSITION RESET
Even when there’s a power blackout the controller card will remember
50:Position reset its last position. But in some special cases when the power returns, a
Cancel position reset may be wanted. In that case the elevator will go until it
reaches the 817 limit switch of the bottom floor. When it reaches the
bottom floor, the floor counter will reset. For example: with systems
that have battery charged rescuers, this parameter can be activated to
reset the position.
ACTIVE Position reset is activated.
CANCEL Position reset is canceled.
GONG SOUND
56:Gong sesi
It activates or cancels the gong sound in serial communication.
Active
01 Ocak 2016
www.hedefsan.net 17
LCD CONTRAST
FACTORY SETTINGS
64: Factory settings Here you can cancel your settings and return to factory settings.
ERROR LIST
01 STOP INTERRUPTED
02 PLUG INTERRUPTED
03 LOCK INTERRUPTED
04 CONTACT FEEDBACK ERROR
05 PTC ERROR
06 COUNTER ERROR
07 DISTANCE PASSING FLOOR STOPPER ERROR
08 LOCK NOT REALIZED
09 PLUG NOT REALIZED
10 NO LOWER/UPPER LIMIT
11 R - PHASE ERROR
12 S - PHASE ERROR
13 T - PHASE ERROR
14 PHASES GONE
15 LOW VOLTAGE
16 INVOLUNTARY MOVEMENT (PRESS EXIT BUTTON FOR 60 SECONDS TO EXIT ERROR SCREEN)
17 MANUAL BRAKE ERROR (PRESS EXIT BUTTON FOR 60 SECONDS TO EXIT ERROR SCREEN)
18 REVERSE DIR. MOVEMENT (PRESS EXIT BUTTON FOR 60 SECONDS TO EXIT ERROR SCREEN)
PUT INTO APPROPRIATE POSITION (THIS ERROR APPEARS IF READING OF 817 OR 818 IS
19
INTERRUPTED)
20 NO PULSE OF ENCODER (ENCODER DOESN’T COUNT)
21 ML SHORT CIRCUIT (PRESS EXIT BUTTON FOR 60 SECONDS TO EXIT ERROR SCREEN)
01 Ocak 2016
www.hedefsan.net 18
192 mm
LCD Display
Settings Buttons
Mika Hole
257 mm
267 mm
Mika
35 mm
27 mm
Main Controller
260 mm
01 Ocak 2016